| 2013-04-16 14:24:48 | 701 SOUTH ROSEMARY AVENUE - #137 |
| | PERMIT #13040438 |
| | SEE ALSO PERMIT #13040437 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NOTE: ALL FIRE REVIEW COMMENTS REFERENCING NFPA 101 |
| | REFER TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION |
| | WITH FLORIDA AMENDMENTS.) |
| | |
| | |
| | THE PERMIT APPLICATION INDICATES THE PROJECT ADDRESS AS |
| | 701 SOUTH ROSEMARY AVENUE SUITE #137; HOWEVER, THE |
| | ARCHITECTURAL AND MEP SHEETS INDICATE AN ADDRESS OF 700 |
| | SOUTH ROSEMARY AVENUE SUITE #A13. PLEASE COORDINATE THE |
| | CORRECT ADDRESS. |
| | |
| | SHEET A0.10: UPDATE THE CODE LIST TO REFERENCE THE 2010 |
| | EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH |
| | CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 |
| | WITH FLORIDA AMENDMENTS. |
| | |
| | SHEET A0.30: PROVIDE TACTILE SIGNAGE AT ALL REAR EXIT |
| | DOORS WITH EXIT SIGNS. |
| | |
| | SHEET A2.10: TRAVEL DISTANCE TO REAR FIRE EXTINGUISHER |
| | SHALL NOT EXCEED 75 FEET. |
| | |
| | SHEET A2.10: DOOR #112 SWINGS AGAINST THE FLOW OF |
| | TRAFFIC AND SERVES MORE THAN 50 PERSONS. |
| | |
| | SHEET M-1: NO FIRE DAMPER PROVIDED IN DUCTWORK |
| | PENETRATING STOCK ROOM #113. |
| | |
| | GENERAL: PROVIDE DRAWING NOTE INDICATING ALL |
| | CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE |
| | REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS |
| | SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | GENERAL: PROVIDE DRAWING NOTE INDICATING, ?FIRE |
| | PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND |
| | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| | 500 NORTH DIXIE HIGHWAY.? |
| | |
| | GENERAL: EACH FIRE BARRIER SHALL BE PERMANENTLY |
| | IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE |
| | BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT |
| | LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. |
| | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON |
| | CENTER. |
| | |
| | GENERAL: FOR ISSUANCE OF A GENERAL BUILDING PERMIT, |
| | SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING CODE |
| | REQUIRES SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS |
| | FOR THE DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC |
| | FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE CODE |
| | SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING |
| | DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE |
| | WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS |
| | APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD |
| | OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM |
| | TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP |
| | DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED |
| | INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. |
| | |
| | GENERAL: NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED. |
| | PER FBC SECTION 907.1.1 CONSTRUCTION DOCUMENTS - |
| | "CONSTRUCTION DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE, THE |
| | FLORIDA FIRE PREVENTION CODE, AND RELEVANT LAWS, |
| | ORDINANCES, RULES AND REGULATIONS, AS DETERMINED BY THE |
| | BUILDING OFFICIAL." |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |