Plan Review Details - Permit 13040438
Plan Review Stops For Permit 13040438
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-05-08 Cont ID  
Sent By jwitmer Date 2013-05-08 Time 07:53 Rev Time 0.00
Received By jwitmer Date 2013-05-08 Time 07:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-04-13 Cont ID  
Sent By jwitmer Date 2013-04-13 Time 13:00 Rev Time 0.00
Received By jwitmer Date 2013-04-13 Time 11:38 Sent To  
Notes
2013-04-13 12:02:08BUILDING PLAN REVIEW
 PERMIT: 13040438
 ADD: 701 S ROSEMARY AVE SUITE 137 TENANT BUILD-OUT
 CONT: TBD
 TEL: (561)856-6655
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: APRIL 13/ 2013
 ACTION: DENIED
  
 1) THE TENANT BUILD-OUT PLAN UNDER PERMIT # 13040438
 AND LANDLORD TENANT SEPERATION WALL / STORAGE UNDER
 PERMIT (13040437) HAS A DISCREPANCY AS TO WHERE THE
 TENANT SEPERATION WALL AND DOORWAY ARE LOCATED AND THE
 SHARED EXIT PASSAGE WAY BEGIN. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2) SHEET A0.30 THE ACCESSIBLE DRESSING ROOM DOOR SHALL
 NOT SWING INTO THE CLEAR FLOOR SPACE (60 INCH TURNING
 SPACE) SEE 2010 FL ACCESSIBILITY CODE SECTIONS, 803.3
 DOOR SWING AND 803.2 TURNING SPACE.
  
 3) THE BENCH THAT IS LOCATED IN THE ACCESSIBLE DRESSING
 ROOM FOUND ON A0.30 AND DETAILED ON A9.33 DOES NOT
 INDICATE THAT IT IS ATTACHED TO THE WALL OR PROVIDING
 BACK SUPPORT PER SECTION 2010 FL ACCESS CODE 903.4 .
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-05-21 Cont ID  
Sent By dharvey Date 2013-05-21 Time 09:36 Rev Time 0.00
Received By dharvey Date 2013-05-21 Time 09:36 Sent To  
Notes
2013-05-21 09:36:405-21-13
  
 CORRECTIONS MADE TO MEET CODE
 VB

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-04-24 Cont ID  
Sent By dharvey Date 2013-04-24 Time 07:34 Rev Time 0.00
Received By dharvey Date 2013-04-24 Time 07:23 Sent To  
Notes
2013-04-24 07:33:26PROVIDE DETAILS OF TRANSFORMER MOUNTING AND SUPPORT,
 INCLUDING CLEARANCES
 TIE TRANSFORMER TO BUILDING GROUNDING ELECTRODE SYSTEM
 (GES) PER NEC 250
 TRANSFORMER GROUNDING AND CONNECTIONS TO BE PER 250.30
 LOAD CALCULATIONS SHOW NO MOTOR LOADS, AHU IS A MOTOR,
 IS ANYTHING ELSE NOT SHOWN?
 LL PLAN SHOWS HEAT IN EXCESS OF AC, IS HEAT IN THE LOAD
 CALC AS AIR CONDITIONING?
 AIC CALCULATION SOWS SINGLE CONDUCTOR USED FOR THE
 CALCULATIONS WHILE THE VOLTAGE IS SYSTEM VOLTAGE?
 TIME CLOCK MUST RETAIN PROGRAMMING FOR AT LEAST 10
 HOURS (BATTERY BACKUP) FLORIDA ENERGY CODE 505.2.4

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-05-18 Cont ID  
Sent By wjolin Date 2013-05-18 Time 19:43 Rev Time 0.00
Received By wjolin Date 2013-05-18 Time 19:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-04-16 Cont ID  
Sent By wjolin Date 2013-04-16 Time 14:24 Rev Time 0.00
Received By wjolin Date 2013-04-16 Time 13:32 Sent To  
Notes
2013-04-16 14:24:48701 SOUTH ROSEMARY AVENUE - #137
 PERMIT #13040438
 SEE ALSO PERMIT #13040437
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: ALL FIRE REVIEW COMMENTS REFERENCING NFPA 101
 REFER TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION
 WITH FLORIDA AMENDMENTS.)
  
  
 THE PERMIT APPLICATION INDICATES THE PROJECT ADDRESS AS
 701 SOUTH ROSEMARY AVENUE SUITE #137; HOWEVER, THE
 ARCHITECTURAL AND MEP SHEETS INDICATE AN ADDRESS OF 700
 SOUTH ROSEMARY AVENUE SUITE #A13. PLEASE COORDINATE THE
 CORRECT ADDRESS.
  
 SHEET A0.10: UPDATE THE CODE LIST TO REFERENCE THE 2010
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 SHEET A0.30: PROVIDE TACTILE SIGNAGE AT ALL REAR EXIT
 DOORS WITH EXIT SIGNS.
  
 SHEET A2.10: TRAVEL DISTANCE TO REAR FIRE EXTINGUISHER
 SHALL NOT EXCEED 75 FEET.
  
 SHEET A2.10: DOOR #112 SWINGS AGAINST THE FLOW OF
 TRAFFIC AND SERVES MORE THAN 50 PERSONS.
  
 SHEET M-1: NO FIRE DAMPER PROVIDED IN DUCTWORK
 PENETRATING STOCK ROOM #113.
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING ALL
 CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING, ?FIRE
 PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.?
  
 GENERAL: EACH FIRE BARRIER SHALL BE PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 GENERAL: FOR ISSUANCE OF A GENERAL BUILDING PERMIT,
 SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING CODE
 REQUIRES SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS
 FOR THE DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC
 FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE CODE
 SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 GENERAL: NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED.
 PER FBC SECTION 907.1.1 CONSTRUCTION DOCUMENTS -
 "CONSTRUCTION DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE, THE
 FLORIDA FIRE PREVENTION CODE, AND RELEVANT LAWS,
 ORDINANCES, RULES AND REGULATIONS, AS DETERMINED BY THE
 BUILDING OFFICIAL."
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-21 Cont ID  
Sent By dharvey Date 2013-05-21 Time 09:37 Rev Time 0.00
Received By dharvey Date 2013-05-21 Time 09:37 Sent To  
Notes
2013-05-21 08:30:51C-33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-26 Cont ID  
Sent By lmartine Date 2013-04-24 Time 13:50 Rev Time 0.00
Received By lmartine Date 2013-04-12 Time 10:09 Sent To  
Notes
2013-04-12 10:09:46INCOMING SENT TO B-18, "EXPEDITED". JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-05-08 Cont ID  
Sent By jwitmer Date 2013-05-08 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2013-05-08 Time 07:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-04-23 Cont ID  
Sent By hmoser Date 2013-04-23 Time 13:56 Rev Time 0.00
Received By hmoser Date 2013-04-23 Time 11:37 Sent To  
Notes
2013-04-23 13:56:34PLANS DENIED
 1) MECHANICAL PLANS AND LANDLORD'S PLAN PERMIT #
 13040437 DO NOT MATCH.
 FIRE DAMPERS ON LANDLORD'S PLAN SHOW NEW, MECHANICAL
 PLAN SHOW EXISTING.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-04-19 Cont ID  
Sent By lwagner Date 2013-04-19 Time 09:39 Rev Time 0.00
Received By lwagner Date 2013-04-19 Time 09:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2013-05-20 Cont ID  
Sent By eschneid Date 2013-05-20 Time 15:42 Rev Time 0.25
Received By eschneid Date 2013-05-20 Time 15:42 Sent To  
Notes
2013-05-20 15:58:25SEPARATE PERMITS REQUIRED FOR STOREFRONT AND SIGNAGE.

Review Stop Z ZONING
Rev No 1 Status F Date 2013-04-18 Cont ID  
Sent By eschneid Date 2013-04-18 Time 14:27 Rev Time 0.50
Received By eschneid Date 2013-04-18 Time 14:27 Sent To  
Notes
2013-04-18 14:28:53FAILED
  
 INCORRECT ADDRESS OF 700 S. ROSEMARY ON THE PLANS.
  
 SEPARATE PERMITS FOR STOREFRONT AND SIGNS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.