Plan Review Details - Permit 13040367
Plan Review Stops For Permit 13040367
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-06-28 Cont ID  
Sent By rmcdouga Date 2013-06-28 Time 12:48 Rev Time 0.00
Received By rmcdouga Date 2013-06-28 Time 08:38 Sent To  
Notes
2013-06-28 12:52:23A REVISION IS REQUIRED
  
 SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR EXPOSURE CATEGORY D FOR THE TAMKO
 BUILT UP ROOF FL741-R6 (NOA NO.12-0601.10

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-30 Cont ID  
Sent By rmcdouga Date 2013-05-30 Time 08:22 Rev Time 0.00
Received By rmcdouga Date 2013-05-30 Time 07:29 Sent To  
Notes
2013-05-29 15:38:572010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE WITH A
 REQUIRED MINIMUM FINISH FLOOR ELEVATION OF 7.5 FEET. AN
 ELEVATION CERTIFICATE WILL BE REQUIRED. FBC R322.1
  
 2) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORMS. FBC ENERGY 405.4
  
 3) SPECIFY THE FASTENING OPTION, DESIGN PRESSURE THAT
 WILL BE USED ON THE PRODUCT APPROVAL FOR THE BUILT UP
 ROOFING FL 741-R6 (NOA 12-0601.12). SUBMIT SIGNED AND
 SEALED RAS 117 CALCULATIONS FOR ENHANCED FASTENING AT
 THE PERIMETER AND CORNER ROOF AREAS. SEE LIMITATION #7
 OF THE NOA. DCA RULE 9N-3 AND FBC R905.1
  
 4) SPECIFY THE DESIGN PRESSURE, ANCHOR TYPE, ANCHOR
 SPACING, EDGE DISTANCE, SPAN, ETC. BY CIRCLING THE
 APPROPRIATE ITEMS IN THE TABLES ON PAGES 5-7 OF THE
 STORM PANEL PRODUCT APPROVAL DRAWINGS OR ON AN
 INSTALLATION SCHEDULE. FBC R301.2.1.2
  
 5) SUBMIT THE PRODUCT EVALUATION REPORT FOR THE ICYNENE
 SPRAY FOAM INSULATION. FBC R316
  
 NOTE: A SEPARATE PERMIT, APPLICATION AND REVIEW IS
 REQUIRED FOR A POOL PERMIT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-28 Cont ID  
Sent By rmcdouga Date 2013-06-28 Time 10:33 Rev Time 0.00
Received By rmcdouga Date 2013-06-28 Time 10:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-16 Cont ID  
Sent By dharvey Date 2013-05-16 Time 13:37 Rev Time 0.00
Received By dharvey Date 2013-05-16 Time 13:37 Sent To  
Notes
2013-05-16 13:41:165-16-13
  
 1. PER NEC 406.11, ALL REQUIRED RECEPTACLES MUST BE
 TAMPER RESISTANT
 2. PER NEC 680.74, BOND ALL METAL PIPING AND PARTS IN
 CONTACT WITH WATER AND CIRCULATOR PUMP
 3. PER NEC 680.22B. POOL EQUIPMENT CIRCUIT, AS SHOWN IN
 L-26/28, MUST USE GFCI BREAKER
 VB

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-05-22 Cont ID  
Sent By rmcdouga Date 2013-05-22 Time 08:26 Rev Time 0.00
Received By rmcdouga Date 2013-05-22 Time 08:26 Sent To  
Notes
2013-05-22 08:44:05****PROVISO****
  
 ELECTRICAL BONDING
 310.1.1 CSST. CORRUGATED STAINLESS STEEL TUBING (CSST)
 GAS PIPING SYSTEMS SHALL BE BONDED TO THE ELECTRICAL
 SERVICE GROUNDING ELECTRODE SYSTEM AT THE POINT WHERE
 THE GAS SERVICE ENTERS THE BUILDING. THE BONDING JUMPER
 SHALL BE NOT SMALLER THAN 6 AWG COPPER WIRE OR
 EQUIVALENT.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2013-06-28 Cont ID  
Sent By rmcdouga Date 2013-06-28 Time 12:55 Rev Time 0.00
Received By rmcdouga Date 2013-06-28 Time 12:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-30 Cont ID  
Sent By rmcdouga Date 2013-05-30 Time 08:22 Rev Time 0.00
Received By rmcdouga Date 2013-04-10 Time 12:58 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2013-05-21 Cont ID  
Sent By rmcdouga Date 2013-05-21 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2013-05-21 Time 16:23 Sent To  
Notes
2013-05-21 16:35:49MU-2013-7279

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-05-23 Cont ID  
Sent By hmoser Date 2013-05-23 Time 08:29 Rev Time 0.00
Received By hmoser Date 2013-05-23 Time 08:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-05-22 Cont ID  
Sent By rmcdouga Date 2013-05-22 Time 08:25 Rev Time 0.00
Received By rmcdouga Date 2013-05-22 Time 06:51 Sent To  
Notes
2013-05-22 08:26:48REDLINED PLANS FOR MISSING WATER LINES TO LAUNDRY SINK.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2013-06-28 Cont ID  
Sent By rmcdouga Date 2013-06-28 Time 12:55 Rev Time 0.00
Received By rmcdouga Date 2013-06-28 Time 12:55 Sent To  
Notes
2013-06-28 13:22:26FLAT ROOF: (NEEDS RAS 117 CALCS FOR EXPOSURE D)
 FL741-R6 BUR (NOA NO.12-0601.10)
  
 SLOPE ROOF: FL601-R8 (NOA NO.12-0904.07) CONCRETE TILE
 / FL717-R4 (11-0616.03) TILE BOND ADHESIVE

Review Stop Z ZONING
Rev No 1 Status P Date 2013-05-10 Cont ID  
Sent By mdekle Date 2013-05-10 Time 15:48 Rev Time 0.00
Received By ajones Date 2013-05-10 Time 15:48 Sent To  
Notes
2013-04-23 09:47:374/23/13