Plan Review Details - Permit 13040324
Plan Review Stops For Permit 13040324
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-06-11 Cont ID  
Sent By rmcdouga Date 2013-06-11 Time 10:09 Rev Time 0.00
Received By rmcdouga Date 2013-06-11 Time 07:00 Sent To  
Notes
2013-06-11 10:04:45BUILDING PROVISO
  
 PROVIDE TWO COPIES OF THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND LISTING INFORMATION FOR THE OUTDOOR
 BBQ. TO THE FIELD INSPECTOR. FBCR M1901.2 & FBCR
 G2408.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-07 Cont ID  
Sent By rmcdouga Date 2013-05-07 Time 12:07 Rev Time 0.00
Received By rmcdouga Date 2013-04-26 Time 13:55 Sent To  
Notes
2013-05-06 16:46:492010 FBC
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF A SURFACE WATER DRAINAGE PLAN
 THAT SHOWS COMPLIANCE WITH FBCR 401.3.
  
 2) SUBMIT 2 SETS OF SIGNED AND SEALED SUBSURFACE SOIL
 REPORTS. FBCR 401.4
  
 3) FBCR 302.1 REQUIRES EXTERIOR WALLS LOCATED ON A ZERO
 LOT LINE TO HAVE A FIRE RESISTANCE RATING OF ONE HOUR.
 SUBMIT TESTING REPORTS AND SPECIFICATIONS SHOWING THAT
 THE GLASS BLOCK PANEL WALL SYSTEM THAT IS PROPOSED FOR
 THIS WALL HAS A ONE HOUR FIRE RESISTANCE RATING IN
 ACCORDANCE WITH ASTM E 119 OR UL 263 WITH EXPOSURE FROM
 BOTH SIDES.
  
 4) THE VALUE OF $ 243,980.00 APPEARS TO BE
 UNDER-ESTIMATED FOR THIS PROJECT. PER CITY AMENDMENTS
 109.3, FOR PERMITTING PURPOSES THE VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. THE VALUE WILL BE CHANGED TO
 $513920.00 BASED ON LATEST ICC BUILDING VALUATION DATA.
  
 5) SUBMIT TWO COPIES OF THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND LISTING INFORMATION FOR THE OUTDOOR
 BBQ. FBCR M1901.2 & FBCR G2408.1
  
 6) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 ONE HOUR FIRE-RATED GLASS BLOCK, THE PRE-CAST LINTELS
 AND THE SIMPSON MBHU GIRDER TRUSS HANGER AS REQUIRED BY
 DCA RULE 9N-3.
  
 7) THE DESIGNER OF RECORD IS REQUIRED TO REVIEW AND
 APPROVE THE PRODUCT APPROVALS IN WRITING. CITY
 AMENDMENT 107.3.4.1
  
 8) SPECIFY THE EMBED DEPTH / LENGTH OF THE 3/4"
 DIAMETER ANCHOR BOLTS FOR THE DOUBLE 2 X 10 LEDGER AND
 THE THREE MEMBER GIRDER SHOWN IN DETAIL 2 ON S-2. CITY
 AMENDMENTS 107.2.1
  
 9) THE ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS HAVE THE WRONG ORIENTATION. THE FRONT DOOR
 OF THE STRUCTURE FACES EAST NOT SOUTHWEST AS SHOWN IN
 THE CALCULATIONS. PLEASE REVISE. FBC ENERGY 405.4 AND
 CITY AMENDMENTS 107.2.1
  
 10) THE UPLIFT PRESSURES FOR THE ROOF LISTED ON THE
 COVER SHEET ARE TOO LOW FOR A TWO STORY STRUCTURE
 LOCATED IN EXPOSURE CATEGORY C WITH A 170 MPH ULTIMATE/
 132 MPH ASD WINDSPEED. PLEASE REVISE. FBC R301.2.1
  
 11) THE ARCHITECTURAL AND ELECTRICAL DRAWINGS SHOW
 THREE (3) A/C SYSTEMS AND THE MECHANICAL PLANS SHOW TWO
 (2). PLEASE COORDINATE THE DRAWINGS. CITY AMENDMENTS
 107.2.1
  
 NOTE: WHEN RESUBMITTING PLEASE PROVIDE A RESPONSE
 LETTER INDICATING HOW EACH OF THE REVIEW COMMENTS HAS
 BEEN ADDRESSED.
  
  
 TRUSS DRAWING REVIEW DENIED BY BUILDING
  
 1) THE ORIGINAL WET SIGNATURE OF THE TRUSS ENGINEER AS
 WELL AS HIS SEAL IS REQUIRED ON THE TRUSS LAYOUT AND
 THE TRUSS DRAWINGS PER FS 471.025 AND FAC 61G15-23.002.
  
 2) THE STRUCTURAL DESIGNER OF RECORD IS REQUIRED TO
 REVIEW AND APPROVE THE TRUSS DRAWINGS AND LAYOUT.
 61G15-31.003
  
 3) THE UPLIFT AT THE CENTER BEARING POINT OF TRUSS P06
 IS -2323 PSF, WHICH EXCEEDS THE SPECIFIED ANCHOR
 CAPACITY ON THE STRUCTURAL PLANS. PLEASE REVIEW AND
 CORRECT. CITY AMENDMENTS 107.2.1 AND FBC R802.1.6.5
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-11 Cont ID  
Sent By rmcdouga Date 2013-06-11 Time 08:35 Rev Time 0.00
Received By rmcdouga Date 2013-06-11 Time 07:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-07 Cont ID  
Sent By rmcdouga Date 2013-05-07 Time 15:07 Rev Time 0.00
Received By rmcdouga Date 2013-05-07 Time 15:07 Sent To  
Notes
2013-05-07 15:06:572010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) THE CONDUCTORS BETWEEN THE METER AND THE MAIN
 CIRCUIT IS REQUIRED TO BE 2/0 PER NEC 310.15 (B) (6).
  
 2) ALL RECEPTACLES WITHIN 6 FT OF A WET BAR SINK OR A
 LAUNDRY SINK ARE REQUIRED TO BE GFCI. THE EXCEPTIONS
 ONLY APPLY TO KITCHENS. PER NEC 210.8 (A) (7).
  
 3) THE ELECTRICAL PLANS AND PANEL SCHEDULES SPECIFY
 THREE A/C SYSTEMS AND THE MECHANICAL PLANS ONLY SHOW
 TWO. PLEASE REVISE PLANS TO MATCH. CITY AMENDMENTS
 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2013-06-11 Cont ID  
Sent By rmcdouga Date 2013-06-11 Time 08:06 Rev Time 0.00
Received By rmcdouga Date 2013-06-11 Time 08:06 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-05-07 Cont ID  
Sent By rmcdouga Date 2013-05-07 Time 15:47 Rev Time 0.00
Received By rmcdouga Date 2013-05-07 Time 15:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-11 Cont ID  
Sent By rmcdouga Date 2013-06-11 Time 10:09 Rev Time 0.00
Received By rmcdouga Date 2013-05-30 Time 11:58 Sent To  
Notes
2013-06-01 12:00:09*EXPEDITED*
 GAVE TO HAROLD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-10 Cont ID  
Sent By jwitmer Date 2013-05-10 Time 16:36 Rev Time 0.00
Received By jwitmer Date 2013-04-09 Time 16:36 Sent To  
Notes
2013-04-10 16:36:58SENT TO R6 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2013-04-26 Cont ID  
Sent By rmcdouga Date 2013-04-26 Time 14:55 Rev Time 0.00
Received By rmcdouga Date 2013-04-26 Time 14:55 Sent To  
Notes
2013-04-26 14:56:31MU-2013-7364

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-06-03 Cont ID  
Sent By hmoser Date 2013-06-03 Time 14:09 Rev Time 0.00
Received By hmoser Date 2013-06-03 Time 13:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-04-19 Cont ID  
Sent By hmoser Date 2013-04-19 Time 11:01 Rev Time 0.00
Received By hmoser Date 2013-04-18 Time 15:07 Sent To  
Notes
2013-04-25 11:13:24****CORRECTIONS****
  
 1. PROVIDE MANUFACTURER SPECIFICATIONS FOR THE OUTDOOR
 GRILL; A HOOD MAY BE REQUIRED FBC M 1503.1.
  
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-06-11 Cont ID  
Sent By rmcdouga Date 2013-06-11 Time 08:15 Rev Time 0.00
Received By rmcdouga Date 2013-06-11 Time 08:15 Sent To  
Notes
2013-06-11 08:33:22THE PLUMBING RISER HAS BEEN REDLINED AND PASSED
 PROVISIONALLY. A CORRECTED RISER DIAGRAM IS REQUIRED TO
 BE SUBMITTED FOR REVIEW AS A REVISION PRIOR TO FINAL
 PLUMBING INSPECTION.

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-05-06 Cont ID  
Sent By rmcdouga Date 2013-04-26 Time 13:55 Rev Time 0.00
Received By rmcdouga Date 2013-04-26 Time 13:55 Sent To  
Notes
2013-05-06 16:46:102010 FBC
  
 DENIED BY PLUMBING
  
 1) THE FIRST FLOOR POWDER ROOM IS NOT SHOWN ON THE
 PLUMBING RISER DIAGRAM ON SHEET A-6. THE PLUMBING RISER
 IS REQUIRED TO CORRESPOND WITH THE ARCHITECTURAL
 DRAWINGS. PLEASE CORRECT. CITY AMENDMENTS 107.2.1 &
 107.3.5
  
 2) AN EXTRA BAR SINK IS SHOWN ON THE PLUMBING RISER
 DIAGRAM ON SHEET A-6 AT THE LOCATION OF THE FIRST FLOOR
 POWDER ROOM. PLEASE CORRECT. CITY AMENDMENTS 107.2.1 &
 107.3.5
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2013-06-06 Cont ID  
Sent By rmcdouga Date 2013-06-06 Time 15:44 Rev Time 0.00
Received By rmcdouga Date 2013-06-06 Time 15:44 Sent To  
Notes
2013-06-06 15:44:37ENTEGRA, ESTATE "S" TILE NOA NO. 11-0510.02 WITH 3M
 2-COMPONENT FOAM ROOF TILE ADHESIVE AH-160 NOA
 NO.12-0228.18 WERE SUBMITTED FOR THE ROOFING MATERIALS.

Review Stop Z ZONING
Rev No 1 Status P Date 2013-05-10 Cont ID  
Sent By mdekle Date 2013-05-10 Time 15:47 Rev Time 0.00
Received By ajones Date 2013-05-10 Time 15:47 Sent To  
Notes
2013-04-23 09:30:564/23/13


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved