Plan Review Details - Permit 13040318
Plan Review Stops For Permit 13040318
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-12 Cont ID  
Sent By hmoser Date 2013-04-12 Time 08:29 Rev Time 0.00
Received By hmoser Date 2013-04-09 Time 12:00 Sent To  
Notes
2013-04-11 12:01:14SENT TO HAROLD'S DESK FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-04-12 Cont ID  
Sent By hmoser Date 2013-04-12 Time 09:01 Rev Time 0.00
Received By hmoser Date 2013-04-12 Time 09:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-04-12 Cont ID  
Sent By hmoser Date 2013-04-12 Time 08:20 Rev Time 0.00
Received By hmoser Date 2013-04-12 Time 08:20 Sent To  
Notes
2013-04-12 08:29:13PLANS DENIED
 1) PROVIDE EQUIPMENT SCHEDULE ON PLANS.
 PER SECTION 107 FBC. 2010
 PROVIDE HEAT LOADS WITH THE PLANS.
 PER SECTION M1601.1 DUCT DESIGN.
 2010 RESIDENTIAL CODE.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676