Plan Review Details - Permit 13040312
Plan Review Stops For Permit 13040312
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-05-06 Cont ID  
Sent By dharvey Date 2013-05-06 Time 11:49 Rev Time 0.00
Received By dharvey Date 2013-05-06 Time 11:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-04-15 Cont ID  
Sent By dharvey Date 2013-04-15 Time 10:41 Rev Time 0.00
Received By dharvey Date 2013-04-15 Time 10:41 Sent To  
Notes
2013-04-15 10:41:49THE ELECTRICAL SERVICE MAINS MUST BE GROUPED IN ONE
 LOCATION. THE PRINCIPAL SAFETY RULE FOR ELECTRICAL
 SERVICES REQUIRES A BUILDING OR STRUCTURE TO HAVE ONE
 POINT OF SERVICE. NEC 230.2, 230.71, 230.72
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 ELECTRICAL SERVICE AND SWITCH GEAR. NEC 110.9, 110.10
  
 PROVIDE PROPER DOWNSTREAM RATINGS OF EQUIPMENT IN
 ACCORDANCE WITH THE FAULT CURRENT AND/OR PROVIDE PROPER
 SERIES RATINGS VALUES 240.4 (B) (C) (F), 240.12
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS.
 NEC 110.22, 110.16, 110.22
  
 GROUND FAULT PROTECTION EQUIPMENT (GFPE) IS REQUIRED
 FOR THE NEW ELECTRIC SERVICE. NEC 230.95, 240.13
  
 PROVIDE AND ILLUSTRATE THE SAFE WORKING CLEARANCES AND
 DEDICATED WORKING SPACE AT ALL ELECTRICAL PANEL BOARDS
 AND TRANSFORMERS. NEC 110.26, 240.24
  
 EQUIPMENT GROUNDING CONDUCTORS IN PARALLEL TO BE FULL
 SIZED 250.122 (F)
  
 HOW WILL EXISTING LIGHTING, 120V AND 240V EQUIPMENT BE
 MAINTAINED? PLAN INDICATES THIS EQUIPMENT IS TO REFED
 ?IN FUTURE? AND NOT AT THIS TIME.
  
 REVIEW INCOMPLETE BASED ON MISSING INFORMATION
  
 CONTRACTOR CALLED
 DOUG HARVEY [email protected] 561-805-6740
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-07 Cont ID  
Sent By shill Date 2013-05-07 Time 10:54 Rev Time 0.00
Received By shill Date 2013-04-29 Time 08:59 Sent To  
Notes
2013-04-30 08:59:32SENT TO ELECTRICAL BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-15 Cont ID  
Sent By dharvey Date 2013-04-15 Time 10:51 Rev Time 0.00
Received By dharvey Date 2013-04-09 Time 14:07 Sent To  
Notes
2013-04-11 14:07:37SENT TO ELECTRICAL SHELF FOR REVIEW. JG.