Plan Review Details - Permit 13040307
Plan Review Stops For Permit 13040307
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-06-03 Cont ID  
Sent By jgomez Date 2013-06-03 Time 11:14 Rev Time 0.00
Received By jgomez Date 2013-06-03 Time 11:14 Sent To  
Notes
2013-06-03 14:44:57BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- TRUSS PACKAGE:
 A) TRUSS ENGINEER TO PROVIDE ORIGINAL SIGNATURE (NOT
 COPY) IN ALL DRAWINGS WITH HIS SIGNATURE.
  
 B) TRUSS PACKAGE SUBMITTED DOESN'T COMPLY WITH SEC.
 61G15-31.003, EACH DRAWING SHALL HAVE A TITLE BLOCK
 WITH ENGINEER'S NAME, LICENSE, ADDRESS AND DATE OF THE
 DRAWING. AND, THE PAGES NEED TO BE NUMBERED TO MATCH
 INDEX SHEET.
  
 2- SHEET S-2:
 A) ENGINEER OF RECORD TO REVISE ALL THE CONNECTORS THAT
 DON'T MEET THE UPLIFT CALCULATIONS AS SHOWN ON THE
 TRUSS PACKAGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-04-29 Cont ID  
Sent By jgomez Date 2013-04-29 Time 15:54 Rev Time 0.00
Received By jgomez Date 2013-04-29 Time 15:54 Sent To  
Notes
2013-04-29 16:33:12NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- VALUATION SPECIFIED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION
 INCLUDES ALL THE LABOR, MATERIALS, OVERHEAD AND PROFIT
 AND DESIGN PROFESSIONALS FEES. VALUATION WAS UPDATED.
 PERMIT FEE BALANCE IS $4350.39.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) 1 HOUR FIRE RATED GLASS BLOCK ASSEMBLY AS REQUIRED
 ON THE ZERO LOT LINE WALL.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 C) SIMPSON MBHU GIRDER TRUSS HANGER AS SPECIFIED ON
 PLANS.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS TO FBC.
  
 4- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF 2010
 FBC-RESIDENTIAL.
  
 5- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING
 METHOD AND WIND UPLIFT AS REQUIRED BY SEC. 107.2.1.2
 CITY AMENDMENTS TO VERIFY COMPLIANCE WITH THE PRODUCT
 APPROVAL SUBMITTED.
 ***NOTE: COMPONENTS AND CLADDING UPLIFT PRESSURES
 SPECIFIED ON THE PLANS COVER SHEET ARE INCORRECT. THEY
 DON'T CORRESPOND TO EXPOSURE "C" AS REQUIRED BY SEC.
 R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. AND, CLARIFY WHY
 ROOF ZONE 2 AND 3 HAVE THE SAME UPLIFT PRESSURES.
 REVISE AS REQUIRED.
  
 6- PROVIDE DETAILS/SPECIFICATIONS SHOWING COMPLIANCE
 WITH THE FOOTING MINIMUM DEPTH AS REQUIRED BY SEC.
 R403.1.4 OF 2010 FBC- RESIDENTIAL AND THE CLEARANCE
 BETWEEN EXTERIOR WALL COVERING AND FINAL EARTH GRADE AS
 REQUIRED BY SEC. R704 OF 2010 FBC-RESIDENTIAL.
  
 7- PROVIDE MANUFACTURER SPECS FOR BBQ GRILL THAT IS
 DESIGNED AND LISTED TO BE INSTALLED IN A PORCH AS SHOWN
 ON PLANS. SEC. M1901.2 OF 2010-FBC-RESIDENTIAL.
  
 8- SURVEY SAYS PROPOSED 2 STORY RESIDENCE. PLANS SHOW
 ONE STORY. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 9- TRUSS PACKAGE:
 A) TRUSS ENGINEER TO PROVIDE ORIGINAL SIGNATURE (NOT
 COPY) AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES.
  
 B) TRUSS PACKAGE SUBMITTED DOESN'T COMPLY WITH SEC.
 61G15-31.003, IF ENGINEER WANTS TO USE A COVER SHEET
 INSTEAD OF SIGNING AND SEALING EACH INDIVIDUAL TRUSS
 SHEET. ENGINEER TO REVIEW THIS SECTION AND REVISE ALL
 THE TRUSS PACKAGE AS REQUIRED. NOTE: THERE IS AN
 ENGINEER OF RECORD ON THIS PROJECT.
  
 C) THE TRUSS PACKAGE NEEDS TO BE REVIEWED AND APPROVED
 BY THE ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-31.003. NOTE: J.A.O IS NOT THE ENGINEER OF
 RECORD.
  
  
 10- SHEET S-2:
 A) ENGINEER OF RECORD TO REVISE ALL THE SIMPSON
 CONNECTORS THAT DON'T MEET THE UPLIFT CALCULATIONS AS
 SHOWN ON THE TRUSS PACKAGE. COORDINATE WITH THE TRUSS
 PACKAGE AND REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 B) SIMPSON CONNECTOR LTA1 WAS DISCONTINUED BY SIMPSON.
 SPECIFY CURRENT CONNECTOR. SEC. 107.2.1 CITY AMENDMENTS
 TO FBC.
  
 11- THE CERTIFICATE OF AUTHORIZATION (#8495) FOR
 "DESIGN ENGINEERING & SUPPLY" ENGINEER FIRM NEEDS TO BE
 UPDATED. ENGINEER TO CONTACT DBPR AND UPDATE AS
 REQUIRED BY SEC. 61G15-23.002.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-03 Cont ID  
Sent By dharvey Date 2013-06-03 Time 09:52 Rev Time 0.00
Received By dharvey Date 2013-06-03 Time 09:52 Sent To  
Notes
2013-06-03 09:52:546-1-13
 CORRECTIONS MADE
 VB

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-06 Cont ID  
Sent By dharvey Date 2013-05-06 Time 15:40 Rev Time 0.00
Received By dharvey Date 2013-05-06 Time 15:40 Sent To  
Notes
2013-05-06 15:42:565-06-13
  
 1. CONDUCTORS IN NIPPLE BETWEEN METER AND 200A MCB
 SHOULD BE 2/0 PER 310.15.B.6
 2. COORDINATE ELECTRICL PANEL SCHEDULE WITH AC
 EQUIPMENT SCHEDULE. NOTHING MATCHES, INSTALL CORRECT
 BREAKERS
 3. ANY RECEPT WITHIN 6 FT OF WET SINK MUST BE GFI PER
 NEC 210.8.7. THERE ARE NO EXCEPTIONS LISTED.
 VB

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2013-06-03 Cont ID  
Sent By lwagner Date 2013-06-03 Time 08:46 Rev Time 0.00
Received By lwagner Date 2013-06-03 Time 08:38 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-05-01 Cont ID  
Sent By lwagner Date 2013-05-01 Time 10:57 Rev Time 0.00
Received By lwagner Date 2013-05-01 Time 10:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-03 Cont ID  
Sent By jgomez Date 2013-06-03 Time 16:08 Rev Time 0.00
Received By jgomez Date 2013-05-30 Time 11:30 Sent To  
Notes
2013-06-01 11:32:20*EXPEDITED*
 GAVE TO LARRY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-10 Cont ID  
Sent By ajones Date 2013-05-10 Time 15:46 Rev Time 0.00
Received By ajones Date 2013-04-09 Time 16:25 Sent To  
Notes
2013-04-10 16:25:53SENT TO R2 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2013-04-24 Cont ID  
Sent By jgomez Date 2013-04-24 Time 13:57 Rev Time 0.00
Received By jgomez Date 2013-04-24 Time 13:57 Sent To  
Notes
2013-04-24 13:59:18PAID MU-2013-007338. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-04-17 Cont ID  
Sent By hmoser Date 2013-04-17 Time 11:35 Rev Time 0.00
Received By hmoser Date 2013-04-17 Time 11:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-05-01 Cont ID  
Sent By lwagner Date 2013-05-01 Time 10:57 Rev Time 0.00
Received By lwagner Date 2013-05-01 Time 10:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-05-10 Cont ID  
Sent By ajones Date 2013-05-10 Time 15:46 Rev Time 0.00
Received By ajones Date 2013-05-10 Time 15:46 Sent To Z
Notes
2013-04-23 09:29:164/23/13