Plan Review Details - Permit 13040273
Plan Review Stops For Permit 13040273
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-06-28 Cont ID  
Sent By jgomez Date 2013-06-28 Time 14:30 Rev Time 0.00
Received By jgomez Date 2013-06-28 Time 14:30 Sent To  
Notes
2013-06-28 14:45:48BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- RAS 117 CALCULATIONS FOR FLAT ROOF: A) ENGINEER TO
 REVIEW SEC. 8.1 OF RAS 117 AND REVISE NAILING FOR FIELD
 ZONE #1. B) PROVIDE COMPLETE LAP & FIELD NAILING
 SPECIFICATIONS FOR PERIMETER AND CORNER AREAS. C)
 ENGINEER TO USE CURRENT ENGINEER SEAL.
 2- REVISE ENERGY CALCULATIONS AND PLANS TO MATCH:
 A)PROVIDE SPECIFICATIONS/DETAILS SHOWING HOW THE ATTIC
 AND CEILING ARE VENTED. INCLUDING THE NEW ADDITION. B)
 DOORS ON SHEET 3 OF 6. REVISE ORIENTATION TO MATCH
 PLANS.
 3- REVISE EXTERIOR WALL SECTION ON SHEET S.2. THERE IS
 NO TILE ROOF ON THIS PROJECT.
 4- REVISE CRAWL SPACE VENTILATION INFORMATION (SEE SEC.
 R408): A) MIN. NET AREA SHALL NOT BE LESS THAN 1S.F.
 PER 150S.F. (16"X8" DOESN'T COMPLY). B)SHOW LOCATION OF
 THE 3 VENTILATION OPENINGS. C) ACCESS PANEL SIZE SHOWN
 DOESN'T COMPLY WITH SEC. R408.4. D) NEED PANEL LOCATION
 WITHIN 3'-0" OF EACH CORNER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-05-31 Cont ID  
Sent By jgomez Date 2013-05-29 Time 15:44 Rev Time 0.00
Received By jgomez Date 2013-05-29 Time 15:44 Sent To  
Notes
2013-05-29 15:45:26RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- ENGINEER TO USE CURRENT ENGINEER SEAL AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES. NEW SEAL SAYS "LICENSE"
 NOT "CERTIFICATE" . PROVIDE NEW DRAWINGS WITH CURRENT
 SEAL.
  
 2- ACCORDING TO SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL, THIS BUILDING IS LOCATED ON EXPOSURE
 "C".
 A) THE DESIGN PRESSURES SPECIFIED ON THE WINDOW
 SCHEDULE ARE STILL TOO LOW FOR EXPOSURE "C" ON WINDOWS
 LOCATED IN THE WALL ZONE 5. REVISE AS REQUIRED.
 ***NOTE: SOME WINDOWS ARE LOCATED ON ZONE 5. SEE NOTE
 "A" ON FIGURE R301.2(7) OF 2010 FBC-RESIDENTIAL FOR
 MINIMUM "A" DIMENSION REQUIRED.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SIMPSON STRUCTURAL CONNECTORS CBSQ-SDS2. INFORMATION
 SUBMITTED ER-5952 IS NOT AN APPROVED FLORIDA PRODUCT
 APPROVAL. IF THERE IS NOT CURRENT PRODUCT APPROVAL,
 THEN MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL.
  
 B) FLAT ROOF: (1) ENGINEER TO REVIEW SEC. 8.1 OF RAS
 117 AND REVISE NAILING FOR FIELD ZONE #3 AS REQUIRED.
 (2) ENGINEER TO SPECIFY NAIL SPACING FOR THE LAP AND
 NUMBER OF ROWS AND SPACING FOR THE FIELD STAGGERED ROWS
 FOR PERIMETER AND CORNER AREAS. (3) ENGINEER TO USE
 CURRENT ENGINEER SEAL AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE.
  
 4- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 5- REVISE AND PROVIDE COMPLETE ENERGY CALCULATIONS
 SUBMITTED (SEC. 107.2.1 CITY AMENDMENTS TO FBC):
 A) THE AREA WEIGHTED AVERAGE OVERHANG DEPTH OF 7.720 FT
 ON ITEM #7 IS INCORRECT. TYPICAL OVERHANG ON THIS HOUSE
 IS 6" OR LESS. SEE EXTERIOR ELEVATIONS AND REVISE AS
 REQUIRED.
 ***NOTE: REVISE ALL THE WINDOWS WALL ORIENTATION,
 OVERHANG DEPTH AND SEPARATION, SQUARE FOOTAGE AND
 NUMBER OF WINDOWS/DOORS WITH GLAZING TO MATCH PLANS.
  
 B) PROVIDE COMPLETE SPECIFICATIONS AND DETAILS ON PLANS
 SHOWING HOW THE HOUSE COMPLIES WITH THE "CF" AND "CV"
 CREDITS TAKEN ON ITEM #15.
 ***NOTE: SEE TABLE 405.6.6 AND SEC. 405.6.4 OF 2010
 FBC-ENERGY CONSERVATION. AND REVISE CALCULATIONS AND
 PLANS AS REQUIRED.
  
 C) PROVIDE SPECIFICATIONS/DETAILS SHOWING HOW THE ATTIC
 AND CEILING ARE VENTED AS SPECIFIED ON SHEET 2 OF 6
 SUBMITTED. (COORDINATE WITH PLANS).
 ***NOTE: EXTERIOR ELEVATIONS ONLY SHOW ONE GABLE VENT
 ON SOUTH ELEVATION. THIS DOESN'T PROVIDE CROSS
 VENTILATION. ALSO, COORDINATE THIS ITEM WITH THE CROSS
 VENTILATION CREDIT TAKEN ON ITEM # 5(B) ABOVE.
  
 D) DOORS ITEM ON SHEET 3 OF 6: CLARIFY THE DOOR
 ORIENTATION. LOOK AT NORTH ARROW ON PLANS FOR CORRECT
 ORIENTATION. REVISE AS REQUIRED.
  
 6- ACCORDING TO PLANS SUBMITTED THE ROOF PITCH IS 3/12.
 NEED TO SPECIFY TWO LAYERS OF UNDERLAYMENT AS REQUIRED
 BY SEC. R905.2.2 OF 2010 FBC-RESIDENTIAL.
 ***NOTE: REVISED NOTE SPECIFY 2 LAYERS OF PLYWOOD
 INSTEAD OF 2 LAYERS OF UNDERLAYMENT. REVISE AS
 REQUIRED.
  
 7- PROVIDE COMPLETE DETAILS, SPECIFICATION AND LOCATION
 OF THE CROSS VENTILATION AND ACCESS OF THE CRAWL SPACE
 AS REQUIRED BY SEC. R408 OF 2010 FBC-RESIDENTIAL.
 ***NOTE: INFORMATION SUBMITTED DOESN'T COMPLY. READ
 CITED SECTION AND REVISE AS REQUIRED.
  
 8- NEED TO SPECIFY GUTTERS WITH DOWNSPOUTS AS REQUIRED
 BY SEC. R318.6 OF 2010 FBC-RESIDENTIAL.
 ***NOTE: INFORMATION SUBMITTED ON SHEET S.2 IS
 INCOMPLETE. MISSING GUTTERS SIZE. 2" DIAMETER DOWNSPOUT
 IS TOO SMALL. PROVIDE GUTTER AND DOWNSPOUT SIZING
 CALCULATIONS.
  
 9- PROVIDE COMPLETE DETAILS AND SPECIFICATION SHOWING
 COMPLIANCE WITH THE ROOF VENTILATION AS REQUIRED BY
 SEC. R806 OF 2010 FBC-RESIDENTIAL.
 ***NOTE: INFORMATION SUBMITTED DOESN'T COMPLY WITH
 CROSS VENTILATION. AND, COORDINATE WITH CREDIT TAKEN ON
 THE ENERGY CALCULATIONS.
  
 10- SHEET S.4:
 A) REVISE GENERAL ROOF NOTES #8. NEED TO USE 8D RING
 SHANK NAILS ONLY. SEC. R803.2.3.1 OF 2010
 FBC-RESIDENTIAL. REVISE NOTE AS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-04-22 Cont ID  
Sent By jgomez Date 2013-04-22 Time 17:37 Rev Time 0.00
Received By jgomez Date 2013-04-22 Time 17:37 Sent To  
Notes
2013-04-22 17:47:01RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL, THIS BUILDING IS LOCATED ON EXPOSURE
 "C".
 A) THE DESIGN PRESSURES SPECIFIED ON THE WINDOW AND
 DOOR SCHEDULES ARE TOO LOW FOR EXPOSURE "C". REVISE AS
 REQUIRED.
  
 B) THE ROOF PRESSURES FOR THE FLAT ROOF SHOWN ON ROOF
 FRAMING PLAN ON SHEET S.4 ARE TOO LOW FOR EXPOSURE "C".
 AND, CLARIFY WHY SHOWING THE SAME DESIGN PRESSURES FOR
 ZONE 2 AND 3. REVISE AS REQUIRED.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF SHINGLES. THE STATUS FOR PRODUCT APPROVAL
 FL10124-R9 SUBMITTED SAYS "PENDING FBC APPROVAL". NEED
 PRODUCT APPROVAL WITH APPROVED STATUS.
  
 B) ALL THE SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS. ***NOTE: PROVIDE ONLY THE PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR.
  
 C) FLAT ROOF: (1)PROVIDE THE RAS 117 CALCULATIONS FOR
 THE NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 12-0227.18 SUBMITTED.
 NEED THESE CALCULATIONS IN ORDER TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL.
  
 (2) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY FROM NOA
 SUBMITTED IS GOING TO BE USED. COORDINATE WITH RAS 117
 CALCULATIONS SUBMITTED.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 OF CITY AMENDMENTS TO FBC.
  
 4- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 5- REVISE AND PROVIDE COMPLETE ENERGY CALCULATIONS
 SUBMITTED (SEC. 107.2.1 CITY AMENDMENTS TO FBC):
 A) COMPLETE ALL THE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME, PERMITTING OFFICE, ETC.
  
 B) CLARIFY IF DOING THE CALCULATIONS FOR ENTIRE HOUSE
 OR JUST FOR THE ADDITION. CONDITIONED SPACE ON ITEM #6
 IS FOR ENTIRE HOUSE.
  
 C) THE AREA WEIGHTED AVERAGE OVERHANG DEPTH OF 7.720 FT
 ON ITEM #7 IS INCORRECT. TYPICAL OVERHANG ON THIS HOUSE
 IS 6" OR LESS. SEE EXTERIOR ELEVATIONS AND REVISE AS
 REQUIRED.
  
 D) PROVIDE COMPLETE SPECIFICATIONS AND DETAILS ON PLANS
 SHOWING HOW THE HOUSE COMPLIES WITH THE "CF" AND "CV"
 CREDITS TAKEN ON ITEM #15.
  
 E) CLARIFY WHY IS THERE ONLY "ONE" OCCUPANT CONSIDERED
 IF THERE ARE THREE BEDROOMS UNDER THE "SPACES" LINE ON
 SHEET 2 OF 6 SUBMITTED.
  
 F) THE TYPE OF ROOF SPECIFIED ON ROOF LINE ON SHEET 2
 OF 6 IS INCORRECT. THERE IS NOT HIP ROOF. SEE
 ELEVATIONS.
  
 G) PROVIDE SPECIFICATIONS/DETAILS SHOWING HOW THE ATTIC
 AND CEILING ARE VENTED AS SPECIFIED ON SHEET 2 OF 6
 SUBMITTED. (COORDINATE WITH PLANS).
  
 H) DOORS ITEM ON SHEET 3 OF 6: CLARIFY THE DOOR
 ORIENTATION AND THE WOOD STORM. THERE ARE NOT STORM
 DOORS AND LOOOK AT NORTH ARROW ON PLANS FOR CORRECT
 ORIENTATION. SEE PLANS AND PRODUCT APPROVALS SUBMITTED.
 REVISE AS REQUIRED.
  
 I) FRENCH DOORS ARE ALUMINUM, NOT VINYL. GLASS AREA
 TAKEN INTO CONSIDERATION FOR THE FRENCH DOORS NEED TO
 BE REVISED.
  
 6- ACCORDING TO WALL SECTIONS SUBMITTED, THE FLOOR
 JOISTS AND GIRDERS ARE CLOSER THAN 18" AND 12" FROM THE
 GROUND. PROVIDE COMPLETE SPECIFICATIONS AND DETAILS
 SHOWING COMPLIANCE WITH THE PROTECTION AGAINST WOOD
 DECAY AS REQUIRED BY SEC. R317 OF 2010 FBC-RESIDENTIAL.
  
 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF GUARDRAILS AND HANDRAILS TO SHOW
 COMPLIANCE WITH SEC. TABLE R301.5 OF 2010
 FBC-RESIDENTIAL.
  
 8- THE R-19 BATT INSULATION DOESN'T FIT ON A 2X6 WALL.
 (R-19 IS ABOUT 6-1/4" THICK). REVISE INFORMATION IN ALL
 THE WALL SECTIONS AS REQUIRED. COORDINATE WITH THE
 ENERGY CALCULATIONS ALSO. SEC. 107.2.1 CITY AMENDMENTS
 TO FBC.
  
 9- ACCORDING TO PLANS SUBMITTED THE ROOF PITCH IS 3/12.
 NEED TO SPECIFY TWO LAYERS OF UNDERLAYMENT AS REQUIRED
 BY SEC. R905.2.2 OF 2010 FBC-RESIDENTIAL.
  
 10- PROVIDE COMPLETE DETAILS, SPECIFICATION AND
 LOCATION OF THE CROSS VENTILATION AND ACCESS OF THE
 CRAWL SPACE AS REQUIRED BY SEC. R408 OF 2010
 FBC-RESIDENTIAL.
  
 11- NEED TO SPECIFY GUTTERS WITH DOWNSPOUTS AS REQUIRED
 BY SEC. R318.6 OF 2010 FBC-RESIDENTIAL.
  
 12- PROVIDE COMPLETE DETAILS AND SPECIFICATION SHOWING
 COMPLIANCE WITH THE ROOF VENTILATION AS REQUIRED BY
 SEC. R806 OF 2010 FBC-RESIDENTIAL.
  
 13- SPECIFY CARBON MONOXIDE ALARMS IN ALL AREAS
 REQUIRED BY SEC. R315 OF 2010 FBC-RESIDENTIAL.
  
 14- SHEET S.1:
 A) REVISE SCOPE OF WORK NOTES 3 AND 4. REVISE
 ORIENTATION OF THE NEW ROOMS. SEE NORTH ARROW AND
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO
 FBC.
  
 B) REVISE ROOF SHEATHING TYPE OF NAILS SPECS SHOWN ON
 THE TYP. WOOD COLUMN DETAIL (AND IN ALL WALL SECTIONS
 AND DETAILS SHOWN ON ALL SHEETS). SEE REVISED SPECS ON
 SHEET S.4 (COMPONENTS AND CLADDING PRESSURE ZONES).
 NEED TO USE MIN. 8D RING SHANK NAILS. SEC. R803.2.3.1
 OF 2010 FBC-RESIDENTIAL.
  
 15- SHEET S.4:
 A) COMPONENT AND CLADDING PRESSURE ZONES CHART. (1)
 REVISE SPACING FOR ZONE #3. NEED 4"O.C. AS REQUIRED BY
 SEC. R803.2.3.1. (2) REVISE THE DIMENSION FOR ROOF ZONE
 #3 TO COMPLY WITH FIGURE R803.2.3.1 OF 2010
 FBC-RESIDENTIAL.
  
 B) REVISE GENERAL ROOF NOTES #7 AND #8. COORDINATE WITH
 ITEM #15(A) ABOVE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-28 Cont ID  
Sent By rmcdouga Date 2013-06-28 Time 16:40 Rev Time 0.00
Received By rmcdouga Date 2013-06-28 Time 16:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-04-24 Cont ID  
Sent By dharvey Date 2013-04-24 Time 17:31 Rev Time 0.00
Received By dharvey Date 2013-04-24 Time 15:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-06-28 Cont ID  
Sent By jgomez Date 2013-06-28 Time 16:47 Rev Time 0.00
Received By jgomez Date 2013-06-25 Time 09:40 Sent To  
Notes
2013-06-25 09:40:49TO JG DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-06-14 Cont ID  
Sent By jgomez Date 2013-06-14 Time 10:33 Rev Time 0.00
Received By jgomez Date 2013-06-10 Time 12:23 Sent To  
Notes
2013-06-14 10:36:28NOTE: THIS IS A SUBMITTAL OF PLANS WITH IMPACT FEES
 STAMP ONLY. IS MISSING THE COPY OF THE IMPACT FEES PAID
 RECEIPT AND THE REST OF THE PACKAGE ADDRESSING COMMENTS
 WERE NOT SUBMITTED AT THIS TIME. JG.
2013-06-10 12:24:17SENT TO JULIO DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-03 Cont ID  
Sent By jgomez Date 2013-06-03 Time 10:32 Rev Time 0.00
Received By jgomez Date 2013-05-15 Time 16:03 Sent To  
Notes
2013-05-16 16:13:58R--6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-24 Cont ID  
Sent By dharvey Date 2013-04-24 Time 17:32 Rev Time 0.00
Received By dharvey Date 2013-04-08 Time 08:02 Sent To  
Notes
2013-04-09 08:02:41INCOMING SENT TO R-04. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status P Date 2013-07-01 Cont ID  
Sent By jgomez Date 2013-07-01 Time 10:11 Rev Time 0.00
Received By jgomez Date 2013-07-01 Time 10:11 Sent To  
Notes
2013-07-01 10:12:29PAID $1093.12. MU 2013-012539. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2013-06-28 Cont ID  
Sent By jgomez Date 2013-06-28 Time 16:47 Rev Time 0.00
Received By jgomez Date 2013-06-28 Time 16:47 Sent To  
Notes
2013-06-28 16:47:33ONLY THE PLANS WITH IMPACT FEES STAMP WAS SUBMITTED.
 NEED COPY OF PAID RECEIPT. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2013-06-14 Cont ID  
Sent By jgomez Date 2013-06-14 Time 10:37 Rev Time 0.00
Received By jgomez Date 2013-06-14 Time 10:37 Sent To  
Notes
2013-06-14 10:39:31ONLY THE PLANS WITH IMPACT FEES STAMP WAS SUBMITTED.
 NEED COPY OF PAID RECEIPT. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-06-03 Cont ID  
Sent By jgomez Date 2013-06-03 Time 10:32 Rev Time 0.00
Received By jgomez Date 2013-06-03 Time 10:32 Sent To  
Notes
2013-06-03 10:32:19BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-04-22 Cont ID  
Sent By jgomez Date 2013-04-22 Time 17:35 Rev Time 0.00
Received By jgomez Date 2013-04-22 Time 17:35 Sent To  
Notes
2013-04-22 17:36:35BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-04-16 Cont ID  
Sent By hmoser Date 2013-04-16 Time 09:05 Rev Time 0.00
Received By hmoser Date 2013-04-15 Time 12:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2013-06-28 Cont ID  
Sent By jgomez Date 2013-06-28 Time 16:19 Rev Time 0.00
Received By jgomez Date 2013-06-28 Time 16:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2013-06-03 Cont ID  
Sent By jgomez Date 2013-06-03 Time 09:51 Rev Time 0.00
Received By jgomez Date 2013-06-03 Time 09:51 Sent To  
Notes
2013-06-03 10:20:30RESIDENTIAL (R3) ADDITION, PLUMBING REVIEW SECOND
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- REVISE PLUMBING RISER DIAGRAM. THE WASHER NEEDS TO
 DISCHARGE DOWNSTREAM OF THE BATHROOM GROUP. SEC. P3108
 OF 2010 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-04-23 Cont ID  
Sent By jgomez Date 2013-04-23 Time 16:52 Rev Time 0.00
Received By jgomez Date 2013-04-23 Time 16:52 Sent To  
Notes
2013-04-23 17:00:11RESIDENTIAL (R3) ADDITION, PLUMBING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE PLUMBING RISER DIAGRAM. THE WASHER NEEDS TO
 DISCHARGE DOWNSTREAM OF THE BATHROOM GROUP. AND, THE
 BATHROOM GROUP DRY VENT IS NOT PROPERLY LOCATED. SEC.
 P3108 OF 2010 FBC-RESIDENTIAL.
  
 ***NOTE: YOU MAY CONTACT THE LICENSED PLUMBER DOING THE
 JOB TO SEE HOW HE/SHE PROPOSES TO VENT THE BATHROOM
 GROUP ACCORDING TO THE PROPOSED BATHROOM LAYOUT. THIS
 WILL ELIMINATE ANY DISCREPANCIES OR DELAYS IN THE
 FIELD.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2013-09-09 Cont ID  
Sent By jgomez Date 2013-09-09 Time 16:40 Rev Time 0.00
Received By jgomez Date 2013-09-09 Time 16:40 Sent To  
Notes
2013-09-09 16:42:01REVISED RAS 117 CALCULATIONS SUBMITTED UNDER REVISION
 #13090050. JG.
  
 NOA'S SUBMITTED: 08-0410.09 FOR FLAT ROOF. AND,
 FL10124-R9 FOR SHINGLES. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2013-05-28 Cont ID  
Sent By avann Date 2013-05-28 Time 10:35 Rev Time 0.00
Received By ajones Date 2013-05-20 Time 15:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2013-04-11 Cont ID  
Sent By mdekle Date 2013-04-11 Time   Rev Time  
Received By mdekle Date 2013-04-11 Time   Sent To  
Notes
2013-04-11 09:39:57DATE OF REVIEW: 04.11.2013
 PERMIT NO.: 13040273
 ADDRESS: 222 BLOOMFIELD DRIVE
 SCOPE OF REVIEW: INTERIOR AND EXTERIOR REMODEL. ADD NEW
 COVERED DECK
  
 ZONING PLAN REVIEW
 REVIEW STATUS: FAILED
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
 ___________________________________________
  
 1. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 2. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK ($94,968.00) EXCEEDS 50% OF THE
 STRUCTURE'S VALUE ($57,849.00) (LISTED AS "IMPROVEMENT
 VALUE" WITH THE P.B.C. PROPERTY APPRAISER'S OFFICE),
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. PLEASE
 SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN SHOWING
 COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF THE ZLDR.
 PLEASE BE ADVISED; WE WILL CREDIT FOR ALL EXISITING
 LANDSCAPING TO MEET CODE COMPLIANCE HOWEVER; IF YOU ARE
 GOING TO DO LANDSCAPE WORK, LANDSCAPE PLANS SHALL BE
 SUBMITTED UNDER A SEPERATE LANDSCAPE PERMIT AND SHALL
 BE ACCOMPANIED BY A CERTIFIED COST ESTIMATE (LABOR AND
 MATERIALS).
  
 3. THE APPLICANT MUST SUBMIT A SITE PLAN DEPICTING THE
 PROPOSED BUILDING SETBACKS, MEASURED FROM THE PROPERTY
 LINES FOR THE 'NEW' LIVING AREA AND THE 'NEW' COVERED
 DECK.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AND/OR
 CONSULT THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA, PLANNER
 PLANNING & ZONING DIVISION
 TEL: (561) 822-1442
 EMAIL: [email protected]
  