Plan Review Details - Permit 13040205
Plan Review Stops For Permit 13040205
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-10-02 Cont ID  
Sent By jwitmer Date 2013-10-02 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2013-10-02 Time 07:15 Sent To  
Notes
2013-10-02 08:24:25BUILDING PLAN REVIEW
 REVISION: 13040205
 PERMIT: 12100336
 ADD: 1720 PALM BEACH LAKES
 CONT: NUNNO BUILDERS
 TEL: (561)743-8066 MARK PAULES
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: 10/02/2013
 ACTION: PROVISO
  
 1) RESPONCE LETTER INDICATES ROOFING CONTRACTOR TO GET
 THEIR OWN ROOFING PERMIT WITH PRODUCT APPROVAL.
 SUB-SYSTEM NOT IDENTIFIED, THIS WILL PRODUCT APPROVAL
 WILL BE STRUCK AND A SEPERATE PERMIT,WITH ASSOCIATED,
 REVIEW AND FEES DUE WOULD BE DUE.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES IDENTIFY THE
 SUB-SYSTEM TO BE INSTALLED AND NOA: LIMITATION # 7 IS
 INDICATED, THEN RAS 117 CALCULATIONS FOR ZONES 2 & 3 BY
 A ENGINEER OR ARCHITECT.
  
  
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-09-17 Cont ID  
Sent By jwitmer Date 2013-09-17 Time 13:54 Rev Time 0.00
Received By jwitmer Date 2013-09-17 Time 12:30 Sent To  
Notes
2013-09-17 12:55:18BUILDING PLAN REVIEW
 REVISION: 13040205
 PERMIT: 12100336
 ADD: 1720 PALM BEACH LAKES
 CONT: NUNNO BUILDERS
 TEL: (561)743-8066 MARK PAULES
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: 9/17/2013
 ACTION: DENIED
  
 1) SHEET AR1 UNDER THE HEADING OF OCCUPANT LOAD, HAS
 TAKEN A SEATING COUNT THAT TOTALS UNDER 100 OCCUPANTS.
 THE DESIGNER HAS FIGURED FOR THE DINING AREA FIXED
 SEATING AS PER 1004.7 BUT THIS CODE SECTION ALSO NEEDS
 TO COMPLY WITH THE SECOND HALF OF THIS CODE SECTION,
 THE OCCUPANT LOAD FOR AREAS WHERE FIXED SEATING IS NOT
 INSTALLED SHALL BE DETERMINED IN ACCORDANCE WITH
 SECTION 1004.1.1 AND ADDED TO THE FIXED SEATING.
  
 THE OCCUPANT LOAD I FIGURE IS:
 DINING ROOM 1179 SQ FT/ 15= 79
 DIN ROOM CONCENTRATED AREAS 191 SQ FT/ 07= 28
 KITCHEN 1385 SQ FT/ 200= 7
 STORAGE 726 SQ FT/ 300= 3
 TOTAL OCCUPANT LOAD OF 117 OCCUPANTS
  
 PLEASE NOTE UNDER THE 2010 EXISTING BUILDING CODE
 1001.2 CREATION OR EXTENTION OF NONCONFORMITY, IT
 APPEARS THAT THE OCCUPANT LOAD WILL BE OVER 100
 OCCUPANTS. 2010 FBC-B 903.2.1.2(2) WILL REQUIRE FIRE
 SPRINKLERS WITH AN OCCUPANT LOAD OF 100 OR MORE.
  
 2) COMPLIED.
  
 3) 2ND REQUEST: 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES IDENTIFY THE
 SUB-SYSTEM TO BE INSTALLED AND NOA: LIMITATION # 7 IS
 INDICATED, THEN RAS 117 CALCULATIONS FOR ZONES 2 & 3 BY
 A ENGINEER OR ARCHITECT.
 IF NOT IDENTIFIED THIS WILL PRODUCT APPROVAL WILL BE
 STRUCK AND A SEPERATE PERMIT,WITH ASSOCIATED, REVIEW
 AND FEES DUE WOULD BE DUE.
  
  
 4) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-04-22 Cont ID  
Sent By J WITMER Date 2013-04-22 Time 14:00 Rev Time 0.00
Received By jwitmer Date 2013-04-22 Time 13:34 Sent To  
Notes
2013-04-22 14:34:19BUILDING PLAN REVIEW
 REVISION: 13040205
 PERMIT: 12100336
 ADD: 1720 PALM BEACH LAKES
 CONT: NUNNO BUILDERS
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 4/22/2013
 ACTION: DENIED
  
 1) SHEET AR1 UNDER THE HEADING OF OCCUPANT LOAD, HAS
 NOT PROVIDED THE TOTAL OCCUPANT LOAD FOR THE BUILDING.
 THE DESIGNER HAS LEFT OUT THE SQ FOOTAGE FOR THE
 KITCHEN AREA, STORAGE AND FRONT COUNTER STANDING IN
 LINE. 2010 FBC-B TABLE 1004.1.1 KITCHENS 200 GROSS,
 STORAGE 300 GROSS, TABLES AND CHAIRS 15 NET AND
 STANDING SPACE 5 NET (AT COUNTER). IT APPEARS THIS
 OCCUPANT LOAD MAY BE OVER 100 OCCUPANTS.
  
 PLEASE NOTE UNDER THE 2010 EXISTING BUILDING CODE
 1001.2 CREATION OR EXTENTION OF NONCONFORMITY, IT
 APPEARS THAT THE OCCUPANT LOAD WILL BE OVER 100
 OCCUPANTS. 2010 FBC-B 903.2.1.2(2) WILL REQUIRE FIRE
 SPRINKLERS WITH AN OCCUPANT LOAD OF 100 OR MORE.
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. CIRCLE WHICH SUB-SYSTEM TO BE
 INSTALLED, CICRLE TYPE OF GLAZING TO BE USED,
 (B) WINDOWS CIRCLE THE MULLIONS TO BE INSTALLED ,CIRCLE
 TYPE OF SUB-SYSTEM TO BE INSTALLED AND CIRCLE THE TYPE
 OF GLAZING.
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES IDENTIFY THE
 SUB-SYSTEM TO BE INSTALLED AND IF LIMITATION # 7 IS
 INDICATED, THEN RAS 117 CALCULATIONS FOR ZONES 2 & 3 BY
 A ENGINEER OR ARCHITECT.
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-09-30 Cont ID  
Sent By dharvey Date 2013-09-30 Time 14:59 Rev Time 0.00
Received By dharvey Date 2013-09-30 Time 14:57 Sent To  
Notes
2013-09-30 14:59:31PREVIOUSLY OK'D BY VB

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-05-03 Cont ID  
Sent By dharvey Date 2013-05-03 Time 13:51 Rev Time 0.00
Received By dharvey Date 2013-05-03 Time 13:51 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2013-09-18 Cont ID  
Sent By mgonzale Date 2013-09-18 Time   Rev Time 1.00
Received By mgonzale Date 2013-09-18 Time   Sent To I
Notes
2013-09-18 13:33:01SITE CALCULATIONS WHERE RECEIVED FOR THE SUBJECT SITE.
  
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2013-06-04 Cont ID  
Sent By M GONZAL Date 2013-06-04 Time   Rev Time 0.25
Received By mgonzale Date 2013-06-04 Time   Sent To Z
Notes
2013-06-04 15:19:08#1 SUBMIT DRAINAGE CALCULATIONS
  
 #2 SUBMIT PERVIOUS AND IMPERVIOUS AREAS + TOTAL SITE
 SQUARE FOOTAGE.
  
 YOU MAY PDF TO [email protected]
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-10-07 Cont ID  
Sent By scaldero Date 2013-10-07 Time 12:21 Rev Time 0.00
Received By scaldero Date 2013-10-07 Time 12:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-09-04 Cont ID  
Sent By wjolin Date 2013-09-04 Time 11:52 Rev Time 0.00
Received By wjolin Date 2013-09-04 Time 11:30 Sent To  
Notes
2013-09-04 11:52:311720 PALM BEACH LAKES BOULEVARD
 TRACKING #13040205
 PERMIT #12100336
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT: THE BUILDING OCCUPANT LOAD IS
 INDICATED AS 99 PERSONS; HOWEVER, THE KITCHEN AREA
 OCCUPANT LOAD FACTOR IS INDICATED AS 200 SQ.FT. PER
 PERSON (PER FBC) BUT THE LIFE SAFETY CODE (NFPA 101)
 TABLE 7.3.1.2 INDICATES THE OCCUPANT LOAD FACTOR FOR
 KITCHENS IS TO BE FIGURED AT 100 SQ.FT. PER PERSON
 WHICH WILL RESULT IN A BUILDING OCCUPANT LOAD OF 106
 PERSONS AND THEREFORE WILL STILL REQUIRE AUTOMATIC
 SPRINKLER PROTECTION. ADDITIONALLY, THERE IS OPEN FLOOR
 AREA ADAJACENT TO THE SEATING AND STANDING AREAS THAT
 HAS NOT BEEN FIGURED INTO THE TOTAL POSSIBLE OCCUPANT
 LOAD.
  
 ORIGINAL COMMENT - ENCLOSED ADDITION: THE 90 FIXED
 SEATS ADDED TO THE OCCUPANT LOAD OF THE
 STANDING/ORDERING CUSTOMERS WILL RESULT IN A NEW
 OCCUPANT LOAD EXCEEDING 100 PERSONS. PER FBC SECTION
 903.2.1.2 AN AUTOMATIC SPRINKLER WILL BE REQUIRED.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-04-16 Cont ID  
Sent By W JOLIN Date 2013-04-16 Time 11:36 Rev Time 0.00
Received By wjolin Date 2013-04-16 Time 11:06 Sent To  
Notes
2013-04-16 11:36:371720 PALM BEACH LAKES BOULEVARD
 TRACKING #13040205
 PERMIT #12100336
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ENCLOSED ADDITION: THE 90 FIXED SEATS ADDED TO THE
 OCCUPANT LOAD OF THE STANDING/ORDERING CUSTOMERS WILL
 RESULT IN A NEW OCCUPANT LOAD EXCEEDING 100 PERSONS.
 PER FBC SECTION 903.2.1.2 AN AUTOMATIC SPRINKLER WILL
 BE REQUIRED.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-10-08 Cont ID  
Sent By hmoser Date 2013-10-08 Time 14:49 Rev Time 0.00
Received By hmoser Date 2013-10-02 Time 06:36 Sent To  
Notes
2013-10-02 06:38:23C-26

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-09-30 Cont ID  
Sent By dharvey Date 2013-09-30 Time 14:59 Rev Time 0.00
Received By dharvey Date 2013-08-22 Time 17:40 Sent To  
Notes
2013-09-30 15:00:00TO DENIED LARGE FILE UNDER "N"
2013-08-22 17:42:09SENT TO C26 BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-25 Cont ID  
Sent By shill Date 2013-06-25 Time 09:32 Rev Time 0.00
Received By shill Date 2013-04-05 Time 11:40 Sent To  
Notes
2013-04-05 11:41:34C03

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2013-09-17 Cont ID  
Sent By jwitmer Date 2013-09-17 Time 12:55 Rev Time 0.00
Received By jwitmer Date 2013-09-17 Time 12:55 Sent To  
Notes
2013-09-17 12:56:29IMPACT FEES : $ 8,551.43.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-04-22 Cont ID  
Sent By jwitmer Date 2013-04-22 Time 14:55 Rev Time 0.00
Received By jwitmer Date 2013-04-22 Time 14:55 Sent To  
Notes
2013-04-22 14:55:19BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-10-08 Cont ID  
Sent By hmoser Date 2013-10-08 Time 14:49 Rev Time 0.00
Received By hmoser Date 2013-10-08 Time 14:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-09-09 Cont ID  
Sent By hmoser Date 2013-09-09 Time 09:55 Rev Time 0.00
Received By hmoser Date 2013-09-09 Time 09:55 Sent To  
Notes
2013-09-09 10:03:01CALLED MARK MECHANICAL PLANS ARE OK.
 THE AIR CONDITIONING CONTRACTOR NEEDS
 TO PROVIDE A APPLICATION BE FOR REVISION CAN
 BE APPROVED .
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-04-12 Cont ID  
Sent By hmoser Date 2013-04-12 Time 14:53 Rev Time 0.00
Received By hmoser Date 2013-04-12 Time 14:33 Sent To  
Notes
2013-04-12 15:31:51THERE IS NO MECHANICAL PERMIT ISSUED ON THIS JOB .
 PROVIDE APPLICATION AND PLANS SUBMIT TO THE CITY
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop Z ZONING
Rev No 3 Status P Date 2013-10-02 Cont ID  
Sent By dkittred Date 2013-10-02 Time 08:52 Rev Time 0.00
Received By dkittred Date 2013-10-02 Time 08:52 Sent To  
Notes
2013-10-08 15:36:12REFERENCE LANDSCAPE PLAN - PERMIT NO. 12100337 WILL BE
 REVISED WITH THE LANDSCAPE PLAN COMPATIBLE WITH
 APPROVED SITE PLAN IN THIS PERMIT. DK

Review Stop Z ZONING
Rev No 2 Status F Date 2013-09-05 Cont ID  
Sent By dkittred Date 2013-09-05 Time 15:10 Rev Time 0.00
Received By dkittred Date 2013-09-05 Time 11:09 Sent To  
Notes
2013-09-05 15:40:18PLANNING & ZONING COMMENTS: ***FAILED***
  
 9/5/2013
 1. SHEET C-002 IS OUT OF DATED. PLEASE REPLACE WITH
 DEMOLITION PLAN SHEET APPROVED WITH THE SITE PLAN AND
 HAVING THE LAST REVISION DATE OF 05-02-13.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2013-04-11 Cont ID  
Sent By A JONES Date 2013-04-11 Time 09:49 Rev Time 0.00
Received By ajones Date 2013-04-11 Time 09:49 Sent To  
Notes
2013-04-11 09:58:364/11/13- FAILED BASED ON THE FOLLOWING:
  
 1. THE TRUCK TURN DETAIL SHOWN ON THE SITE PLAN DOES
 NOT WORK. PLEASE PROVIDE OTHER ALTERNATIVE FOR TRUCKS
 TO ENTER THE SITE.
 2. A SEPARATE PERMIT IS REQUIRED FOR SIGNAGE AND
 LANDSCAPING.
 3. THE BICYCLE RACK SHOWN DOES NOT MEET CODE. CONTACT
 ALEX HANSEN AT 561-822-1463 FOR THE CORRECT RACK.
 4. IT APPEARS THAT THE BUILDING IS MOVING CLOSER TO THE
 STREET. ARE ADDITIONAL SEATS BEING ADDED? CHANGES TO
 THE BUILDING WERE NOT APPROVED AS PART OF THE PLANNING
 DIVISION'S SITE PLAN REVIEW PROCESS
  
 ANGELLA VANN, AICP
 561-822-1441
 [email protected]