| 2013-04-16 16:07:55 | BUILDING PLAN REVIEW |
| | PERMIT: 13040187 |
| | ADD: 400 N FLAGLER # 1701 |
| | CONT: A. D. SABA ENTERPRISES |
| | TEL: (561)969-2920 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1A) GENERAL NOTE # 12 STATES FBC-B 1207.3 WHICH DEALS |
| | WITH STRUCTURE BORNE SOUND, 1207.3 STRUCTURE-BORNE |
| | SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | IF FLOORING IS TO BE REPLACED WITH TILE OR MARBLE TYPE |
| | PRODUCTS THEN A REVISION WILL BE REQUIRED MEETING THESE |
| | REQUIREMENTS. |
| | |
| | 1B) IF FLOORING IS BEING REPLACED WITH A TILE OR |
| | SIMILAR PRODUCT THEN THE FLOOR INSULATION WILL ALSO |
| | NEED TO MEET 2010 FBC-B 603.1(2) EXCEPTION (1). |
| | INSULATION PLACED BETWEEN TWO LAYERS OF NONCOMBUSTIBLE |
| | MATERIALS WITHOUT AN INTERVENING AIRSPACE SHALL BE |
| | ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 100. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |