| Plan Review Stops For Permit 13040094 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2013-06-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-06-06 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-06-06 |
Time |
07:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-04-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-04-09 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-04-05 |
Time |
08:01 |
Sent To |
|
|
| Notes |
| 2013-04-09 14:30:18 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES OF A SURFACE WATER DRAINAGE PLAN | | | THAT SHOWS COMPLIANCE WITH FBCR 401.3. | | | | | | 2) SUBMIT 2 SETS OF SIGNED AND SEALED SUBSURFACE SOIL | | | REPORTS. FBCR 401.4 | | | | | | 3) FBCR 302.1 REQUIRES EXTERIOR WALLS LOCATED ON A ZERO | | | LOT LINE TO HAVE A FIRE RESISTANCE RATING OF ONE HOUR. | | | SUBMIT TESTING REPORTS AND SPECIFICATIONS SHOWING THAT | | | THE GLASS BLOCK PANEL WALL SYSTEM THAT IS PROPOSED FOR | | | THIS WALL HAS A ONE HOUR FIRE RESISTANCE RATING IN | | | ACCORDANCE WITH ASTM E 119 OR UL 263 WITH EXPOSURE FROM | | | BOTH SIDES. | | | | | | 4) THE SUMMER KITCHEN OPTION HAS BEEN CROSSED OFF ON | | | THE PLANS. HOWEVER, THE MANUFACTURER'S SPECS. WERE | | | SUBMITTED FOR THE OUTDOOR GRILL, REFRIGERATOR AND SINK. | | | PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 | | | | | | 5) THE VALUE OF $145,255.00 APPEARS UNDERESTIMATED THIS | | | PROJECT. PER CITY AMENDMENTS 109.3, FOR PERMITTING | | | PURPOSES THE VALUATION OF BUILDINGS AND SYSTEMS SHALL | | | BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. | | | | | | WHEN RESUBMITTING PLEASE PROVIDE A RESPONSE LETTER | | | INDICATING HOW EACH OF THE REVIEW COMMENT HAS BEEN | | | ADDRESSED. | | | | | | NOTE: ON FUTURE SUBMITTALS PLEASE DO NOT STAPLE THE | | | PRODUCT APPROVALS TO THE PLANS. | | | | | | | | | TRUSS DRAWING REVIEW DENIED BY BUILDING | | | | | | 1) THE ORIGINAL WET SIGNATURE OF THE TRUSS ENGINEER AS | | | WELL AS HIS SEAL IS REQUIRED ON THE TRUSS LAYOUT AND | | | THE TRUSS DRAWINGS PER FS 471.025 AN FAC 61G15-23.002. | | | | | | 2) SPECIFY THE TRUSS ANCHORS THAT WILL BE USED FOR THE | | | FLAT GIRDER TRUSSES FG2 AND FG3 AT THE MASONRY WALLS. | | | FBCR 802.1.6.5 | | | | | | 3) THE TRUSS ANCHORS THAT ARE SPECIFIED FOR THE HIP | | | GIRDER TRUSS A10 ARE NOT ADEQUATE. THE UPLIFT ON THE | | | TRUSS DRAWINGS AT BEARING POINT 18 IS -2683 AND AT B.P. | | | 13 IT IS -1618. SHEET S-2 OF THE PLANS LISTS ANCHOR B | | | (-2235) AND A (-1220) RESPECTIVELY. PLEASE CORRECT. | | | FBCR 802.1.6.5 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2013-06-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-06-06 |
Time |
07:31 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-06-06 |
Time |
07:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2013-04-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-04-08 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-04-08 |
Time |
15:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2013-06-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-06-06 |
Time |
07:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-06-06 |
Time |
07:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2013-04-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-04-08 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-04-08 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2013-04-08 13:43:59 | A SEPARATE APPLICATION AND PERMIT IS REQUIRED FOR GAS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-06-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-06-06 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-05-30 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2013-06-01 11:11:51 | *EXPEDITED* | | | GAVE TO ROBBIE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-04-11 |
|
|
Cont ID |
|
| Sent By |
mdekle |
Date |
2013-04-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
mdekle |
Date |
2013-04-02 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2013-04-03 11:26:50 | INCOMING SENT TO R-04. JW |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2013-04-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-04-16 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-04-16 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2013-04-16 09:04:25 | MU-2013-6687 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2013-04-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-04-08 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-04-08 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2013-04-08 11:03:03 | SUBMIT A COPY OF THE PAID IMPACT FEE RECEIPT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2013-06-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-06-06 |
Time |
07:31 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-06-06 |
Time |
07:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2013-04-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-04-09 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-04-09 |
Time |
07:18 |
Sent To |
|
|
| Notes |
| 2013-04-09 08:54:48 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) SHOW COMPLIANCE WITH FBCR G2407.1 (304.1) FOR | | | COMBUSTION AIR IN THE LAUNDRY ROOM FOR THE 35,000 BTU | | | GAS CLOTHES DRYER. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2013-04-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-04-08 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-04-08 |
Time |
10:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2013-06-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-06-06 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-06-06 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2013-06-06 15:39:39 | ENTEGRA, ESTATE "S" TILE NOA NO. 11-0510.02 WITH 3M | | | 2-COMPONENT FOAM ROOF TILE ADHESIVE AH-160 NOA | | | NO.12-0228.18 WERE SUBMITTED FOR THE ROOFING MATERIALS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2013-04-11 |
|
|
Cont ID |
|
| Sent By |
mdekle |
Date |
2013-04-11 |
Time |
|
Rev Time |
|
| Received By |
mdekle |
Date |
2013-04-11 |
Time |
|
Sent To |
|
|
| Notes |
| 2013-04-11 11:21:44 | ZONING** PASSED W/PROVISO** | | | LANDSCAPE PLANS SHALL BE SUBMITTED | | | AND UNDER A SEPERATE LANDSCAPE | | | PERMIT AND SHALL BE ACCOMPANIED BY A | | | CERTIFIED COST ESTIMATE (LABOR & MATERIALS). | | | MURRIAH DEKLE, MPA, PLANNER | | | PLANNING & ZONING DIVISION | | | TEL: (561) 822-1442 | | | EMAIL: [email protected] | | | | | 2013-04-10 11:47:47 | 4/10/13 |
|
|