| 2013-04-12 11:20:06 | BUILDING PLAN REVIEW |
| | PERMIT: 13040089 |
| | ADD: 400 N FLAGLER PH#B4 |
| | CONT: A D SABA ENTERPRISES |
| | TEL: (561)307-5358 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 4/12/ 2013 |
| | ACTION: BUILDING PROVISO: |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | THESE DOCUMENTS LISTED BELOW MUST BE SUBMITTED BEFORE |
| | FRAMING INSPECTION TO THE BUILDING DEPARTMENT. |
| | |
| | 1) SUBMIT MANUFACTURERS SPECIFICATIONS MEETING THE |
| | SOUND DEADENING REQUIREMENT FOR (WOOD FLOORS & TILE ) |
| | 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2) HIGH RISE REQUIREMENTS :2010 FBC 603.1 ALLOWABLE |
| | MATERIALS. |
| | COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS |
| | OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING |
| | APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1 |
| | THROUGH 603.1.3: |
| | |
| | |
| | 2A) TILE AAND OR MARBLE FLOORS EXCEPTION1.INSULATION |
| | PLACED BETWEEN TWO LAYERS OF NONCOMBUSTIBLE MATERIALS |
| | WITHOUT AN INTERVENING AIRSPACE SHALL BE ALLOWED TO |
| | HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 100. |
| | |
| | 2B) WOOD FLOORS, SECTION 805 COMBUSTIBLE MATERIALS IN |
| | TYPES I AND II CONSTRUCTION |
| | 805.1.3 INSULATING BOARDS. COMBUSTIBLE INSULATING |
| | BOARDS NOT MORE THAN 1/2 INCH (12.7 MM) THICK AND |
| | COVERED WITH FINISH FLOORING ARE PERMITTED WHERE |
| | ATTACHED DIRECTLY TO A NONCOMBUSTIBLE FLOOR ASSEMBLY. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |