Plan Review Details - Permit 13030820
Plan Review Stops For Permit 13030820
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-07-05 Cont ID  
Sent By jwitmer Date 2013-07-05 Time 16:30 Rev Time 0.00
Received By jwitmer Date 2013-07-05 Time 16:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-04-29 Cont ID  
Sent By jwitmer Date 2013-04-29 Time 14:16 Rev Time 0.00
Received By jwitmer Date 2013-04-29 Time 13:46 Sent To  
Notes
2013-04-29 14:35:27BUILDING PLAN REVIEW
 REVISION: 13030820
 PERMIT: 12030240
 ADD: 6701 N JOG RD
 CONT: LOBOLO CONSTRRUCTION
 TEL: (561)541-0191
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 4/29/2013
 ACTION: DENIED
  
 1) SHEET 720-A1-101 & 103 THTE BREAK ROOM IS
 APPROXIMATELY 1060 SQ FT. / 15 SQ FT= A OCCUPANT LOAD
 OF 70 OCCUPANTS. THIS WILL CREATE A A-2 ASSEMBLY
 OCCUPANCY. DOOR IDENTIFIED AS DA-110 IS SWINGING THE
 WRONG WAY WITH AN OCCUPANT LOAD OF OVER 50. FBC-B
 1008.1.2 DOOR SWING. DOORS SHALL SWING IN THE DIRECTION
 OF EGRESS TRAVEL WHERE SERVING AN OCCUPANT LOAD OF 50
 OR MORE PERSONS OR A GROUP H OCCUPANCY.
  
 2) SHEET 720-A2-100 DOOR SCHEDULE INDICATES DOOR #
 DA-110 AS A HARDWARE PACKAGE 3. THIS IS NOT LOCATED ON
 THIS SHEET. PLEASE COMPLY WITH:
 2010 FBC-B 1008.1.10 PANIC AND FIRE EXIT HARDWARE.
 DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING
 ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN
 A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A
 LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 1008.1.10.1 INSTALLATION.
 WHERE PANIC OR FIRE EXIT HARDWARE IS INSTALLED, IT
 SHALL COMPLY WITH THE FOLLOWING:
  
 1. PANIC HARDWARE SHALL BE LISTED IN ACCORDANCE WITH UL
 305;
  
 2. FIRE EXIT HARDWARE SHALL BE LISTED IN ACCORDANCE
 WITH UL 10C AND UL 305;
  
 3. THE ACTUATING PORTION OF THE RELEASING DEVICE SHALL
 EXTEND AT LEAST ONE-HALF OF THE DOOR LEAF WIDTH; AND
  
 4. THE MAXIMUM UNLATCHING FORCE SHALL NOT EXCEED 15
 POUNDS (67 N).
  
 3) SHEET A72-150-100 BUILDING CODE SUMMARY INDICATES A
 BUSINESS OCCUPANCY PLEASE ADD THE A-2 ASSEMBLY
 OCCUPANCY ALSO TO THE LIST.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-08-02 Cont ID  
Sent By dharvey Date 2013-08-02 Time 16:02 Rev Time 0.00
Received By dharvey Date 2013-08-02 Time 16:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-05-07 Cont ID  
Sent By dharvey Date 2013-05-07 Time 11:17 Rev Time 0.00
Received By dharvey Date 2013-05-07 Time 10:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-06-29 Cont ID  
Sent By wjolin Date 2013-06-29 Time 15:15 Rev Time 0.00
Received By wjolin Date 2013-06-29 Time 14:38 Sent To  
Notes
2013-06-29 15:15:536701 NORTH JOG ROAD - MAINTENANCE BUILDING
 TRACKING #13030820
 PERMIT #12030240
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A1-100: ALL EXIT AND EXIT ACCESS DOORS SHALL BE
 EQUIPPED WITH PANIC HARDWARE FOR NON-SEPARATED MIXED
 USE ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 50 OR
 MORE PERSONS. THE FOLLOWING DOORS WILL NEED PANIC
 HARDWARE:
 DA100, DA110A, DA113A, DA113B, DA113C, DA114, DA114A
 AND DA114B.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-04-22 Cont ID  
Sent By wjolin Date 2013-04-22 Time 12:44 Rev Time 0.00
Received By wjolin Date 2013-04-22 Time 11:04 Sent To  
Notes
2013-04-22 12:44:246701 NORTH JOG ROAD - MAINTENANCE BUILDING
 TRACKING #13030820
 PERMIT #12030240
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A5-100: THE BUILDING CLASSIFICATION FAILS TO
 CLASSIFY THE BREAK ROOM AS AN ASSEMBLY OCCUPANCY. THIS
 SPACE APPEARS TO BE APPROXIMATELY 900 SQUARE FEET WITH
 AN OCCUPANT LOAD OF APPROXIMATELY 60 PERSONS FIGURED AT
 15 SQ.FT. PER PERSON. PROVIDE THE TRAVEL DISTANCES,
 DEAD-END, COMMON PATH OF TRAVEL, ETC. INFORMATION FOR
 ASSEMBLY OCCUPANCIES. FOR NONSEPARATED MIXED USE
 OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE SAFETY
 REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO THE
 BUILDING.
  
 SHEET A5-100:THE BREAK ROOM IS AN ASSEMBLY OCCUPANCY
 WITH AN OCCUPANT LOAD OF APPROXIMATELY 60 PERSONS;
 THEREFORE, TWO EXITS ARE NEEDED FROM THE BREAK ROOM AND
 THE BREAKROOM DOORS SHALL SWING IN THE DIRECTION OF
 EGRESS.
  
 SHEET A5-100: ASSEMBLY OCCUPANCIES WITH AN OCCUPANT
 LOAD ABOVE 50 PERSONS REQUIRE THE DOOR LOCKS AND
 LATCHES TO BE RELEASED BY PANIC OR FIRE EXIT HARDWARE.
 BECAUSE THIS IS A NON-SEPARATED USE BUILDING, ALL EXIT
 AND EXIT ACCESS DOORS WILL REQUIRE PANIC/FIRE EXIT
 HARDWARE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2013-08-02 Time   Rev Time 0.00
Received By rregueir Date 2013-06-17 Time 16:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-07 Cont ID  
Sent By dharvey Date 2013-05-07 Time 11:17 Rev Time 0.00
Received By dharvey Date 2013-04-12 Time 15:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-07-17 Cont ID  
Sent By rregueir Date 2013-07-17 Time 16:11 Rev Time 0.00
Received By rregueir Date 2013-07-17 Time 16:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-04-30 Cont ID  
Sent By rregueir Date 2013-04-30 Time 16:07 Rev Time 0.00
Received By rregueir Date 2013-04-30 Time 15:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-06-28 Cont ID  
Sent By lwagner Date 2013-06-28 Time 13:16 Rev Time 0.00
Received By lwagner Date 2013-06-27 Time 15:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-04-22 Cont ID  
Sent By lwagner Date 2013-04-22 Time 10:02 Rev Time 0.00
Received By lwagner Date 2013-04-19 Time 14:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-09-16 Cont ID  
Sent By rregueir Date 2013-09-16 Time 14:40 Rev Time 0.00
Received By rregueir Date 2013-09-16 Time 14:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2013-07-16 Cont ID  
Sent By eschnide Date 2013-07-16 Time 13:56 Rev Time 0.75
Received By eschneid Date 2013-07-16 Time 13:56 Sent To  
Notes
2013-07-16 14:05:30FAILED
  
 1) REPEAT COMMENT: SECTION 94-444(B) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS REQUIRES SCREENING FOR
 OUTDOOR STORAGE RACKS. PLEASE PROVIDE DETAILS VERIFYING
 THAT THE STORAGE RACK WILL COMPLY WITH THE SCREENING
 REQUIREMENTS. THE RESPONSE COMMENTS STATE THAT THERE
 WILL BE LANDSCAPE ON THE EAST AND SOUTH SIDES. THIS
 ONLY PARTIALLY MEETS THE REQUIREMENTS FROM SECTION
 94-44(B) AS FOLLOWS:
  
 "OUTDOOR STORAGE FOR NONRESIDENTIAL AND MULTIFAMILY
 USES; STORAGE AND DISPOSAL FACILITIES. OUTDOOR
 INCINERATORS, GARBAGE OR TRASH RECEPTACLES, FUEL OIL OR
 PROPANE TANKS, AND STORAGE RACKS SHALL NOT BE PERMITTED
 UNLESS APPROPRIATE SCREENING IS PROVIDED. SCREENING
 SHALL BE CONSTRUCTED OF BRICK, DECORATIVE CONCRETE,
 OTHER DECORATIVE MASONRY, OR COMPARABLY DURABLE WOOD
 AND STEEL. WALLS SHALL BE LANDSCAPED WITH SHRUBS AND
 HEDGES PLANTED AT TWO-FOOT INTERVALS."
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2013-06-24 18:44:506/25/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-04-26 Cont ID  
Sent By eschneid Date 2013-04-26 Time 14:19 Rev Time 0.50
Received By eschneid Date 2013-04-26 Time 14:19 Sent To  
Notes
2013-04-26 14:36:03FAILED
  
 1) PLEASE EXPLAIN THE NEW "BOTTLED STORAGE RACK".
 SECTION 94-444(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS REQUIRES SCREENING FOR OUTDOOR STORAGE
 RACKS. PLEASE PROVIDE DETAILS VERIFYING THAT THE
 STORAGE RACK WILL COMPLY WITH THE SCREENING
 REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.