| 2013-04-15 07:57:28 | BUILDING PLAN REVIEW |
| | PERMIT: 13030811 |
| | ADD: 4001 S DIXIE HWY |
| | CONT: TBD |
| | TEL: (727)216-6354 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 4/15/2013 |
| | ACTION: DENIED |
| | |
| | 1) COVERSHEET G-010:, |
| | |
| | 1A) THE STRUCTURE WAS DESIGNED TO THE 2007 FBC FAMILY |
| | OF CODES, AS OF MARCH 15 2012 THE 2010 FBC WAS ADOPTED |
| | STATEWIDE. |
| | |
| | 1B) THE WIND DESIGN CRITERIA PRESSURES STATE THEY ARE |
| | ASCE 7-05 WHERE AS THE WIND DESIGN SHOULD BE UNDER ASCE |
| | 7-10/ 2010 FBC-B. IT IS NOTED THAT THE WIND DEISN FOUND |
| | ON S-320 ARE ASCE -7-10 V-ULT BUT THE EXPOSURE IS |
| | INDICATED A "B" EXPOSURE PLEASE REVIEW SECTION 2010 |
| | FBC-B SURFACE ROUGHNESS C. 1609.4.2 SURFACE ROUGHNESS |
| | CATEGORIES. |
| | THIS CATEGORY INCLUDES FLAT OPEN COUNTRY AND |
| | GRASSLANDS.THIS SURFACE ROUGHNESS SHALL ALSO APPLY TO |
| | ANY BUILDING LOCATED WITHIN SURFACE ROUGHNESS B-TYPE |
| | TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET |
| | HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF SURFACE |
| | ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE THAN |
| | 600 FEET (182.9 M) AND WIDTH GREATER THAN 150 FEET IN |
| | THE UPWIND DIRECTION. SHORT-TERM (LESS THAN TWO YEAR) |
| | CHANGES IN THE PRE-EXISTING TERRAIN EXPOSURE,... |
| | THIS CATEGORY INCLUDES FLAT OPEN COUNTRY AND GRASSLANDS |
| | AND SHALL EXTEND DOWNWIND FOR A DISTANCE OF 1500 FEET |
| | THIS WILL AFFECT THE PRRESSURES OF THE WALL AND ROOF |
| | PRESSURES FOR ALL ZONES. |
| | |
| | 2) ON THE FOLLOWING SHEETS WEILDING INFORMATION AS TO |
| | WIDTH AND LENGTH OF WELD HAS BEEN LEFT OFF THE SHEET: |
| | S110 DETAIL 5, S-310 DETAIL # 8, S-330 DETAIL # 4 & |
| | S340 DETAIL #9. |
| | |
| | 3) SHEET S-210 WALL SECTION 6 INCH METAL STUD DOES NOT |
| | PROVIDE HOW IT WILL BE ATTACHED TO THE BOTTOM CHORD OF |
| | THE TRUSS. |
| | |
| | 4) SHEET S-220 & S-230 THE PLANS DO NOT STATE HOW THE |
| | STEEL ANGLES WILL BE ATTACHED TO THE STRUCTURAL STEEL |
| | OR HOW THE 16 GA. CLIPS WILL BE ATTACHED TO THE STEEL |
| | ANGLES? |
| | |
| | 5) THIS PROJECT WILL REQUIRE A RESIDENT INSPECTOR. 2010 |
| | FBC* 110.3.9 RESIDENT INSPECTOR. SUBMIT INSPECTOR |
| | RESUME' AND LICENSE |
| | DOCUMENTS TO KEN CONRAD, DIRECTOR OF THE RESIDENT |
| | INSPECTOR PROGRAM. A RESIDENT INSPECTOR PROGRAM IS |
| | REQUIRED, ON THIS PROJECT, DUE TO ONE OR MORE OF THE |
| | FOLLOWING: |
| | - BUILDINGS/ADDITIONS OF TYPE I OR II CONSTRUCTION |
| | - ANY MAJOR STRUCTURAL ALTERATIONS |
| | - STRUCTURES IN WHICH THE CONCRETE DESIGN IS BASED ON |
| | COMPRESSIVE STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| | - PILE DRIVING |
| | - BUILDINGS OVER 20,000 SQ FT IN AREA |
| | - BUILDINGS OVER 2 STORIES IN HEIGHT |
| | - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS OF |
| | CONSTRUCTION |
| | KEN CONRADS CONTACT INFORMATION: |
| | TEL: (561)805-6666 |
| | E-MAIL: KCONRAD @WPB.ORG |
| | |
| | 6) THREE SETS OF PLANS AND PRODUCT APPROVALS WILL BE |
| | REQUIRED, A THIRD SET OF PLANS WILL BE REQUIRED FOR THE |
| | ON-SITE RESIDENT INSPECTOR. |
| | |
| | 7) WITH THE PROJECT BEING DESIGNED AS A EXPOSURE B THE |
| | PRESSURES WILL INCREASE BEING LOCATED WITHIN A "C" |
| | EXPOSURE. FOR THE PRODUCT APPROVALS THAT DEAL WITH |
| | GLAZINGPLEASE CIRCLE WHICH SYTEM WILL BE INSTALLED IN |
| | THIS PROJECT, PLEASE CIRCLE THE TYPE OF GLAZING, AND IF |
| | MULLIONS ARE REQUIRED PLEASE CIRCLE THE APPROPRIATE IF |
| | RE-INFORCED OR NON-REINFORCED. THEN THE APPROPRIATE |
| | PRESSURES CAN BE |
| | DETERMINED UNTIL THEN NO REVIEW CAN TAKE PLACE ON THESE |
| | ASSEMBLIES. 1609. 5.4.4.1.COMPONENTS AND CLADDING. |
| | |
| | 8) ROOFING PRODUCT APPROVALS, IN EACH OF THESE |
| | APPROVALS THERE ARE SEVERAL SUB-SYSTEMS WITH VARYING |
| | PRESSURES, PLEASE CIRCLE WHICH SUB-SYSTEM WHICH WILL BE |
| | INSTALLED ON THIS PROJECT, VERIFY PRESSURES FOR ZONE 1, |
| | PLEASE NOTE IF THIS APPROVAL WILL ALLOW ENHANCED |
| | FASTENING OR NOT. IF ENHANCED FASTENING IS ALLOWED BY A |
| | DESIGN PROFESSIONAL PLEASE PROVIDE CALCULATION FOR RAS |
| | 117 FOR FLAT DECKS. |
| | 2010 FBC-B 1609.5.2. |
| | |
| | 9) FOR THE CAPRI CONCRETE ROOF TILE NOA 12-0904.07 |
| | CIRCLE WHICH TYPE OF FASTENER WILL BE USED TO SECURE |
| | THE ROOF TILE TO THE DECK BELOW. 2010 FBC-B 1609.5.3. |
| | |
| | 10) THE PLANS NOR THE ROOFING PRODUCT APPROVAL NOA # |
| | 12-0904.07 INDICATE THE FASTENING OF THE RIDGE TILE |
| | PLEASE PROVIDE CODE COMPLIANCE WITH 1507.3.7 AND |
| | FRSA/TRI 07320//8-05. |
| | |
| | 11) UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE |
| | TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS |
| | WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE' |
| | SHALL BE |
| | RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE |
| | RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE |
| | 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| | NOT APPLICABLE. |
| | SEE WEBSITE FOR APPLICATION: |
| | HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| | "APPLICATION FOR UNITY OF TITLE" |
| | |
| | HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| | -38-UNITYOFTITLE3.PDF |
| | |
| | VINCENT J NOEL |
| | SURVEYOR/REAL ESTATE SUPERVISOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33401 |
| | PHONE: 494-1040 EXT: 1096 |
| | FAX: 494-1116 |
| | E-MAIL: [email protected] |
| | |
| | ********************************************* |
| | |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |