Plan Review Details - Permit 13030792
Plan Review Stops For Permit 13030792
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-03-28 Cont ID  
Sent By rlecky Date 2013-03-28 Time 15:12 Rev Time 0.00
Received By rlecky Date 2013-03-28 Time 12:04 Sent To  
Notes
2013-03-28 15:14:2013030792
 1006 HENRIETTA AVE.
 ELECTRIC SERVICE
  
 PLEASE REVISE THE PLAN IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS. THE SCOPE OF ELECTRICAL
 WORK PROPOSED IS NOT CLEAR. IS THE ELECTRICAL SERVICE
 NEW OR IS THIS A REPAIR TO AN EXISTING SERVICE?
  
 PROVIDE AN ELECTRICAL RISER PLAN FOR THE SERVICE. NEC
 215.5
  
 SHOW LOCATION OF ALL SERVICE DISCONNECTS. A BUILDING OR
 OTHER STRUCTURE SERVED SHALL BE SUPPLIED BY ONLY ONE
 SERVICE. MAIN DISCONNECTS SHALL BE GROUPED IN ONE
 LOCATION. NEC 230.2
  
 PROVIDE A GROUND ROD AND GROUNDING ELECTRODE FOR THE
 ELECTRIC SERVICE. NEC 250.32
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-28 Cont ID  
Sent By rlecky Date 2013-03-28 Time 15:14 Rev Time 0.00
Received By rlecky Date 2013-03-27 Time 15:02 Sent To  
Notes
2013-03-27 15:02:28TO ELECTRIC


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved