Plan Review Details - Permit 13030782
Plan Review Stops For Permit 13030782
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-10-28 Cont ID  
Sent By J WITMER Date 2013-10-28 Time 08:07 Rev Time 0.00
Received By jwitmer Date 2013-10-28 Time 06:05 Sent To  
Notes
2013-10-28 07:57:40BUILDING PLAN REVIEW
 PERMIT: 13030782
 ADD: 326 FERN ST
 CONT: STRATICON, LLC
 TEL: (772)210-0200
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: JULY 14-15/ 2013
 ACTION: PASSED/ PROVISO
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED
  
 1) PROVIDE COMPLIANCE WITH : SOUND TRANSMITION 2010
 FBC-B1207.2. WALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES SEPARATING DWELLING UNITS FROM EACH OTHER OR
 FROM PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND
 TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 IF
 FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS OR OPENINGS IN
 CONSTRUCTION ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES;
 RECESSED CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE SEALED, LINED,
 INSULATED OR OTHERWISE TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT APPLY TO DWELLING
 UNIT ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 2) PROVIDE CODE COMPLIANCE WITH: 2010 FBC-B 1207.3
 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-07-15 Cont ID  
Sent By jwitmer Date 2013-07-15 Time 09:01 Rev Time 0.00
Received By jwitmer Date 2013-07-14 Time 09:33 Sent To  
Notes
2013-07-15 09:01:25BUILDING PLAN REVIEW
 PERMIT: 13030782
 ADD: 326 FERN ST
 CONT: STRATICON, LLC
 TEL: (772)210-0200
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: JULY 14-15/ 2013
 ACTION: DENIED
  
 1) SHEET A0.01:
 1A) COMPLIED.
  
 1B) PROJECT SPECIFIC CODE SUMMARY INDICATE THIS PROJECT
 WAS DESIGNED AS A LEVEL IIL ALTERATION. PLEASE REFER TO
 THE 2010 EXISTING BUILDING CODE SECTION 901.3 CHANGE OF
 OCCUPANCY CLASSIFICATION. WHERE THE OCCUPANCY
 CLASSIFICATION OF A BUILDING CHANGES, THE PROVISIONS OF
 SECTIONS 902 THROUGH 912 SHALL APPLY. THIS INCLUDES A
 CHANGE OF OCCUPANCY CLASSIFICATION WITHIN A GROUP AS
 WELL AS A CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE
 GROUP TO A DIFFERENT GROUP.
  
 1C-D) COMPLIED.
  
 1E) COMPLIED. MEETING WITH B.O. ROBERT BROWN GRANTED A
 WAIVER FOR HIGH RISE REQUIREMENTS. THE FINISH FLOOR OF
 THE SIXTH FLOOR IS 76'-0" ABOVE GRADE AND MEETS THE
 DEFINITION OF HIGHRISE DEFINITION 202 FBC-B.
  
 2) THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING.
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
 (3) SETS OF PLANS ARE REQUIRED.
  
 2A) COMPLIED. 109.3.6.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL
 INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A
 WRITTEN STRUCTURAL INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST
 BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 2B) 2ND REQUEST: THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 2C) COMPLIED. THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 -------------------------------------------------------
 -----------------------------------
  
 2D) COMPLIED. 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
 -------------------------------------------------------
 -------------------------------------
  
 2E) 2ND REQUEST: A THRESHOLD PLAN REVIEW STOP WILL BE
 ADDED TO THE PLAN REVIEW FOR THIS PROJECT UNTIL THESE
 ITEMS ARE COMPLETED AS REQUESTED BY THE CHIEF BUILDING
 INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2E)(1)) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2E)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3) COMPLIED.
  
 4A-4E) COMPLIED.
  
 4F)BUILDING PROVISO: CODE ANALYSIS NOTE # 5 INDICATES
 SOUND TRANSMITION FBC-B1207.2 BUT NO COMMENT TO FBC-B
 1207.3 AND COMPLIANCE WITH :
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 5-11) COMPLIED.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-04-18 Cont ID  
Sent By jwitmer Date 2013-04-18 Time 12:13 Rev Time 0.00
Received By jwitmer Date 2013-04-17 Time 10:30 Sent To  
Notes
2013-04-17 16:58:52BUILDING PLAN REVIEW
 PERMIT: 13030782
 ADD: 326 FERN ST
 CONT: STRATICON, LLC
 TEL: (772)210-0200
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: APRIL 17/ 2013
 ACTION: DENIED
  
 1) SHEET A0.01:
 1A) PLEASE REVISE THE GENERAL PROJECT INFORMATION NOTE,
 THAT INDICATES THE SCOPE OF THESE DRAWINGS ARE FOR
 INTERIOR DEMOLITION ONLY.
  
 1B) PROJECT SPECIFIC CODE SUMMARY INDICATE THIS PROJECT
 WAS DESIGNED AS A LEVEL II ALTERATION. PLEASE REFER TO
 THE 2010 EXISTING BUILDING CODE SECTION 901.3 CHANGE OF
 OCCUPANCY CLASSIFICATION. WHERE THE OCCUPANCY
 CLASSIFICATION OF A BUILDING CHANGES, THE PROVISIONS OF
 SECTIONS 902 THROUGH 912 SHALL APPLY. THIS INCLUDES A
 CHANGE OF OCCUPANCY CLASSIFICATION WITHIN A GROUP AS
 WELL AS A CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE
 GROUP TO A DIFFERENT GROUP.
  
 1C) THIS STRUCTURE IS ALSO CLASSIFIED AS A HISTORIC
 STUCRTURE PLEASE INDICATE WHICH METHOD OF COMPLIANCE
 YOU WOULD BE CLAIMING UNDER THE HISTORICAL DESIGNATION.
 SECTION 1104 EQUIVALENCY, SECTION 1105 COMPLIANCE OR
 SECTION 1106 INVESTIGATION AND EVALUATION.
  
 1D) THE COVERSHEET ALSO REFERENECES THE PALM BEACH
 COUNTY AMENDMENTS. THE PALM BEACH COUNTY AMENDMENTS
 WILL ONLY PERTAIN TO
 CHAPTER 1 AND ONLY IF THIS PROJECT WAS LOCATED IN THE
 COUNTY. THE CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 PLEASE UPDATE.
  
 1E) THE FINISH FLOOR OF THE SIXTH FLOOR IS 76'-0" ABOVE
 GRADE AND MEETS THE DEFINITION OF HIGHRISE DEFINITION
 202 FBC-B.
  
 2) THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING.
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 2C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 -------------------------------------------------------
 -----------------------------------
  
 2D) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
 -------------------------------------------------------
 -------------------------------------
  
 2E) A THRESHOLD PLAN REVIEW STOP WILL BE ADDED TO THE
 PLAN REVIEW FOR THIS PROJECT UNTIL THESE ITEMS ARE
 COMPLETED AS REQUESTED BY THE CHIEF BUILDING INSPECTOR
 KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2E)(1)) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2E)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3) SHEET A2.001 LS- BASEMENT:
 3A) THE STAIRWELL # 1 HAS THE ELEVATOR LOCATED IN THE
 VERTICAL EXIT. 2010 EXISTING BUILDING CODE
 912.1.1COMPLIANCE WITH CHAPTER 8.
 SEE COMPLIANCE WITH 801.2 COMPLIANCE. IN ADDITION TO
 THE PROVISIONS OF THIS CHAPTER, WORK SHALL COMPLY WITH
 ALL OF THE REQUIREMENTS OF CHAPTERS 6 AND 7. THE
 REQUIREMENTS OF SECTIONS 703, 704, AND 705 SHALL APPLY
 WITHIN ALL WORK AREAS WHETHER OR NOT THEY INCLUDE EXITS
 AND CORRIDORS SHARED BY MORE THAN ONE TENANT AND
 REGARDLESS OF THE OCCUPANT LOAD. 703.2.1 EXISTING
 VERTICAL OPENINGS.
 ALL EXISTING INTERIOR VERTICAL OPENINGS CONNECTING TWO
 OR MORE FLOORS SHALL COMPLY WITH THE APPROPRIATE
 SECTIONS OF THE FLORIDA FIRE PREVENTION CODE. 2010
 FBC-B 10.22.3 ELEVATORS SHALL NOT OPEN INTO AN EXIT
 ENCLOSURE.
  
 3B) NEITHER THIS SHEET NOR A2.01 SHOW THE WALLS OR
 OPENING PROTECTIVES TO BE FIRE RATED BARRIERS. 2010
 FBC-B 913.2.1 PROTECTION OF FIRE PUMP ROOMS.
 FIRE PUMPS SHALL BE LOCATED IN ROOMS THAT ARE SEPARATED
 FROM ALL OTHER AREAS OF THE BUILDING BY 2-HOUR FIRE
 BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 2-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE
 WITH SECTION 712, OR BOTH. EXISTING BUILDING CODE
 912..2 FIRE PROTECTION SYSTEMS.
  
 4) SHEET A2.002 LS- 1ST FLOOR:
 4A) FIRE COMMAND ROOM FBC-B 403.4.5 SEE SECTION 911 1
 HOUR FIRE SEPERATION.
  
 4B) THE AREA LISTED AS MERCANTILE OR RESTARAUNT MAY
 ALSO MEET THE OCCUPANCY LOAD FOR AN A2 ASSEMBLY IF THE
 OCCUPANT LOAD IS OVER 50.
 THE IF THE RESTARAUNT IS LESS THAN 50 IT WILL BE
 CONSIDERED MERCANTILE. THE OCCUPANT LOADING FOR
 MERCANTILE AT GRADE IS 30 SQ FT / OCCUPANT BUT THE A2
 ASSEMBLY IS FIGURED AT 15 SQ FT / OCCUPANT IF THE SPACE
 IS GOING TO SELL GROCERCIES IT WILL BE CONSIDERED
 MERCANTILE
 BUT IF THE RENTAL SPACE WILL BE CONSIDERED A RESTARAUNT
 USE THE 15 SQ FT /OCCUPANT. 2010 FBC-B TABLE 1004.1.1.
  
 4C) THE OCCUPANCY SEPERATION WALL BETWEEN THE R2
 OCCUPANCY AND THE BUSINESS & ASSEMBLY (COMMUNITY ROOM #
 102) IS NOT A CONTINIOUS SEPERATION AND OR OPENING
 PROTECTIVES, PLEASE IDENTIFY? 2010 FBC-B TABLE 508.4 &
 TABLE 715.4.
  
 4D) FOR BOTH VERTICAL EXITS THAT OPEN ONTO THIS FLOOR
 AND THEN CONTINUE INTO THE BASEMENT, PLEASE PLACE EXIT
 DIRECTIONAL SIGNAGE PER
 (2010 FBC-B 1022.7) TO PREVENT PERSONS FROM
 UNINTENIONALLY CONTINUING INTO LEVELS BELOW GRADE.
  
 4E) ALSO REVIEW FBC-B 1009.6.4 STAIR IDENTIFICATION &
 1022.8 FLOOR IDENTIFICATION.
  
 4F) CODE ANALYSIS NOTE # 5 INDICATES SOUND TRANSMITION
 FBC-B1207.2 BUT NO COMMENT TO FBC-B 1207.3 AND
 COMPLIANCE WITH :
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 5) SHEET A2.00.3 LS 2ND FLOOR:
 5A) COMMON STATEMENT FOR THE 2ND -6TH FLOOR. PLANS ARE
 MISSING THE ELEVATOR LOBBY FBC-B 708.14.1. 2010
 EXISTING BLDG CODE SECTION
 703.2.2. SUPPLEMENTAL SHAFT AND FLOOR OPENING ENCLOSURE
 REQUIREMENTS. WHERE THE WORK AREA ON ANY FLOOR EXCEEDS
 50 PERCENT OF THAT FLOOR AREA, THE ENCLOSURE
 REQUIREMENTS OF SECTION 703.2 SHALL APPLY TO VERTICAL
 OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE FLOOR.
  
 5B) COMMON STATEMENT FOR THE 2ND -6TH FLOOR AT GRID
 LINES E BETWEEN 4 &5. THIS AREA IS SHARED BETWEEN 3
 TENANTS, THE CONCERN IS IF A FIRE IS STARTED WITHIN
 THIS AREA THE THREE UNITS WILL BE EFFECTED BY NOT
 HAVING FIRE RATED GLASS IN THE WINDOWS & DOORS. THE
 PLANS DO STATE THESE OPENINGS WILL HAVE LARGE MISSILE
 IMPACT RESISTANT GLAZING IN THE OPENINGS, WE WOULD BE
 LESSS CONCERNED WITH THE FIRE RATED GLASS IF THIS AREA
 IS TO BE FIRE SPRINKLERED SINCE THERE ARE CURRENTLY NO
 FIRE SPRINKLER PLANS THAT WERE SUBMITTED IN THIS SET OF
 PLANS. FBC-B 403.3.
  
 6) SHEET A3.01.1 & A3.01.2ELEVATIONS, PRESSURES &
 PRODUCT APPROVALS:
 6A) THE LIST OF PRODUCT APPROVALS IS NOT ENOUGH TO BE
 ABLE TO DO A COMPLETE REVIEW OF THE LISTED PRODUCTS.
 THE CITY WILL REQUIRE PRODUCT APPROVALS FOR ALL
 COMPONENTS AND CLADDING THAT WILL BE INSTALLED ON THE
 EXTERIOR OF THIS PROJECT. A LIST IS NOT SUFFICIENT
 ENOUGH, TO BE ABLE TO DO A REVIEW OF THE PRODUCT. (3)
 COPIES OF EACH PRODUCT WILL BE REQUIRED SINCE THIS IS A
 THRESHOLD BUILDING. 2010 WPB ADMIN CODE 107.3
 EXAMINATION OF DOCUMENTS/ 2010 FBC-B 1609.6.4.4.1.
 COMPONENTS & CLADDING.
  
 6B) FOR GLAZING PRODUCT APPROVALS PLEASE CIRCLE THE
 LENGTH, WIDTH, TYPE OF GLAZING, MULLIONS AND PRESSURES
 SO WE WILL KNOW WHICH OPTIONS YOU ARE SELECTING.
  
 6C) ROOFING PRODUCT APPROVALS, WILL HAVE VARIOUS
 SUB-SYSTEMS THAT CAN BE INSTALLED UNDER VARYING
 CONDITIONS AND ASSOCATED PRESSURES. PLEASE HIGHLIGHT
 WHICH OF THESE SUB-SYSTEMS WILL BE INSTALLED ON THIS
 PROJECT, IF MORE THAN ONE SUB-SYSTEM WILL BE INSTALLED
 PLEASE IDENTIFY EACH AND THE LOCATION OF THE
 INSTALATION. NOTE IF THE PRODUCT APPROVALS HAS
 LIMITATIONS ON ENHANCED FASTENING IN ZONES 2 & 3. IF
 ALLOWED PROVIDE RAS 117 CALCULATIONS PREPARED BY A
 DESIGN PROFESSIONAL. 1609.6.4.3.
  
 6D) PLEASE NOTE THE LISTED PRODUCT NOA 09-0804.05 ROOF
 TOP A/C RACK +/- 75 , SHEET S0.02 INDICATES TTHE ROOF
 TOP PRESSUES IN VULT
 ZONE 1 VULT -122.1= -73,26 VASD
 ZONE 2 &3 VULT -191.7= -115.02 VASD
 PLEASE ALSO REVIEW FBC-B 1609.8 FOR ROOF TOP STRUCTURES
 AND EQUIPMENT AAND MULTIPLIERS TO BE USED.
 IT APPEARS THIS PRODUCT WILL NOT MEET THE ASSOCIATED
 PRESSURES FOR ANY ZONE. THERE ARE ALOT OF A/C ROOFTOP
 UNITS THAT ARE LOCATED WITHIN ZONE 2 WITH THE INCREASED
 PRESSURES.
  
 6E) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6F) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES ROOFTOP EQUIPMENT/
 EXHAUST FANS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 6G) SHEET SHEET A3.01.2 DETAIL SOUTH ELEVATION BALCONY
 AREA, PLEASE PROVIDE A SUMMARY OF PRESSURES FOR THE
 INSET BALCONY AREA. WIND DESIGN IS TO BE TAKEN FORM ALL
 DIRECTIONS, IF SUCH WHEN THE WIND WOULD BE FROM THE
 SOUTHEAST THIS AREA IS LIKE A PARTIALLY ENCLOSED
 BUILDING THAT WILL ALLOW THE WIND TO ENTER AND
 PRESSUREIZE THIS AREA GREATER THAN THE SURROUNDING
 SURFACES WHERE THE WIND WOULD BE ABLE TO RACE ACROSS
 THE FRONT. THE SECOND EFFECT IS IF THE WIND DIRECTION
 IS FROM THE NORTH EAST WHERE A VENTURI-EFFECT TAKES
 PLACE SIMILAR TO AN END ZONE WHERE THE NEGATIVE
 PRESSURES WILL BE HIGHER? 1609.4.1 WIND DIRECTION AAND
 SECTORS.
  
 7) SHEET A4.02N DOOR # 21A IS MISSING FIRE RATING PER
 FBC-B 911.1.2 OPENING PROTECTION TABLE 715.4.
  
 8SHEET A4.02S DOOR # 19 STAAIRWELL DOOR MISSING FIRE
 RATING OPENING PROTECTIVES T 715.4.
  
 9) SHEET A4-10 :
 9A) LOBBY TOILET ROOM INDICATES THE ACCESSIBLE WATER
 CLOSET IS 1'-8" AWAY FROM THE SIDE WALL NOT 18" PLEASE
 SEE 2010 FL ACC CODE 604.2.
  
 9B) DETAIL # 7 RETAIL WATER CLOSET ROOM IS INDICATED TO
 BE 2'-0" AWAY FROM THE SIDE WALL. 2010 FL ACC CODE
 604.2.
  
 10) A8.01 DETAIL 4 WALL TYPE A.4 DOES NOT PROVIDE THE
 FBC-B 1207.2 AIR-BORNE SOUND.
  
 11) SHEET A8.02 WINDOW BUCK DETAILS INDICATE A BEVELED
 BUCK THAT DOES NOT EXTEND TO THE BACK WINDOW FLANGE, NO
 SUPPORT. FBC-B 1715.5.4.2 MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBSTRATE. UNLESS OTHERWISE TESTED, BUCKS
 SHALL EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW OR
 DOOR FRAME SUCH THAT FULL SUPPORT OF THE FRAME IS
 PROVIDED. SHIMS SHALL BE MADE FROM MATERIALS CAPABLE OF
 SUSTAINING APPLICABLE LOADS, LOCATED AND APPLIED IN A
 THICKNESS CAPABLE OF SUSTAINING APPLICABLE LOADS.
 ANCHORS SHALL BE PROVIDED TO TRANSFER LOAD FROM THE
 WINDOW OR DOOR FRAME ASSEMBLY TO THE SECURED WOOD BUCK.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-11-19 Cont ID  
Sent By D HARVEY Date 2013-11-19 Time 16:38 Rev Time 0.00
Received By skennedy Date 2013-11-19 Time 16:38 Sent To  
Notes
2013-11-19 16:38:45RESTAMP

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-07-02 Cont ID  
Sent By dharvey Date 2013-07-02 Time 13:47 Rev Time 0.00
Received By dharvey Date 2013-07-02 Time 12:52 Sent To  
Notes
2013-07-02 13:47:51RESTAMP. RL

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-05-30 Cont ID  
Sent By dharvey Date 2013-05-30 Time 15:53 Rev Time 0.00
Received By dharvey Date 2013-05-30 Time 15:53 Sent To  
Notes
2013-05-30 15:55:555-30-13
  
 PROVISIO - APPROVED WITH EXCEPTIONS
  
 1. ALL DISCONECTS TO BE LABELED PER NEC 110.22A
 2. COMPLY TO NEC 410.130G - FLUORESCENT FIXTURES TO
 HAVE INDIVISUAL DISCONNECT SWITCHES
 3. COMPLY TO NEC 210.4, MULTI BRANCH CIRCUITING
 VB
2013-05-06 13:20:29WAITING FOR A CALL FROM URSULA ADDRESSING PREVIOUS
 ITEMS

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-10-07 Cont ID  
Sent By W JOLIN Date 2013-10-07 Time 12:23 Rev Time 0.00
Received By scaldero Date 2013-10-07 Time 12:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-07-13 Cont ID  
Sent By wjolin Date 2013-07-13 Time 16:44 Rev Time 0.00
Received By wjolin Date 2013-07-10 Time 09:43 Sent To  
Notes
2013-07-10 15:23:51326 FERN STREET
 PERMIT #13030782
 REVIEW #2 COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT/RESUBMIT DRAWINGS ADDRESSING THE
 FIRE REVIEW COMMENTS*****
  
 SHEET A2.00.1: ACCESS TO AN EXIT IS NOT PERMITTED TO BE
 ROUTED THROUGH A STORAGE ROOM ("NEW TENANT STORAGE")
 PER NFPA 101 SECTION 7.5.2.1.
  
  
 ELEVATORS: CONFIRM EXISTING ELEVATORS CONFORM TO THE
 FIREFIGHTERS' EMERGENCY OPERATIONS REQUIREMENTS OF ASME
 A17.3.
  
  
 RESPONSE: THE FIRE DEPARTMENT HAS BEEN REVIEWING AND
 INSPECTING THIS BUILDING AS AN EXISTING HIGH-RISE
 BUILDING; THEREFORE, THE BUILDING AND FIRE CODE
 REQUIREMENTS FOR A "NEW" HIGH-RISE ARE NOT APPLICABLE.
 WITH THAT BEING SAID, THERE ARE CERTAIN SYSTEMS, SUCH
 AS THE FIRE ALARM SYSTEM, THAT NEED TO BE UPGRADED WITH
 THE CHANGE OF OCCUPANCY TO ENSURE THE SAFETY OF THE
 BUILDING OCCUPANTS AND EMERGENCY RESPONDERS. NOTE: THE
 FIRE ALARM DRAWINGS WERE NOT RESUBMITTED FOR REVIEW #2.
  
 REPEAST COMMENT - FIRE ALARM: PER NFPA 101 SECTION
 11.8.4.1, A FIRE ALARM SYSTEM USING AN APPROVED
 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM SHALL BE
 INSTALLED. PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION
 MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN
 REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT, AND
 EXIT THE BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR.
  
 REPEAST COMMENT - FIRE ALARM: PER NFPA 101
 SECTION11.8.4.2.1 TWO-WAY TELEPHONE COMMUNICATION
 SERVICE SHALL BE PROVIDED FOR FIRE DEPARTMENT USE. THIS
 SYSTEM SHALL BE IN ACCORDANCE WITH NFPA 72, NATIONAL
 FIRE ALARM CODE. THE COMMUNICATIONS SYSTEM SHALL
 OPERATE BETWEEN THE EMERGENCY COMMAND CENTER AND EVERY
 ELEVATOR CAR, EVERY ELEVATOR LOBBY, AND EACH FLOOR
 LEVEL OF EXIT STAIRS.
  
 REPEAST COMMENT - FIRE ALARM: PLANS DO NOT INDICATE THE
 METHOD (HEAT DETECTOR/FLOW SWITCH WITHOUT TIME DELAY)
 USED TO SHUNT TRIP POWER TO THE ELEVATOR IN THE EVENT
 AN AUTOMATIC SPRINKLER ACTIVATES IN THE ELEVATOR
 MACHINE ROOM.
  
 REPEAST COMMENT - FIRE ALARM: PLANS INDICATE BOTH A
 HEAT AND SMOKE DETECTOR AT THE TOP OF THE ELEVATOR
 SHAFTS. PER NFPA 72 SECTION 21.3.6 (2010 ED), SMOKE
 DETECTORS SHALL NOT BE INSTALLED IN UNSPRINKLERED
 ELEVATOR HOISTWAYS UNLESS THEY ARE INSTALLED TO
 ACTIVATE THE ELEVATOR HOISTWAY SMOKE RELIEF EQUIPMENT.
  
 REPEAST COMMENT - FIRE ALARM: ADD THE WATERFLOW AND
 TAMPER SWITCH SYMBOLS TO THE LEGEND.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-04-04 Cont ID  
Sent By wjolin Date 2013-04-04 Time 14:14 Rev Time 0.00
Received By wjolin Date 2013-04-03 Time 11:22 Sent To  
Notes
2013-04-03 13:43:17326 FERN STREET
 PERMIT #13030782
 REVIEW COMMENTS - FIRE DEPARTMENT
 *****THIS IS A CHANGE OF OCCUPANCY FROM BUSINESS TO
 APARTMENT OCCUPANCY*****
  
 NOTE: ANY REFERENCE TO NFPA 101 - THE LIFE SAFETY CODE
 IS REFERRING TO THE 2010 EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF NFPA
 101 WITH FLORIDA AMENDMENTS.
  
  
 GENERAL: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE
 DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE
 EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR
 MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE SUBMITTED IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 SITE: THE EXISTING SPRINKLER SYSTEM FIRE DEPARTMENT
 CONNECTION IS SURFACE MOUNTED (FERN STREET) ON THE FACE
 OF THE BUILDING. THE CURRENT PARKING SPACE AND METER
 NEEDS TO BE REMOVED AND THE SPACE SHOULD BE IDENTIFIED
 WITH A PERMAMENT FREE STANDING SIGN INDICATING, "FDC -
 NO PARKING BY ORDER OF THE FIRE MARSHAL." SIGN SHALL BE
 12" X 18" WITH A WHITE BACKGROUND AND RED LETTERS AND
 SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE
 BOTTOM OF THE SIGN.
  
 GENERAL: PER NFPA 101 SECTION 7.2.2.5.4 - STAIRWAY
 IDENTIFICATION: NEW ENCLOSED STAIRS SERVING THREE OR
 MORE STORIES AND EXISTING ENCLOSED STAIRS SERVING FIVE
 OR MORE STORIES SHALL COMPLY WITH (A) THROUGH (L).
 (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE
 WITHIN THE ENCLOSURE AT EACH FLOOR LANDING.
 (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL.
 (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP
 AND BOTTOM OF THE STAIR ENCLOSURE.
 (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF
 THE STAIR ENCLOSURE.
 (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND
 THE DIRECTION TO, EXIT DISCHARGE.
 (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE
 APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A
 POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN
 OR CLOSED POSITION.
 (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE.
 (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE
 WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE
 WALL.
 (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED
 AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH
 LETTERING.
 (J) SIGNAGE THAT READS "NO ROOF ACCESS" AND IS LOCATED
 UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL
 DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS.
 LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH.
 (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE
 MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS.
 MEZZANINE LEVELS SHALL HAVE THE LETTER "M" OR OTHER
 APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR
 NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER "B"
 OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING
 THE FLOOR LEVEL NUMBER.
 (M) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF
 THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN
 IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS.
  
 ELEVATORS: CONFIRM EXISTING ELEVATORS CONFORM TO THE
 FIREFIGHTERS' EMERGENCY OPERATIONS REQUIREMENTS OF ASME
 A17.3.
  
 SHEET A0.01: PROVIDE BUILDING ADDRESS VISIBLE FROM THE
 STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING AND
 BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND
 SHALL CONTRAST THE BACKGROUND PER NFPA 1 SECTION
 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA 1.
  
 SHEET A2.00.1LS: PER NFPA 101 SECTION 7.2.2.5.4.2:
 WHEREVER AN ENCLOSED STAIR REQUIRES TRAVEL IN AN UPWARD
 DIRECTION TO REACH THE LEVEL OF EXIT DISCHARGE, SPECIAL
 SIGNS WITH DIRECTIONAL INDICATORS SHOWING THE DIRECTION
 TO THE LEVEL OF EXIT DISCHARGE SHALL BE PROVIDED AT
 EACH FLOOR LEVEL LANDING FROM WHICH UPWARD DIRECTION OF
 TRAVEL IS REQUIRED.
  
 SHEET A2.00.1LS: PER NFPA 101 SECTION 9.4.7 ELEVATORS
 SHALL NOT OPEN INTO AN EXIT ENCLOSURE.
  
 SHEET A2.00.2LS: RETAIL #100 IS INDICATED AS POSSIBLY
 BEING A FUTURE RESTAURANT. THIS WILL CHANGE THE
 OCCUPANCY FROM MERCANTILE TO ASSEMBLY REQUIRING TWO
 SEPARATE EXITS. THE CURRENT EXITING SCHEME SHOWS THE
 SECONDARY EXIT ROUTED THROUGH THE RESIDENTIAL LOBBY
 WHICH WOULD NOT BE PERMITTED UTILIZING A DESIGN OF
 "SEPARATED MIXED-USE." NOTE: THE MERCANTILE OCCUPANCY
 REQUIRES ONLY ONE EXIT SO THE CURRENT LAYOUT IS NOT AN
 ISSUE.
  
 SHEET A2.00.2LS: PER NFPA 101 SECTION 7.5.1.1.1, WHERE
 EXITS ARE NOT IMMEDIATELY ACCESSIBLE FROM AN OPEN FLOOR
 AREA, CONTINUOUS PASSAGEWAYS, AISLES, OR CORRIDORS
 LEADING DIRECTLY TO EVERY EXIT SHALL BE MAINTAINED AND
 SHALL BE ARRANGED TO PROVIDE ACCESS FOR EACH OCCUPANT
 TO NOT LESS THAN TWO EXITS BY SEPARATE WAYS OF TRAVEL.
 CORRIDOR #C101 DOES NOT APPEAR TO HAVE A FIRE
 RESISTANCE RATING ALL THE WAY TO THE EXIT DOOR. PER
 NFPA 101 SECTION 30.3.6.1.2, IN BUILDINGS PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM, CORRIDOR WALLS SHALL HAVE A MINIMUM
 1/2-HOUR FIRE RESISTANCE RATING AND DOORS THAT OPEN
 ONTO EXIT ACCESS CORRIDORS SHALL HAVE NOT LESS THAN A
 20-MINUTE FIRE PROTECTION RATING. PROTECT ALL OPENINGS
 AND PENETRATIONS.
  
 SHEET A2.00.2LS: ANOTHER EXIT SIGN IS NEEDED AT THE TOP
 OF THE SMALL STAIR ADJACENT TO THE WHEELCHAIR LIFT IN
 CORRIDOR #C101.
  
 SHEET A2.00.2LS: RETAIL #100 - ALL EXTERIOR DOORS NOT
 FUNCTIONING AS EXITS SHALL BE PERMANENTLY MARKED AND
 CLEARLY INDICATED AS, "NOT AN EXIT."
  
 SHEET A2.00.2LS: COMMUNITY ROOM #102 - TABLES AND
 CHAIRS ARE OBSTRUCTING THE EXIT DOORS.
  
 SHEET A2.00.2LS: LAUNDRY ROOM (#115) LARGER THAN 100
 SQ.FT. SHALL BE SEPARATED FROM OTHER AREAS BY A 1-HOUR
 FIRE RATED BARRIER PER TABLE 30.3.2.1.1 OF NFPA 101.
 PROTECT ALL OPENINGS AND PENETRATIONS.
  
 SHEET A4.02S: DOOR (#1) LOCATED IN STAIR ENCLOSURE
 VESTIBULE (C104) NEEDS A FIRE RESISTANCE RATING OF
 90-MINUTES. ALSO CONFIRM VESTIBULE IS FIRE RATED FOR
 2-HOURS.
  
 SHEET A4.02S: ELECTRICAL ROOM DOORS SHALL BE EQUIPPED
 WITH PANIC/FIRE EXIT HARDWARE PER NFPA 70 SECTION
 110.26.
  
 SHEET M1.2N: FIRE DAMPERS WILL BE NEEDED FOR DUCTWORK
 PENETRATING LAUNDRY ROOM WALLS. LAUNDRY ROOM (#115)
 LARGER THAN 100 SQ.FT. SHALL BE SEPARATED FROM OTHER
 AREAS BY A 1-HOUR FIRE RATED BARRIER PER TABLE
 30.3.2.1.1 OF NFPA 101.
  
 SHEET M1.2N: UNPROTECTED EXHAUST DUCT IS ROUTED THROUGH
 A 2-HOUR FIRE BARRIER. EXHAUST DUCT IS SERVING ADJACENT
 RETAIL SPACE BATHROOM.
  
 SHEET E0.1: "ELECTRICAL RESIDENTIAL UNIT NOTES" #2
 INDICATES THAT THE SMOKE/CARBON MONOXIDE ALARMS SHALL
 BE TIED INTO THE THE FIRE ALARM SYSTEM. THE SMOKE/CO
 ALARMS IN THE INDIVIDUAL APARTMENT UNITS SHALL BE LOCAL
 ALARM ONLY AND SHALL NOT RESULT IN ACTIVATION OF THE
 BUILDING FIRE ALARM SYSTEM.
  
 SHEET E1.2S: SMOKE ALARM OMITTED FROM RESIDENTIAL UNIT
 #105.
  
 FIRE ALARM: PER NFPA 101 SECTION 11.8.4.1, A FIRE ALARM
 SYSTEM USING AN APPROVED EMERGENCY VOICE/ALARM
 COMMUNICATION SYSTEM SHALL BE INSTALLED. PROVIDE A
 PRE-RECORDED FIRE ALARM EVACUATION MESSAGE NOTIFYING
 OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN THE
 BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR.
  
 FIRE ALARM: PER NFPA 101 SECTION11.8.4.2.1 TWO-WAY
 TELEPHONE COMMUNICATION SERVICE SHALL BE PROVIDED FOR
 FIRE DEPARTMENT USE. THIS SYSTEM SHALL BE IN ACCORDANCE
 WITH NFPA 72, NATIONAL FIRE ALARM CODE. THE
 COMMUNICATIONS SYSTEM SHALL OPERATE BETWEEN THE
 EMERGENCY COMMAND CENTER AND EVERY ELEVATOR CAR, EVERY
 ELEVATOR LOBBY, AND EACH FLOOR LEVEL OF EXIT STAIRS.
  
 FIRE ALARM: PLANS DO NOT INDICATE THE METHOD (HEAT
 DETECTOR/FLOW SWITCH WITHOUT TIME DELAY) USED TO SHUNT
 TRIP POWER TO THE ELEVATOR IN THE EVENT AN AUTOMATIC
 SPRINKLER ACTIVATES IN THE ELEVATOR MACHINE ROOM.
  
 FIRE ALARM: PLANS INDICATE BOTH A HEAT AND SMOKE
 DETECTOR AT THE TOP OF THE ELEVATOR SHAFTS. PER NFPA 72
 SECTION 21.3.6 (2010 ED), SMOKE DETECTORS SHALL NOT BE
 INSTALLED IN UNSPRINKLERED ELEVATOR HOISTWAYS UNLESS
 THEY ARE INSTALLED TO ACTIVATE THE ELEVATOR HOISTWAY
 SMOKE RELIEF EQUIPMENT.
  
 FIRE ALARM: ADD THE WATERFLOW AND TAMPER SWITCH SYMBOLS
 TO THE LEGEND.
  
 FIRE ALARM: PROVIDE NOTIFICATION APPLIANCE IN LAUNDRY
 ROOM #115.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2013-11-19 Cont ID  
Sent By FMITTNER Date 2013-11-19 Time 12:29 Rev Time 0.00
Received By fmittner Date 2013-11-19 Time 12:29 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2013-07-26 Cont ID  
Sent By fmittner Date 2013-07-26 Time 16:51 Rev Time 0.00
Received By fmittner Date 2013-07-26 Time 16:51 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2013-04-26 Cont ID  
Sent By fmittner Date 2013-04-26 Time 10:26 Rev Time 0.00
Received By fmittner Date 2013-04-26 Time 10:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-11-19 Cont ID  
Sent By skennedy Date 2013-11-19 Time 16:38 Rev Time 0.00
Received By skennedy Date 2013-11-07 Time 07:39 Sent To  
Notes
2013-11-08 11:12:39 
 11/7/13 SUBMITTED NEW SHEETS, IMPACT FEES AND SPECIAL
 INSPECTOR AGREEMENT. SENT TO JIM'S DESK FOR
 COORDINATION.
2013-10-02 07:39:55C28 - FULL SET OF NEW PLANS WAS SUBMITTED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-14 Cont ID  
Sent By shill Date 2013-08-14 Time 15:54 Rev Time 0.00
Received By shill Date 2013-06-14 Time 09:43 Sent To  
Notes
2013-06-15 09:43:21INCOMING SENT TO C-31 BOX . JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-30 Cont ID  
Sent By dharvey Date 2013-05-30 Time 15:56 Rev Time 0.00
Received By dharvey Date 2013-05-30 Time 15:56 Sent To  
Notes
2013-03-27 16:29:24C--28

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2013-11-19 Cont ID  
Sent By jwitmer Date 2013-11-12 Time 10:31 Rev Time 0.00
Received By jwitmer Date 2013-11-12 Time 10:30 Sent To  
Notes
2013-11-12 10:33:47IMPACT FEES
 RECEIPT # 2013-1107-48
 $271,757.57. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2013-10-28 Cont ID  
Sent By jwitmer Date 2013-10-28 Time 08:29 Rev Time 0.00
Received By jwitmer Date 2013-10-28 Time 08:29 Sent To  
Notes
2013-10-28 08:30:34BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-10-28 Cont ID  
Sent By jwitmer Date 2013-10-28 Time 08:29 Rev Time 0.00
Received By jwitmer Date 2013-10-28 Time 08:29 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-04-17 Cont ID  
Sent By jwitmer Date 2013-04-17 Time 10:30 Rev Time 0.00
Received By jwitmer Date 2013-04-17 Time 10:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-11-04 Cont ID  
Sent By H MOSER Date 2013-11-04 Time 15:17 Rev Time 0.00
Received By hmoser Date 2013-11-04 Time 12:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-07-26 Cont ID  
Sent By hmoser Date 2013-07-26 Time 14:45 Rev Time 0.00
Received By hmoser Date 2013-07-26 Time 09:40 Sent To  
Notes
2013-07-26 14:45:43PASS PROVISO
 1) IN REGARDS TO DRYER DUCT SHAFT REFER TO SECTION
 607.5.5 #2
 SHAFT ENCLOSURES 2010 FBC (M) AND 909.11 POWER SYSTEMS
 2010 FBC.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-04-05 Cont ID  
Sent By hmoser Date 2013-04-05 Time 13:59 Rev Time 0.00
Received By hmoser Date 2013-04-04 Time 14:46 Sent To  
Notes
2013-04-05 13:59:13PLANS DENIED
 1) REFER TO SECTION 607.5.5 SHAFT ENCLOSURES
 2010 FBC (M)
 2) DUCT PENETRATING STAIR WELL PAGE M1.25. REFER TO
 SECTION
 1022.4 FBC
 3) MISSING SMOKE FIRE DAMPER IN SHAFT BY TRASH ROOM
 PAGE M 1.25
 PER SECTION 607 FBC (M) 2010
 4) REFER TO SECTION 713.3 FIRE RESISTANCE RATED WALLS
 FBC 2010
 PROVIDE A DETAIL ON THE PLANS ON HOW YOU WILL PROTECT
 THE PENETRATIONS
 OF THE EXHAUST AND FREON LINES IN THE RATED WALLS.
 5) PROVIDE A DETAIL ON THE PLANS FOR THE CURB TO ROOF
 TIEDOWN.
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M) .
 6) PROVIDE EQUIPMENT SCHEDULE ON THE PLANS.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2013-11-04 Cont ID  
Sent By lwagner Date 2013-11-04 Time 15:59 Rev Time 0.00
Received By lwagner Date 2013-11-04 Time 15:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-06-27 Cont ID  
Sent By lwagner Date 2013-06-27 Time 09:58 Rev Time 0.00
Received By lwagner Date 2013-06-25 Time 13:31 Sent To  
Notes
2013-06-25 15:03:24****PROVISO****
  
 1. THE AAV'S SHOWN ON P-1.2 & P2.1 WILL BE REQUIRED TO
 BE VENTED AS THEY ARE NOT WITHIN THE TOP FOUR BRANCH
 INTERVALS.
 FBC PLUMBING 917.3.1
  
 2. THE CONNECTIONS TO THE SOVENT HORIZONTAL LINE AFTER
 THE DEAERATOR ON P1.2S, P1.3N, P1.3S, AND P2.1 ARE TO
 CONNECT ABOVE THE CENTER LINE. SEE DETAIL # 16 ON P0.3
 SOVENT RULE B3:
 SOIL AND WASTE CONNECTIONS BETWEEN
 THE CENTER LINE OF THE
 SOVENT STACK AND TERMINATION
 POINT IN THE BUILDING DRAIN IS ALLOWED.
 CONNECTIONS MUST BE
 MADE ABOVE THE CENTER LINE OF THE
 BUILDING DRAIN, OR THE CONNECTIONS
 CAN BE MADE 10 STACK PIPE DIAMETERS
 DOWN STREAM. (DWG. 101-6B)

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-04-09 Cont ID  
Sent By lwagner Date 2013-04-09 Time 11:16 Rev Time 0.00
Received By lwagner Date 2013-04-04 Time 14:41 Sent To  
Notes
2013-04-04 15:52:15 
 FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
  
 1. PLEASE SUBMIT THE DATA REQUIRED FOR THE SOVENT
 SYSTEM. IF THE SOVENT IS CONINE, DE-AERATOR RULE (D):
 SOIL AND WASTE BRANCHES MAY CONNECT TO THE SOVENT
 BUILDING DRAIN BETWEEN THE CENTERLINE OF THE STACK AND
 THE TERMINATION POINT OF THE PRESSURE RELIEF LINE
 (PRL). ALL CONNECTIONS SHALL BE MADE A MINIMUM DISTANCE
 OF TEN PIPE
 DIAMETERS (BASED ON STACK SIZE) DOWNSTREAM FROM THE
 CENTERLINE OF THE STACK. SOIL AND WASTE BRANCHES SHALL
 NOT CONNECT
 WHERE THE SOVENT BUILDING DRAIN MAKES A HORIZONTAL
 CHANGE OF DIRECTION (EXAMPLE ON P2.1 S6)
  
 P-714.4.3 TECHNICAL DATA. THE REGISTERED DESIGN
 PROFESSIONAL SHALL SUBMIT SUFFICIENT TECHNICAL DATA TO
 SUBSTANTIATE THE PROPOSED ALTERNATIVE ENGINEERED DESIGN
 AND TO PROVE THAT THE PERFORMANCE MEETS THE INTENT OF
 THIS CODE.
  
 2. SHEET A4.10 THE COMMON AREA TOILET ROOMS ARE TO BE
 BETWEEN 16" - 18" MAX. OFF THE SIDE WALL. ACCESSABILITY
 604.2 LOCATION.
  
 *PROVISO*
 FOR THE DOMESTIC PUMPS SHOWN ON P0.2:
 606.5.5 LOW-PRESSURE CUTOFF REQUIRED ON BOOSTER PUMPS.
 A LOW-PRESSURE CUTOFF SHALL BE INSTALLED ON ALL BOOSTER
 PUMPS IN A WATER PRESSURE BOOSTER SYSTEM TO PREVENT
 CREATION OF A VACUUM OR NEGATIVE PRESSURE ON THE
 SUCTION SIDE OF THE PUMP WHEN A POSITIVE PRESSURE OF 10
 PSI (68.94 KPA) OR LESS OCCURS ON THE SUCTION SIDE OF
 THE PUMP.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2013-10-28 Cont ID  
Sent By J WITMER Date 2013-10-28 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2013-10-28 Time 08:02 Sent To  
Notes
2013-10-28 08:07:23ROOFING PRODUCT APPROVAL SUBMITTED:
 NOA: 08-0827.17
 POLYGLASS MODIFIED BITUMEN ROOF SYSTEM OVER LIGHTWEIGHT
 CONCRETE
 SUB-SYSTEM: DECK TYPE 4
 LIGHTWEIGHT CONCRETE NON-INSULATED
 SYSTEM TYPE E(1) BASE SHEET MECHANICALLY FASTENED MAX
 DESIGN PRESSURE -90 PSF GENERAL LIMITATION # 7
 PE LETTER
 TERRENCE E. LUNN

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2013-07-30 Cont ID  
Sent By fmittner Date 2013-07-30 Time 13:41 Rev Time 0.00
Received By fmittner Date 2013-07-30 Time 13:41 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2013-04-18 Cont ID  
Sent By jwitmer Date 2013-04-18 Time 12:15 Rev Time 0.00
Received By jwitmer Date 2013-04-18 Time 12:13 Sent To  
Notes
2013-04-18 12:14:12ROOFING : FAILED
 BUILDING PLAN REVIEW
 PERMIT: 13030782
 ADD: 326 FERN ST
 CONT: STRATICON, LLC
 TEL: (772)210-0200
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: APRIL 17/ 2013
 ACTION: DENIED
  
 1)NO ROOFING PRODUCT APPROVALS WWERE SUBMITTED. ROOFING
 PRODUCT APPROVALS, WILL HAVE VARIOUS SUB-SYSTEMS THAT
 CAN BE INSTALLED UNDER VARYING CONDITIONS AND ASSOCATED
 PRESSURES. PLEASE HIGHLIGHT WHICH OF THESE SUB-SYSTEMS
 WILL BE INSTALLED ON THIS PROJECT, IF MORE THAN ONE
 SUB-SYSTEM WILL BE INSTALLED PLEASE IDENTIFY EACH AND
 THE LOCATION OF THE INSTALATION. NOTE IF THE PRODUCT
 APPROVALS HAS LIMITATIONS ON ENHANCED FASTENING IN
 ZONES 2 & 3. IF ALLOWED PROVIDE RAS 117 CALCULATIONS
 PREPARED BY A DESIGN PROFESSIONAL. 1609.6.4.3.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status P Date 2013-11-19 Cont ID  
Sent By jwitmer Date 2013-11-19 Time 08:58 Rev Time 0.00
Received By jwitmer Date 2013-11-19 Time 08:58 Sent To  
Notes
2013-11-19 09:01:42BUILDING PROVISO:
 11/19/2013
 THRESHOLD DOCUMENTS:
 1) THRESHOLD INSPCECTION REPORT : SUBMITTED
 2) SPECIAL INSPECTOR RESUME: SUBMITTED
 3) CONTRACTOR JOB SUMMARY LETTER: SUBMITTED
  
 4) THRESHOLD AGREEMENT:APPROVED WITH PROVISO THE
 INSPECTION COMPANY HAS NOT COMPLETED THE TOP PORTION OF
 THE FORM PAGE 4 OF 6.
  
 PLEASE CONTACT THE MANAGER OF THE THRESHOLD SPECIAL
 INSPECTOR PROGRAM, KEN CONRAD FOR FORMS AND FURTHER
 INSTRUCTIONS:
 KEN CONRAD- MANAGER OF THRESHOLD INSPECTION PROGRAM.
 TEL: 561-805-6715
 E-MAIL: [email protected]

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2013-10-28 Cont ID  
Sent By jwitmer Date 2013-10-28 Time 08:31 Rev Time 0.00
Received By jwitmer Date 2013-10-28 Time 08:31 Sent To  
Notes
2013-10-28 08:32:0610/28/2013
 THRESHOLD DOCUMENTS:
 1) THRESHOLD INSPCECTION REPORT : SUBMITTED
 2) SPECIAL INSPECTOR RESUME: SUBMITTED
 3) CONTRACTOR JOB SUMMARY LETTER: SUBMITTED
 4) THRESHOLD AGREEMENT: NOT SUBMITTED
  
 PLEASE CONTACT THE MANAGER OF THE THRESHOLD SPECIAL
 INSPECTOR PROGRAM, KEN CONRAD FOR FORMS AND FURTHER
 INSTRUCTIONS:
 KEN CONRAD- MANAGER OF THRESHOLD INSPECTION PROGRAM.
 TEL: 561-805-6715
 E-MAIL: [email protected]

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2013-10-28 Cont ID  
Sent By jwitmer Date 2013-10-28 Time 08:30 Rev Time 0.00
Received By jwitmer Date 2013-10-28 Time 08:30 Sent To  
Notes
2013-10-28 08:31:5210/28/2013
 THRESHOLD DOCUMENTS:
 1) THRESHOLD INSPCECTION REPORT : SUBMITTED
 2) SPECIAL INSPECTOR RESUME: SUBMITTED
 3) CONTRACTOR JOB SUMMARY LETTER: SUBMITTED
 4) THRESHOLD AGREEMENT: NOT SUBMITTED
  
 PLEASE CONTACT THE MANAGER OF THE THRESHOLD SPECIAL
 INSPECTOR PROGRAM, KEN CONRAD FOR FORMS AND FURTHER
 INSTRUCTIONS:
 KEN CONRAD- MANAGER OF THRESHOLD INSPECTION PROGRAM.
 TEL: 561-805-6715
 E-MAIL: [email protected]

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2013-10-28 Cont ID  
Sent By jwitmer Date 2013-10-28 Time 08:08 Rev Time 0.00
Received By jwitmer Date 2013-10-28 Time 08:08 Sent To  
Notes
2013-10-28 08:27:38 
 10/28/2013
 THRESHOLD DOCUMENTS:
 1) THRESHOLD INSPCECTION REPORT : SUBMITTED
 2) SPECIAL INSPECTOR RESUME: SUBMITTED
 3) CONTRACTOR JOB SUMMARY LETTER: SUBMITTED
 4) THRESHOLD AGREEMENT: NOT SUBMITTED
  
 PLEASE CONTACT THE MANAGER OF THE THRESHOLD SPECIAL
 INSPECTOR PROGRAM, KEN CONRAD FOR FORMS AND FURTHER
 INSTRUCTIONS:
 KEN CONRAD- MANAGER OF THRESHOLD INSPECTION PROGRAM.
 TEL: 561-805-6715
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2013-10-24 Cont ID  
Sent By AAPONTE Date 2013-10-24 Time 12:06 Rev Time 0.00
Received By aaponte Date 2013-10-23 Time 14:46 Sent To  
Notes
2013-10-23 16:32:12PROVISO:
 1. PUBLIC OPEN SPACE IS NOT INCLUDED UNDER THIS PERMIT.
 CONSTRUCTION OF OPEN SPACE SHALL START BY APRIL 29,
 2014 IF THE SITE IS NOT UTILIZED FOR STAGGING, OR AT
 THE LATEST SHALL BE COMPLETED BY OCTOBER 29, 2015 (RES.
 NO. 437-08 AND 438-08)
 2. APPROVAL OF EASEMENT FOR CANOPY AND ADA RAMP IS
 REQUIRED BEFORE CO CAN BE ISSUED.
 3. RESTRICTIVE COVENANT OR EASEMENT REGARDING THE WEST
 SIDE WINDOWS OVER OPEN SPACE SHALL BE APPROVED AND
 RECORDED BEFORE PUBLIC OPEN SPACE TRANSFER.
 4. EXISTING COBRA LIGHT IN FRONT OF THE PROPERTY SHALL
 BE CHANGED TO CITY STANDARD DECORATIVE LIGHT.
 PHOTOMETRIC SHALL BE ADJUSTED.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2013-08-01 Cont ID  
Sent By aaponte Date 2013-08-01 Time 12:52 Rev Time 0.00
Received By aaponte Date 2013-08-01 Time 12:51 Sent To  
Notes
2013-08-01 13:21:041.THE BUILDING PERMIT WILL NOT BE APPROVED BY ZONING
 UNTIL THE FORMAL SITE PLAN APPROVAL PROCESS HAS BEEN
 COMPLETED. A FINAL RESUBMITTAL HAS NOT BEEN COMPLETED.
 2. THE PROVIDED BIKE PARKING DOES NOT MEET THE CODE
 REQUIREMENTS. DAC RECOMMENDED BIKE PARKING ON SITE. IT
 SHALL BE LOCATED IN A SECURED AREA AND COVERED FROM THE
 ELEMENTS.
 3. STRUCTURAL SOIL SHALL BE SPECIFIED AROUND THE TREE
 GRATES WITHIN THE SIDEWALK FOR AL LEAST 5 FEET.
 4. IS THERE ANY REASON WHY TREES NUMBER 7,8, AND 9 WERE
 REMOVED AND NOT REPLACED? THAT SOUTHWEST SIDE OF THE
 PROPERTY DOES NOT HAVE TREES ON THE SIDEWALK EITHER.
 5. STAFF WILL DETERMINE AFTER INTERNAL DISCUSSIONS IF
 THE EXISTING LIGHT POLE ON FERN STREET NEEDS TO BE
 REPLACED BY THE CITY DECORATIVE POLE AND FIXTURE.
 6. NEW CANOPY OVER ENTRANCE DOORS IS PROJECTING OVER
 THE ROW. AN AIR RIGHT EASEMENT WILL BE NECESSARY.
 7. A NOTE SHALL BE INCLUDED IN THE DRAWINGS REGARDING
 THE NUMBER OF OFF-SITE PARKING THAT WILL BE PROVIDED
 BASED ON DAC APPROVAL.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
2013-06-24 18:42:036/24/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-04-24 Cont ID  
Sent By aaponte Date 2013-04-24 Time 10:47 Rev Time 0.00
Received By aaponte Date 2013-04-23 Time 15:32 Sent To  
Notes
2013-04-23 16:27:03GENERAL COMMENTS:
 1.PLEASE INDICATE THE LOCATION OF THE BIKE PARKING AND
 TENANT STORAGE RECOMMENDED BY THE DAC APPROVAL.
 2. PLEASE INDICATE THE HEIGHT OF THE EXISTING PARAPET
 WALL AND SCREENING CONDITION OF PROPOSED MECHANICAL
 EQUIPMENT ON ROOF TOP.
 3. PLEASE INDICATE THE GROUND COVER OR TREATMENT
 PROPOSED FOR THE AREA SOUTH OF THE OPEN SPACE BETWEEN
 THE SIDEWALK AND THE DUMPSTER. STAFF SUGGESTS
 INTEGRATING IT AS PART OF THE OPEN SPACE OR AT LEAST
 PERCEIVED AS SUCH.
 4. IS THERE ANY DIRECT CONNECTION BETWEEN THE
 RETAIL/RESTAURANT AND THE PARK? COMMERCIAL SPACE MAY
 BENEFIT FROM OUTDOOR SEATING IN THE PARK (SIDEWALK CAFE
 PERMIT).
 5. THE BUILDING PERMIT WILL NOT BE APPROVED BY ZONING
 UNITL THE FORMAL SITE PLAN APPROVAL PROCESS HAS BEEN
 COMPLETED. A FINAL RESUBMITTAL HAS NOT BEEN COMPLETED.
 6. STREET TREES SHALL BE PLANTED ON TREE GRATES ALONG
 THE FERN STREET FRONTAGE. LIVE OAK IS THE RECOMMENDED
 SPECIE.
 7. PEDESTRIAN STREET LIGHT SHALL BE PROVIDED ALONG THE
 PROJECT FRONTAGE.
 8. A MAINTENANCE AGREEMENT FORT HE STREETSCAPE WILL BE
 REQUIRED BEFORE THE FINAL CO IS ISSUED.
 OPEN SPACE COMMENTS:
 1. THE PROPOSED RETENTION AREAS ARE NOT ACCEPTABLE FOR
 AN OPEN SPACE. THE GRASSED AREA SHALL BE DESIGNED IN A
 WAY IS USABLE BY THE GENERAL PUBLIC. IF STORMWATER IS
 THE REASON, THE TECHNICAL SOLUTION SHALL BE APPROACHED
 AS AN INTEGRAL PART OF THE PARK DESIGN.
 2. ADDITIONAL BENCHES ARE REQUIRED TO COMPLY WITH THE
 MINIMUM AMOUNT OF SEATING REQUIRED FOR A PUBLIC OPEN
 SPACE.
 3. THE PROPOSED PRIVATE BBQ AREA DO NOT SEEM PART OF
 THE PARK, BUT AN ADDITION. IT SHOULD BE DESIGNED AS ONE
 ELEMENT OF THE OVERALL DESIGN.
 4. PARK PHOTOMETRICS WILL BE REQUIRED.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439