Plan Review Details - Permit 13030713
Plan Review Stops For Permit 13030713
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-05-14 Cont ID  
Sent By jgomez Date 2013-05-13 Time 14:17 Rev Time 0.00
Received By jgomez Date 2013-05-13 Time 14:17 Sent To  
Notes
2013-05-13 14:23:01BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE PRODUCT APPROVALS (2 COPIES) FOR: A)
 EXTERIOR DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER. B) FLAT ROOF INFORMATION
 UNDER A SEPARATE PERMIT.
 C)PRECAST LINTELS COMPLETE NOA REPORT.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL OF THE ABOVE PRODUCT APPROVALS.
  
 3- REVISE ENERGY CALCULATIONS TO MATCH PLANS. A) THERE
 IS NOT KITCHEN ON THE NEW ADDITION. B) THERE IS NOT
 FLAT TILE/SLATE ROOF. C) THERE IS NOT CATHEDRAL CEILING
 ON THE NEW ADDITION.
  
 4- REVISE FOUNDATION DETAIL. NEED 4" ABOVE FINISH GRADE
 (SEC. R404.1.6). ALSO, NEED TO BE 12" BELOW GRADE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-29 Cont ID  
Sent By jgomez Date 2013-03-29 Time 17:09 Rev Time 0.00
Received By jgomez Date 2013-03-29 Time 16:19 Sent To  
Notes
2013-03-29 17:12:40RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES). SEC. 103.2
 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION TO INCLUDE
 ALL THE LABOR, MATERIALS, ALL DESIGN PROFESSIONAL FEES
 AND OVERHEAD AND PROFIT. VALUE WAS UPDATED TO $43,843.
 PERMIT FEE BALANCE IS $1216.11.
  
 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 4- CLARIFY WHY PLANS TITLE BLOCK CALL FOR
 GARAGE/APARTMENT ADDITION. THERE IS NOT GARAGE OR
 APARTMENT SHOWN ON PLANS. SEC. 107.2.1 CITY AMENDMENTS
 TO FBC. REVISE AS REQUIRED.
  
 5- ROOM ADJACENT TO THE PROPOSED ADDITION WAS A BEDROOM
 NOT STORAGE. THIS ROOM NEEDS:
 A) EGRESS AS REQUIRED BY SEC. R310 OF 2010
 FBC-RESIDENTIAL.
  
 B) LIGHT, VENTILATION AND HEATING AS REQUIRED BY SEC.
 R303 OF 2010 FBC-RESIDENTIAL.
  
 6-SPECIFY THE NAME OF THE LONG ROOM ADJACENT TO THE
 ROOM CALLED "EXISTING STORAGE/CLOSET". SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 7- SPECIFY HOW PROVIDING HEATING TO THE NEW ADDITION.
 SEC. R303.8 OF 2010 FBC-RESIDENTIAL.
  
 8- SHEET A-1:
 A) REVISE ROOF SHEATHING NAILING SPECIFICATIONS ON EAST
 AND WEST WALL DETAILS. NEED TO SPECIFY MIN. 8D RING
 SHANK NAILS AT 6" O.C ON ROOF ZONES 1 AND 2. AND, MIN.
 8D RING SHANK NAILS AT 4"O.C. IN ROOF ZONE 3. SEC.
 R803.2.3.1 OF 2010 FBC-RESIDENTIAL.
  
 B) EAST WALL DETAIL. SPECIFY ROOF VENTILATION SIZE.
 SEC. R806 OF 2010 FBC-RESIDENTIAL. NOTE: NEED TO
 PROVIDE CROSS VENTILATION.
  
 C) REQUIRED ROOF SLOPE IS 1/4" PER FT. SEC. R905.11.
 NEED TO REVISE THE DIMENSIONS SHOWN ON THE EXTERIOR
 ELEVATIONS TO ALLOW ENOUGH DROP TO ALLOW THE 1/4 PER FT
 RATIO. FOR EXAMPLE A DROP OF 4" FROM 11'-0" TO 10'-8"
 DOESN'T WORK FOR THE 22'-2" DISTANCE SHOWN ON THE ROOF
 PLAN.
  
 D) CLARIFY ON FLOOR PLAN WHERE IS THE ENTRY FOR THIS
 HOUSE. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 9- SHEET S-1:
 A) REVISE ROOF SHEATHING SPECIFICATIONS. SEE ITEM 8(A)
 ABOVE.
  
 B) REVISE TOP OF BEAM DIMENSIONS ON THE EXTERIOR
 ELEVATIONS. SEE ITEM 8(C) ABOVE.
  
 C) REVISE THE WINDOWS/DOOR DESIGN PRESSURES SHOWN ON
 THE EXTERIOR ELEVATIONS TO MATCH DESIGN PRESSURES SHOWN
 ON CHART UNDER THE WIND DESIGN CRITERIA. SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 D) ROOF FRAMING PLAN: (1) REVISE THE ROOF SHEATHING
 SPECS. SEE ITEM 8(A) ABOVE. (2) SPECIFY RAFTERS SIZE
 AND SPACING. SEC. 107.2.1 CITY AMENDMENTS TO FBC. (3)
 REVISE THE ROOF UPLIFT DESIGN PRESSURES FOR ZONE 2 AND
 3. SEE NOTE (A) OF TABLE R301.2.(2) OF 2010
 FBC-RESIDENTIAL. (4) SPECIFY SIZE OF SOLID BLOCKING.
 REMEMBER THAT CROSS VENTILATION IS REQUIRED. IF THE
 BLOCKING SIZE IS THE SAME AS THE ROOF RAFTERS, THEN
 CROSS VENTILATION IS BLOCKED ALSO.
  
 E) FOUNDATION DETAIL: SPECIFY FOOTING DEPTH BELOW
 FINISH GRADE. SEC. R403.1.4.
  
 F) ENGINEER OF RECORD TO PROVIDE ALL THE INFORMATION
 REQUIRED BY SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE
 CODE AND CHAPTER 471 FLORIDA STATUTE. INCLUDE THE
 ENGINEER'S NAME, LICENSE NUMBER, CERTIFICATE OF
 AUTHORIZATION NUMBER.
  
 10- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) EXTERIOR DOOR. PROVIDE THE FLORIDA PRODUCT APPROVAL
 COVER PAGE THAT CORRESPOND TO DRAWINGS SUBMITTED. IF
 THERE IS NONE, THEN MANUFACTURER MAY APPLY FOR LOCAL
 PRODUCT APPROVAL.
  
 B) SINGLE HUNG WINDOWS. ALSO, NEED THE FLORIDA PRODUCT
 APPROVAL COVER PAGE.
  
 C) FLAT ROOF. CLEARLY IDENTIFY APPROVED ASSEMBLY TO BE
 INSTALLED TO VERIFY THE DESIGN PRESSURES OF SEC.
 R301.2.1.4.3. AND, PROVIDE THE SIGNED AND SEALED RAS
 117 CALCULATIONS IF PRODUCT APPROVAL SUBMITTED REQUIRES
 THEM TO BE SIGNED AND SEALED.
  
 D) PRECAST LINTELS AS SPECIFIED ON WALL SECTIONS.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED BY THE
 ENGINEER OF RECORD. PROVIDE ONLY THE COVER PAGE AND
 PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-05-03 Cont ID  
Sent By dharvey Date 2013-05-01 Time 15:30 Rev Time 0.00
Received By dharvey Date 2013-05-03 Time 15:58 Sent To  
Notes
2013-05-03 16:00:50RE EXAMINED PLANS. CONTRACTOR REMOVED SUB PANEL IN
 QUESTION, THEREFORE DRAWINGS ARE APPROVED.
2013-05-01 15:32:25 
  
 1) CHANGE RISER DIAGRAM FOR ELECTRICAL SERVICE TO SHOW
 NEW SUB-PANEL WITH CONDUCTOR SIZING AND CIRCUIT
 BREAKER.
  
 INDICATE DISATANCE FROM EXISTING PANEL TO NEW PANEL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-04-01 Cont ID  
Sent By rlecky Date 2013-04-01 Time 17:02 Rev Time 0.00
Received By rlecky Date 2013-04-01 Time 16:36 Sent To  
Notes
2013-04-01 17:02:4813030713
 216 BEVERLY ROAD
 SFD ADDITION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE AN ELECTRICAL RISER PLAN FOR THE SERVICE. SHOW
 THE LOCATION OF THE ELECTRICAL SERVICE AND EXISTING
 PANEL WITH MAIN DISCONNECT. SHOW THE EXISTING AND NEW
 FEEDERS. SHOW THE PANEL SCHEDULES. INCLUDE A LOAD
 CALCULATION. NEC 215.5
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-05-16 Cont ID  
Sent By jgomez Date 2013-05-16 Time 09:40 Rev Time 0.00
Received By jgomez Date 2013-05-15 Time 17:54 Sent To  
Notes
2013-05-15 17:54:37SENT TO J GOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-14 Cont ID  
Sent By jgomez Date 2013-05-14 Time 13:37 Rev Time 0.00
Received By jgomez Date 2013-04-19 Time 15:52 Sent To  
Notes
2013-04-19 15:53:14SENT TO R3 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-03 Cont ID  
Sent By mdekle Date 2013-04-03 Time   Rev Time 0.00
Received By mdekle Date 2013-03-25 Time 13:13 Sent To  
Notes
2013-03-26 13:16:45EXPEDITED
 R--4

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2013-05-16 Cont ID  
Sent By jgomez Date 2013-05-16 Time 09:39 Rev Time 0.00
Received By jgomez Date 2013-05-16 Time 09:39 Sent To  
Notes
2013-05-16 09:40:37PAID MU-2013-10644. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-05-14 Cont ID  
Sent By jgomez Date 2013-05-14 Time 10:54 Rev Time 0.00
Received By jgomez Date 2013-05-14 Time 10:54 Sent To  
Notes
2013-05-14 10:54:31BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-03-29 Cont ID  
Sent By jgomez Date 2013-03-29 Time 16:20 Rev Time 0.00
Received By jgomez Date 2013-03-29 Time 16:19 Sent To  
Notes
2013-03-29 16:21:09BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2013-05-14 Cont ID  
Sent By jgomez Date 2013-05-14 Time 13:37 Rev Time 0.00
Received By jgomez Date 2013-05-14 Time 10:54 Sent To  
Notes
2013-05-14 13:50:48PER PHONE CONVERSATION WITH MR. MESARIC FROM "Z"
 STUDIO. MECHANICAL CONTRACTOR WILL PROVIDE COMPLETE AND
 CORRECT INFORMATION UNDER SEPARATE MECHANICAL PERMIT.
  
 A) INFORMATION ON EQUIPMENT SIZING CALCULATIONS TO
 MATCH INFORMATION ON A/C PLAN AND THE ENERGY
 CALCULATIONS (SIZE OF UNIT AND SEER). B) WHY ROOF
 GAIN/LOSS IS 0%?. C) THERE IS NOT NATURAL GAS FURNACE
 ON PLANS. D) PAGE 9 OF EQUIPMENT CALCULATIONS TO
 INCLUDE ALL THE EQUIPMENT INFORMATION. E) WHY EQUIPMENT
 CALCULATIONS CALL FOR 4 REGISTERS. THIS IS A MINI-SPLIT
 UNIT. F) WHY EQUIPMENT CALCULATIONS ARE CONSIDERING
 DUCTWORK. THIS IS A DUCTLESS UNIT. G) REVISE TOTAL
 BUILDING SUMMARY LOADS ON PAGE 6 OF EQUIPMENT SIZING
 CALCULATIONS. NEED TO MATCH INFORMATION ON PLANS. THERE
 IS IS NOT CRAWL SPACE, ROOF INSULATION IS R19, ETC.

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-04-01 Cont ID  
Sent By jgomez Date 2013-04-01 Time 14:03 Rev Time 0.00
Received By jgomez Date 2013-04-01 Time 14:02 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2013-05-14 Cont ID  
Sent By jgomez Date 2013-05-14 Time 13:57 Rev Time 0.00
Received By jgomez Date 2013-05-14 Time 13:57 Sent To  
Notes
2013-05-14 14:00:11ROOFING CONTRACTOR TO PROVIDE ALL THE FOLLOWING
 INFORMATION UNDER A SEPARATE PERMIT:
  
 1- FLAT ROOF PRODUCT APPROVAL (2 COPIES). AND, CLEARLY
 IDENTIFY APPROVED ASSEMBLY TO BE INSTALLED TO VERIFY
 THE DESIGN PRESSURES OF SEC. R301.2.1.4.3. AND, PROVIDE
 THE SIGNED AND SEALED RAS 117 CALCULATIONS IF PRODUCT
 APPROVAL SUBMITTED REQUIRES THEM TO BE SIGNED AND
 SEALED.

Review Stop Z ZONING
Rev No 3 Status P Date 2013-05-13 Cont ID  
Sent By ajones Date 2013-05-13 Time 13:51 Rev Time 0.00
Received By ajones Date 2013-05-13 Time 13:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2013-05-06 Cont ID  
Sent By mdekle Date 2013-05-06 Time   Rev Time 0.00
Received By mdekle Date 2013-05-06 Time   Sent To  
Notes
2013-05-06 11:27:14ZONING PLAN REVIEW
 REVIEW STATUS: FAILED
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
 REPEAT COMMENT:
  
 1. IN ACCORDANCE WITH SECTION 94-72(A)(2)(D), THE
 PROPOSED SIDE SETBACK DOES NOT MEET THE MINIMUM
 REQUIREMENTS OF FIFTEEN (15') FEET TOTAL. (9.7' + 5.16'
 = 14.8') = .2' DEFICIENCY.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT THE CITY'S
 ZONING ADMINISTRATOR AT
 561-822-1441/[email protected] OR CONSULT THE CITY'S
 ZONING AND LAND DEVELOPMENT REGULATIONS ONLINE
 @WWW.MUNICODE.COM.
  
  
  
2013-04-22 17:08:024/22/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-04-03 Cont ID  
Sent By mdekle Date 2013-04-03 Time   Rev Time  
Received By mdekle Date 2013-04-03 Time   Sent To  
Notes
2013-04-03 13:35:43ZONING PLAN REVIEW
 REVIEW STATUS: FAILED
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 1. IN ACCORDANCE WITH SECTION 94-72(A)(2)(D), THE
 PROPOSED SIDE SETBACK DOES NOT MEET THE MINIMUM
 REQUIREMENTS OF FIFTEEN (15') FEET TOTAL. (9.7' + 5.16'
 = 14.8') = .2' DEFICIENCY.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AND/OR
 CONSULT THE CITY?S ZONING AND LAND DEVELOPMENT
 REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA, PLANNER
 PLANNING & ZONING DIVISION
 TEL: (561) 822-1442
 EMAIL: [email protected]
  