Plan Review Details - Permit 13030668
Plan Review Stops For Permit 13030668
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-04-12 Cont ID  
Sent By shill Date 2013-04-12 Time 11:25 Rev Time 0.00
Received By shill Date 2013-04-12 Time 11:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-04-10 Cont ID  
Sent By shill Date 2013-04-10 Time 16:57 Rev Time 0.00
Received By shill Date 2013-04-10 Time 16:57 Sent To  
Notes
2013-04-10 16:57:59****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 4. OK
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-22 Cont ID  
Sent By shill Date 2013-03-22 Time 13:33 Rev Time 0.00
Received By shill Date 2013-03-22 Time 13:33 Sent To  
Notes
2013-03-22 13:37:39****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 4. THIS SCOPE OF WORK APPEARS TO BE COVERED UNDER THE
 CATEGORY OF TILE, TERRAZZO, AND MARBLE CONTRACTOR:
  
 TILE, TERRAZZO AND MARBLE CONTRACTOR: THOSE WHO ARE
 QUALIFIED TO PREPARE THE BASE, INCLUDING BUT NOT
 LIMITED TO ; BACKING MATERIAL SET, REPAIR AND REFINISH,
 TILE, TERRAZZO AND MARBLE, AND TO INSTALL LAMINATE OR
 NON-NAILABLE WOOD FLOORING. (REV. 1/1/13)
  
 THIS CAN BE FOUND ON PALM BEACH COUNTY'S WEBSITE:
  
 HTTP://WWW.PBCGOV.COM/PZB/CONTRACTORS/STANDARDS.PDF
  
 AN APPLICATION SUBMITTED BY A CONTRACTOR LICENSED FOR
 THIS SCOPE OF WORK IS REQUIRED PRIOR TO PERMIT
 ISSUANCE.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-04-10 Cont ID  
Sent By shill Date 2013-04-10 Time 16:58 Rev Time 0.00
Received By shill Date 2013-04-09 Time 08:42 Sent To  
Notes
2013-04-09 08:42:44INCOMING SENT TO SAMANTHA HILL DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-22 Cont ID  
Sent By shill Date 2013-03-22 Time 13:33 Rev Time 0.00
Received By shill Date 2013-03-22 Time 13:33 Sent To  
Notes
***NONE***