| 2013-03-27 10:58:55 | BUILDING PLAN REVIEW |
| | PERMIT: 13030626 |
| | ADD: 5200 EAST AVE |
| | CONT: JEFFERY W LEWIS INC |
| | TEL: (561)691-1801 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MARCH 27/2013 |
| | ACTION: DENIED |
| | |
| | 1) THIS PROPERTY IS LOCATED IN AN AH FLOOD ZONE WITH A |
| | BASE ELEVATION OF 17'-0" NGVD WITH AN ADITIONAL 6" TO |
| | THE BASE FLOOD BY CITY ORDINANCE. PLEASE PROVIDE THE |
| | ASSESSED VALUE OF THIS BUILDING(NOT LAND, BUILDING |
| | ONLY) TO SEE IF: |
| | 1A) SUBSTAINTIAL IMPROVEMENT HAS MET THE 50 % OF THE |
| | MARKET VALUE. CITY MUNI CODE 94-611 |
| | 1B) IF SUBSTANIAL IMPROVEMENT HAS BEEN MET A SURVEY |
| | WILL BE NEEDED TO SEE THE FLOOR ELEVATION IN NGVD. CITY |
| | MUNI CODE 94-546 PROVISIONS FOR FLOOD HAZARD REDUCTION. |
| | |
| | 2) SHEETS D1 & A1 BOTH INDICATE TWO NEW EXTERIOR DOORS |
| | BUT THE PLANS DO NOT PROVIDE ANY WIND DESIGN CRITERIA: |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 2.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 2.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 2.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | |
| | 5) SHEET D1 INDICATES THE ELIMINATION OF A WINDOW AND A |
| | NEW DOOR OPENING IN THE SAME OPENING, IS THE ROUGH |
| | OPENING THE SAME WIDTH? OR DOES THE OPENING NEED TO BE |
| | CUT LARGER AND VERTICAL REINFORCEMENT REQUIRED? WILL |
| | THERE BE DOOR BUCKS, IF SO HOW WILL THEY BE FASTENED TO |
| | THE SUBSTRATE? 107.2.1.3 ADDITIONAL INFORMATION |
| | REQUIRED. 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. |
| | |
| | 6) SHEET A1 INDICATES TWO NEW EXTERIOR DOORS, DOOR # |
| | 138 THE LIFE SAFETY PLAN SHOW THIS TO BE PART OF THE |
| | EXIT ACCESS ROUTE, WHERE AS DOOR # 142 IS INDICATED TO |
| | HAVE PANIC HARDWARE AND NOT PART OF THE EXIT ACCESS, IS |
| | THERE A DISCREPANCY IN THE HARDWARE SCHEDULE? |
| | 1008.1.10. |
| | |
| | 7) SHEET A-1 INDICATES TWO DOORS IN SERIES BOTH LABELED |
| | # 137 PLEASE REVIEW THE 2010 FL ACCESSIBILTY CODE |
| | SECTION 404.2.6 & FIGURE 404.2.6. |
| | |
| | 8) NEITHER THE LS PLAN NOR SHEET A-1 INDICATE THIS |
| | BUILDING IS FIRE SPRINKLERD, SINCE THERE ARE NEW WALLS, |
| | ROOMS AAND CORRIDORS BEING DEVELOPED PLEASE REVIEW THE |
| | 2010 FBC-B TABLE 1018.1 FOR BUSINESS OCCUPANCIES WITH |
| | AN OCCUPANT LOAD OF GREATER THAN 30 OCCUPANTS THE |
| | CORRIDOR TO BE FIRE RATED. |
| | |
| | 9) 2010 FBC-B 713.6 |
| | FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE |
| | BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL |
| | REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE |
| | AND SMOKE BARRIER ? PROTECT ALL OPENINGS.? |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |