Plan Review Details - Permit 13030626
Plan Review Stops For Permit 13030626
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-05-16 Cont ID  
Sent By jwitmer Date 2013-05-16 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2013-05-16 Time 06:57 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-27 Cont ID  
Sent By jwitmer Date 2013-03-27 Time 12:06 Rev Time 0.00
Received By jwitmer Date 2013-03-26 Time 08:29 Sent To  
Notes
2013-03-27 10:58:55BUILDING PLAN REVIEW
 PERMIT: 13030626
 ADD: 5200 EAST AVE
 CONT: JEFFERY W LEWIS INC
 TEL: (561)691-1801
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MARCH 27/2013
 ACTION: DENIED
  
 1) THIS PROPERTY IS LOCATED IN AN AH FLOOD ZONE WITH A
 BASE ELEVATION OF 17'-0" NGVD WITH AN ADITIONAL 6" TO
 THE BASE FLOOD BY CITY ORDINANCE. PLEASE PROVIDE THE
 ASSESSED VALUE OF THIS BUILDING(NOT LAND, BUILDING
 ONLY) TO SEE IF:
 1A) SUBSTAINTIAL IMPROVEMENT HAS MET THE 50 % OF THE
 MARKET VALUE. CITY MUNI CODE 94-611
 1B) IF SUBSTANIAL IMPROVEMENT HAS BEEN MET A SURVEY
 WILL BE NEEDED TO SEE THE FLOOR ELEVATION IN NGVD. CITY
 MUNI CODE 94-546 PROVISIONS FOR FLOOD HAZARD REDUCTION.
  
 2) SHEETS D1 & A1 BOTH INDICATE TWO NEW EXTERIOR DOORS
 BUT THE PLANS DO NOT PROVIDE ANY WIND DESIGN CRITERIA:
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 2.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 2.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 5) SHEET D1 INDICATES THE ELIMINATION OF A WINDOW AND A
 NEW DOOR OPENING IN THE SAME OPENING, IS THE ROUGH
 OPENING THE SAME WIDTH? OR DOES THE OPENING NEED TO BE
 CUT LARGER AND VERTICAL REINFORCEMENT REQUIRED? WILL
 THERE BE DOOR BUCKS, IF SO HOW WILL THEY BE FASTENED TO
 THE SUBSTRATE? 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED. 1609.6.4.4.1
 COMPONENTS & CLADDING.
  
 6) SHEET A1 INDICATES TWO NEW EXTERIOR DOORS, DOOR #
 138 THE LIFE SAFETY PLAN SHOW THIS TO BE PART OF THE
 EXIT ACCESS ROUTE, WHERE AS DOOR # 142 IS INDICATED TO
 HAVE PANIC HARDWARE AND NOT PART OF THE EXIT ACCESS, IS
 THERE A DISCREPANCY IN THE HARDWARE SCHEDULE?
 1008.1.10.
  
 7) SHEET A-1 INDICATES TWO DOORS IN SERIES BOTH LABELED
 # 137 PLEASE REVIEW THE 2010 FL ACCESSIBILTY CODE
 SECTION 404.2.6 & FIGURE 404.2.6.
  
 8) NEITHER THE LS PLAN NOR SHEET A-1 INDICATE THIS
 BUILDING IS FIRE SPRINKLERD, SINCE THERE ARE NEW WALLS,
 ROOMS AAND CORRIDORS BEING DEVELOPED PLEASE REVIEW THE
 2010 FBC-B TABLE 1018.1 FOR BUSINESS OCCUPANCIES WITH
 AN OCCUPANT LOAD OF GREATER THAN 30 OCCUPANTS THE
 CORRIDOR TO BE FIRE RATED.
  
 9) 2010 FBC-B 713.6
 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-03-22 Cont ID  
Sent By rlecky Date 2013-03-22 Time 16:12 Rev Time 0.00
Received By rlecky Date 2013-03-22 Time 16:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-05-16 Cont ID  
Sent By wjolin Date 2013-05-16 Time 10:44 Rev Time 0.00
Received By wjolin Date 2013-05-16 Time 10:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-04-01 Cont ID  
Sent By wjolin Date 2013-04-01 Time 10:10 Rev Time 0.00
Received By wjolin Date 2013-04-01 Time 09:16 Sent To  
Notes
2013-04-01 10:10:455200 EAST AVENUE
 PERMIT #13030626
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK
 INFORMATION.
  
 SHEET LS-1:
 (1) THE LIFE SAFETY SUMMARY INDICATES A BUSINESS
 OCCUPANCY;HOWEVER, THE DESIGN SHOWS A NON-SEPARATED
 MIXED USE OCCUPANCY CONSISTING OF ASSEMBLY AND BUSINESS
 OCCUPANCIES. ROOMS #119 AND #132 HAVE A COMBINED
 ASSEMBLY OCCUPANT LOAD OF 75 PERSONS. THE SIZE OF THESE
 TWO ROOMS TOGETHER (1,131 SQ.FT.) OCCUPY MORE THAN 10%
 OF THE TOTAL BUILDING AREA TO BE CONSIDERED ACCESSORY
 OR INCIDENTAL TO THE BUSINESS OCCUPANCY.
  
 (2) ROOM #134 IS INDICATED AS DINING ROOM; THEREFORE
 THE OCCUPANT LOAD SHOULD BE DETERMINED USING AN
 OCCUPANT LOAD FACTOR OF 15 SQ.FT. PER PERSON IN LIEU OF
 100 SQ.FT. PER PERSON.
  
 (3) ROOM #135 INDICATES A KITCHEN. INDICATE THE COOKING
 APPLIANCES TO BE USED IN THIS LOCATION.
  
 (4) DOOR IN ROOM #102 IS INDICATED AS AN EXIT DOOR BUT
 NO EXIT SIGN HAS BEEN PROVIDED.
  
 (5) VESTIBULE #137 IS MISSING AN EXIT SIGN LEADING
 OCCUPANTS THROUGH ROOM #138.
  
 (6) CORRIDORS USED AS EXIT ACCESS AND SERVING AN AREA
 HAVING AN OCCUPANT LOAD EXCEEDING 30 SHALL BE SEPARATED
 FROM OTHER PARTS OF THE BUILDING BY WALLS HAVING NOT
 LESS THAN A 1-HOUR FIRE RESISTANCE RATING.
  
 SHEET LS-1 & SHEET E1.1: NO FIRE ALARM NOTIFICATION
 APPLIANCES SHOWN IN ROOM #119 OR #134.
  
 SHEET A-1: DOOR SCHEDULE INDICATES DOOR #142 TO BE
 EQUIPPED WITH PANIC HARDWARE. INDICATE IF OTHER
 NEW/EXISTING DOORS ARE EQUIPPED WITH PANIC HARDWARE.
  
 SHEET E1.1: NO EMERGENCY LIGHTING PROVIDED IN ROOM
 #119, #132, #137 OR #138.
  
 NOTE: SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-16 Cont ID  
Sent By jwitmer Date 2013-05-16 Time 14:11 Rev Time 0.00
Received By jwitmer Date 2013-05-07 Time 09:22 Sent To  
Notes
2013-05-07 09:23:08SENT TO B5 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-01 Cont ID  
Sent By wjolin Date 2013-04-01 Time 10:12 Rev Time 0.00
Received By wjolin Date 2013-03-21 Time 15:48 Sent To  
Notes
2013-03-21 15:48:49B--5


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved