Plan Review Details - Permit 13030620
Plan Review Stops For Permit 13030620
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-06-08 Cont ID  
Sent By lmartine Date 2013-06-08 Time 12:19 Rev Time 0.00
Received By lmartine Date 2013-06-08 Time 12:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-06-03 Cont ID  
Sent By shill Date 2013-06-03 Time 13:51 Rev Time 0.00
Received By shill Date 2013-06-03 Time 13:51 Sent To  
Notes
2013-06-03 14:05:53****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 PLEASE NOTE THAT COMMENTS SHOULD BE ADDRESSED BY
 REVISING THE PLAN TO SHOW CODE COMPLIANCE. A
 TRANSMITTAL LETTER IS HELPFUL FOR PLAN REVIEW. SOME OF
 THE COMMENTS WERE ADDRESSED WITH A PARAGRAPH ON THE
 RESUBMITTAL FORM. SEE FBC 107, PLANS TO CLEARLY SHOW
 SCOPE OF WORK AND CODE COMLIANCE.
  
 COMMENTS FROM PREVIOUS LISTS:
  
 1. IT APPEARS THAT ONE UNIT IS TO BE SPLIT INTO TWO
 UNITS. REVISE THE PLAN TO SHOW EXITING FOR UNIT 103. AS
 DRAWN, THEY NOW NEED TO EXIT THROUGH UNIT 104.
  
 2ND REVIEW, NOT ADDRESSED.
 3RD REVIEW, NOT ADDRESSED. THE RESUB SHEET STATES THAT
 104 IS NOT BEING SPLIT. IT IS NOT CLEAR HOW EXITING FOR
 103 IS AFFECTED AS THE ONLY EXIT SHOWN FOR WHAT IS
 CURRENTLY IN UNIT 103 BUT PROPOSED TO BECOME A PART OF
 104.
  
 PLEASE PROVIDE AN "EXISTING" FLOOR PLAN. NEW
 CONSTRUCTION NOT CLEAR.
  
 2. LOCATION OF RATED WALLS NOT CLEAR. SHOW EXISTING
 RATED WALLS, PROPOSED NEW, AND PROVIDE A DETAIL (TESTED
 ASSEMBLY) FOR NEW RATED WALLS AND INFILL FBC 703,
 709.1. SHOW EXISTING DUCTWORK AND PROPOSED DAMPERS
 REQUIRED BY FBC 713.
  
 2ND REVIEW, NOT ADDRESSED.
 3RD REVIEW, IT APPEARS THAT A PORTION OF UNIT 103 WILL
 BECOME A PART OF UNIT 104. RESUB SHEET STATES THAT THIS
 WALL IS "CLEARLY SHOWN" AND "NON FIRE RATED." SEE FBC
 709.19(6) AND EXCEPTIONS. IT APPEARS THAT A FIRE RATED
 PARTITION IS REQUIRED.
  
 3. OK
  
 4. PROVIDE OCCUPANT LOAD FOR PROPOSED NEW SPACE, FBC
 1004.
  
 2ND REVIEW, NOT ADDRESSED.
 3RD REVIEW, RESUB SHEET STATES THAT THIS WILL HAVE NOT
 MORE THAN 5 PEOPLE FOR 2382 SF. SEE FBC 1004, OCCUPANT
 LOAD NOT TO BE LESS THAN FBC TABLE 1004. REVISE PLAN TO
 INCLUDE OCCUPANT LOAD.
  
 5. OK
  
 6. NEW ROOMS SHOWN; REVISE PLAN TO INCLUDE ROOM
 DESIGNATIONS.
  
 3RD REVIEW, NOT ADDRESSED. RESUB SHEET STATES THAT THIS
 IS OFFICE AND CLERICAL USE ONLY. REVISE PLAN TO INCLUDE
 ROOM DESIGNATIONS SO OCCUPANT LOAD CAN BE
 DETERMINED/CONFIRMED.
  
 NEW COMMENT:
  
 7. RESUB SHEET STATES THAT THIS IS A LEVEL 2
 ALTERATION. REVISE PLAN TO INCLUDE THIS INFORMATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-04-30 Cont ID  
Sent By shill Date 2013-04-30 Time 09:59 Rev Time 0.00
Received By shill Date 2013-04-30 Time 09:59 Sent To  
Notes
2013-04-30 10:36:18****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. IT APPEARS THAT ONE UNIT IS TO BE SPLIT INTO TWO
 UNITS. REVISE THE PLAN TO SHOW EXITING FOR UNIT 103. AS
 DRAWN, THEY NOW NEED TO EXIT THROUGH UNIT 104.
  
 2ND REVIEW, NOT ADDRESSED.
  
 2. LOCATION OF RATED WALLS NOT CLEAR. SHOW EXISTING
 RATED WALLS, PROPOSED NEW, AND PROVIDE A DETAIL (TESTED
 ASSEMBLY) FOR NEW RATED WALLS AND INFILL FBC 703,
 709.1. SHOW EXISTING DUCTWORK AND PROPOSED DAMPERS
 REQUIRED BY FBC 713.
  
 2ND REVIEW, NOT ADDRESSED.
  
 3. OK
  
 4. PROVIDE OCCUPANT LOAD FOR PROPOSED NEW SPACE, FBC
 1004.
  
 2ND REVIEW, NOT ADDRESSED.
  
 5. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1.
  
 2ND REVIEW, NOT ADDRESSED.
  
 NEW COMMENT:
  
 6. NEW ROOMS SHOWN; REVISE PLAN TO INCLUDE ROOM
 DESIGNATIONS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-04-02 Cont ID  
Sent By shill Date 2013-04-02 Time 09:40 Rev Time 0.00
Received By shill Date 2013-04-02 Time 09:40 Sent To  
Notes
2013-04-02 14:47:55****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. IT APPEARS THAT ONE UNIT IS TO BE SPLIT INTO TWO
 UNITS. REVISE THE PLAN TO SHOW EXITING FOR UNIT 103. AS
 DRAWN, THEY NOW NEED TO EXIT THROUGH UNIT 104.
  
 2. LOCATION OF RATED WALLS NOT CLEAR. SHOW EXISTING
 RATED WALLS, PROPOSED NEW, AND PROVIDE A DETAIL (TESTED
 ASSEMBLY) FOR NEW RATED WALLS AND INFILL FBC 703,
 709.1. SHOW EXISTING DUCTWORK AND PROPOSED DAMPERS
 REQUIRED BY FBC 713.
  
 3. TRAVEL DISTANCE IS SHOWN TO THE OFFICE ENTRY RATHER
 THAN TO THE OUTSIDE. EITHER REVISE TRAVEL DISTANCE TO
 INCLUDE TRAVEL TO THE EXIT DISCHARGE OR PROVIDE
 INFORMATION AS TO HOW IT HAS BEEN DETERMINED THAT THE
 LOBBY AND SPACES BEYOND ARE A RATED EXIT, FBC 1016.1.
  
 4. PROVIDE OCCUPANT LOAD FOR PROPOSED NEW SPACE, FBC
 1004.
  
 5. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2013-05-28 Cont ID  
Sent By wjolin Date 2013-05-28 Time 10:12 Rev Time 0.00
Received By wjolin Date 2013-05-28 Time 10:07 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2013-04-26 Cont ID  
Sent By ddaniels Date 2013-04-26 Time 09:18 Rev Time 0.00
Received By ddaniels Date 2013-04-26 Time 09:17 Sent To  
Notes
2013-04-26 09:25:1104/26/2013 PLAN REVIEWED BY FIRE ***DENIED****
  
 1. PROVIED 1-HOUR WALL SEPERATION AND EXITS FOR SUITE
 #104 AND THE EXISTING SUITE #103.
  
 DERRICK DANIELS BATTALION CHIEF / FIRE MARSHAL
 BUREAU OF FIRE PREVENTION
 561 804-4709 OFFICE
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-04-11 Cont ID  
Sent By wjolin Date 2013-04-11 Time 13:00 Rev Time 0.00
Received By wjolin Date 2013-04-11 Time 12:55 Sent To B
Notes
2013-04-11 13:00:122715 NORTH AUSTRALIAN AVENUE - SUITE #104
 PERMIT #13030620
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE 1-HOUR FIRE RATED TENANT SEPARATION WALL NEEDS TO
 BE PROVIDED FOR THE ENTIRE WALL SEPARATING SUITE #104
 FROM SUITE #103. THE FIRE-RATED PARTITION INDICATED ON
 THE PLANS SHOWS TWO ROOMS FROM SUITE #103 (SW CORNER)
 HAVING DOORS THAT OPEN INTO SUITE #104.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-03-27 Cont ID  
Sent By rferguso Date 2013-03-27 Time 13:03 Rev Time 0.00
Received By rferguso Date 2013-03-27 Time 13:03 Sent To B
Notes
2013-03-27 13:47:43PERMIT 13030620
 2715 NORTH ASTRALIAN AVE. #104
  
 PLAN REVIEW COMMENTS FOR WEST PALM BEACH FIRE RESCUE
  
 * PLEASE INDICATE ALL SUITES AND THERE CORRECT NUMBERS,
 I NOTICE TWO SUITES IDENTIFIED AS #103.
  
 * PLEASE SUBMIT A FURNITURE PLAN INDICATING WHERE
 FURNITURE WILL BE LOCATED WHEN MEASURING PATHS OF
 TRAVEL.
  
 * MEASUREMENTS FOR THE PATH OF TRAVEL SHALL TERMINATE
 AT THE EXIT DISCHARGE.
  
 * THE INTIRE FIRE WALL SEPERATION MUST BE INDICATED
 COMPLETELY ON THE DRAUWINGS FOR SPACES #103 AND #104.
  
 * ALL FIRE RATED DOORS MUST BE INDICATED ON PLANS.
  
 * PLEASE INDICATE EXITS AND FIRE WALLS COMPLETELY IN
 SPACE #103, YOU MUST INDICATE WHERE AND HOW THE
 OCCUPANTS WILL EXIT FROM THE SPACE.
  
 * INDICATE THE USE OF ALL SPACE ON PLANS.
  
  
  
 CAPTAIN RONALD E. FERGUSON, ASSISTANT FIRE MARSHAL
 BUREAU OF FIRE PREVENTION
 WEST PALM BEACH FIRE RESCUE
 PHONE #(561) 804-4700
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-06-03 Cont ID  
Sent By shill Date 2013-06-03 Time 14:05 Rev Time 0.00
Received By shill Date 2013-05-23 Time 14:27 Sent To  
Notes
2013-05-24 14:28:36IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-04-30 Cont ID  
Sent By shill Date 2013-04-30 Time 10:37 Rev Time 0.00
Received By shill Date 2013-04-25 Time 08:59 Sent To  
Notes
2013-04-26 09:00:18ANOTHER SUBMITTAL WAS SUBMITTED BY CONTRACTOR TO SHOW
 ONLY ONE TENANT. SUBMITTAL SENT TO SAMANTHA'S DESK FOR
 REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-24 Cont ID  
Sent By lmartine Date 2013-04-25 Time 14:27 Rev Time 0.00
Received By lmartine Date 2013-04-04 Time 13:11 Sent To  
Notes
2013-04-04 13:11:38IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-02 Cont ID  
Sent By shill Date 2013-04-02 Time 14:48 Rev Time 0.00
Received By shill Date 2013-03-21 Time 10:37 Sent To  
Notes
2013-03-29 14:57:253/29 TO MISC 2
  
2013-03-22 19:43:50TO FIRE
  
2013-03-22 10:37:33MISC. #2