Plan Review Details - Permit 13030563
Plan Review Stops For Permit 13030563
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-03-21 Cont ID  
Sent By wjolin Date 2013-03-21 Time 09:52 Rev Time 0.00
Received By wjolin Date 2013-03-21 Time 09:44 Sent To M
Notes
2013-03-21 09:56:35428 10TH STREET
 REVISION #13030563
 PERMIT #13020274
 MASTER #12060308
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 PROVIDE A LOCAL WATERFLOW ALARM TO ALERT BUILDING
 OCCUPANTS.
  
 SPRINKLER DESIGN SHALL CONFORM TO THE 2007 EDITION OF
 NFPA 13R IN LIEU OF THE 2002 EDITION INDICATED ON THE
 PLANS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-25 Cont ID  
Sent By hmoser Date 2013-03-25 Time 11:30 Rev Time 0.00
Received By hmoser Date 2013-03-20 Time 11:56 Sent To  
Notes
2013-03-20 11:56:16TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-03-25 Cont ID  
Sent By hmoser Date 2013-03-25 Time 11:30 Rev Time 0.00
Received By hmoser Date 2013-03-25 Time 11:07 Sent To  
Notes
***NONE***