Plan Review Details - Permit 13030497
Plan Review Stops For Permit 13030497
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-05-14 Cont ID  
Sent By jwitmer Date 2013-05-10 Time 14:16 Rev Time 0.00
Received By jwitmer Date 2013-05-10 Time 07:02 Sent To  
Notes
2013-05-10 13:28:20BUILDING PLAN REVIEW
 PERMIT: 13030497
 ADD: 2707 OKEECHOBEE BLVD
 CONT: RIVER CITY CONTRACTORS
 TEL: (904)422-5988
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MAY 10/2013
 ACTION: PROVISO
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1A) PROVISO: I SPOKE WITH THE ARCHITECT, 5/10/13 ABOUT
 RED LINING THE DRAWINGS FOR:
 REDLINED, SHEET A2.0 RED MISSING WALL TAG W-1 BETWEEN
 SHOWROOM & PARTS, 2HR OCCUPANCY SEPERATION.
 1B) PROVISO: RED LINED P-4 TO BE A 1 HOUR RATED 5/8
 TYPE X DRYWALL ENCLOSURE.
  
 2) PROVISO: REDLINES, A4.1 DOOR SCHEDULE DOOR:
 DOOR # 14 - 1 HOUR
 DOOR # 20- 1 HOUR
 DOOR # 2- 1 HOUR.
  
 3) PROVISO: SHEET A6.0 REDLINED WATER FOUNTAIN DETAIL
 HI-LO DRINKING FOUNTAIN, SKIRT REQUIRED UNDER THE HIGH
 DRINKING FOUNTAIN PER 2010 FL ACCESSIBILITY CODE 307.2
 PROTRUDING OBJECTS.
  
 3) COMPLIED 7/09/2013. JW PROVISO: BEFORE ISSUANCE (2)
 SIGNED & SEALED SOILS REPORT, REPORT SUBMITTED NOT
 SEALED.
  
 4) PROVISO: 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) PROVISO: THE DESIGN PRESSURES ARE CORRECT, THE
 CONTRACTOR ELECTS TO SUBMIT THE PRODUCT APPROVALS AFTER
 PERMIT ISSUANCE TO BE REVIEWED UNDER A REVISION WITH
 ASSOCIATED FEES AND SEPERATE REVIEW.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-29 Cont ID  
Sent By jwitmer Date 2013-03-29 Time 13:30 Rev Time 0.00
Received By jwitmer Date 2013-03-29 Time 08:19 Sent To  
Notes
2013-03-29 13:36:55BUILDING PLAN REVIEW
 PERMIT: 13030497
 ADD: 2707 OKEECHOBEE BLVD
 CONT: RIVER CITY CONTRACTORS
 TEL: (904)422-5988
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MARCH 29/2013
 ACTION: DENIED
  
 1) COVERSHEET INDICATES IN THE INDEX THERE IS TO BE A
 A2.0 SHEET, THIS SHEET IS MISSING, THE PLANS DO CONTAIN
 TWO IDENTICAL A2.1 SHEETS. PLEASE MAKE THE CORRECTION.
  
 2) WITH THERE NOT HAVING ANY A2.0 SHEET WHICH IS THE
 FIRST FLOOR FLOOR PLAN WE CAN ONLY REVIEW THE LIFE
 SAFETY PLAN OF THE FIRST FLOOR. MISSING INFORMATION:
  
 2A) THE PLANS DO NOT PROVIDE OCCUPANCY SEPREATION
 WALLS, SHEET A8.0 PROVIDES DETAILS FOR THE RATED WALLS
 BUT THEY ARE NOT SHOWN ON THE LS SHEET. TABLE 508.4.
  
 2B) THIS PLAN DOES NOT IDENTIFY THE FIRST FLOOR DOORS
 PLEASE PROVIDE DOOR IDENTIFICATION TO TIE TO THE DOOR
 SCHEDULE FOUND ON SHEET A4.1.OCCUPANCY SEPERATION RATED
 WALLS WILL REQUIRE
 FIRE RATED DOORS SEE TABLE 715.4.
  
 2C) THE NEWLY FORMED EXTERIOR STAIR # 2 HAS A DOOR
 DIRECTLY BELOW IT, THE DOOR ON THE FIRST FLOOR WILL
 NEED TO BE FIRE RATED AS PER SECTION 1026.6.
  
 2D) THE LS PLAN HAS THE WORDING STAIR # 3 BUT IT DOES
 NOT SHOW UP ANYWHERE ELSE, IS THIS A DELETED STAIRWAY.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 2E) THE LS PLAN ALSO INDICATES A NEW PLATFORM LIFT,
 PLEASE PROVIDE THE MANUFATURES CUT SHEETS AND OR SPECS
 SHOWING COMPLIANCE WITH 2010 ACCESSIBILITY CODE
 410.1-410.6 AND IN COMPLIANCE WITH ASME A 18.1.
  
 2F) THE FIRST FLOOR PARTS STORAGE INDICATES TWO LARGE
 HOLES THROUGH THE FLOOR INTO THE 2ND FLOOR STORAGE
 AREA, HOW ARE THE HOLES BEING PROTECTED FROM FLOOR TO
 FLOOR? 708.2 SHAFT ENCLOSURES REQUIRED, IT APPEARS THAT
 THE DESIGNER OF RECORD MAY BE LOOKING FOR EXCEPTION
 NUMBER 7 , MISSING THE INFORMATION IN REGARDS TO 7.7
 WITHIN THE SAME SMOKE COMPARTMENT.
  
 2G) STAIR # 1 THAT LEADS INTO THE BUILDING A 18 INCH
 DIFFERENCE IN GRADE IS INDICATED AS A 1/2 INCH
 DIFFERENCE IN GRADE. PLEASE CORRECT THE DISCREPANCY.
  
 3) SHEET A2.1 INDICATE THAT BOTH STAIRS WILL HAVE AN
 AREA OF REFUGE, THE STAIRS ARE TO NARROW FOR AN AREA OF
 REFUGE, PLEASE SEE NFPA 101 SECTION 7.2.12.2 AND
 7.2.12.3 FOR THE REQUIRED CLEAR WIDTH BETWEEN
 HANDRAILS.
  
 4) THE ARCHTITECTURAL & STRUCTURAL SHEETS INDICATE 2
 NEW ADDITIONS, PLEASE PROVIDE A SOILS REPORT FOR THE
 SAFE MINIMUM BEARING VALUE FOR THE NEW ADDITIONS.
 1803.2 INVESTIGATIONS REQUIRED.1803.6 REPORTING.
 WHERE GEOTECHNICAL INVESTIGATIONS ARE REQUIRED, A
 WRITTEN REPORT OF THE INVESTIGATIONS SHALL BE SUBMITTED
 TO THE BUILDING OFFICIAL BY THE OWNER OR AUTHORIZED
 AGENT AT THE TIME OF PERMIT APPLICATION. THIS
 GEOTECHNICAL REPORT SHALL INCLUDE, BUT NEED NOT BE
 LIMITED TO, THE FOLLOWING INFORMATION:
  
 1. A PLOT SHOWING THE LOCATION OF THE SOIL
 INVESTIGATIONS.
  
 2. A COMPLETE RECORD OF THE SOIL BORING AND PENETRATION
 TEST LOGS AND SOIL SAMPLES.
  
 3. A RECORD OF THE SOIL PROFILE.
  
 4. ELEVATION OF THE WATER TABLE, IF ENCOUNTERED.
  
 5. RECOMMENDATIONS FOR FOUNDATION TYPE AND DESIGN
 CRITERIA, INCLUDING BUT NOT LIMITED TO: BEARING
 CAPACITY OF NATURAL OR COMPACTED SOIL; PROVISIONS TO
 MITIGATE THE EFFECTS OF EXPANSIVE SOILS; MITIGATION OF
 THE EFFECTS OF LIQUEFACTION, DIFFERENTIAL SETTLEMENT
 AND VARYING SOIL STRENGTH; AND THE EFFECTS OF ADJACENT
 LOADS.
  
 6. EXPECTED TOTAL AND DIFFERENTIAL SETTLEMENT.
  
 7. DEEP FOUNDATION INFORMATION IN ACCORDANCE WITH
 SECTION 1803.5.5.
  
 8. SPECIAL DESIGN AND CONSTRUCTION PROVISIONS FOR
 FOUNDATIONS OF STRUCTURES FOUNDED ON EXPANSIVE SOILS,
 AS NECESSARY.
  
 9. COMPACTED FILL MATERIAL PROPERTIES AND TESTING IN
 ACCORDANCE WITH SECTION 1803.5.8.
  
 10. CONTROLLED LOW-STRENGTH MATERIAL PROPERTIES AND
 TESTING IN ACCORDANCE WITH SECTION 1803.5.9.
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 7)SHEET A-9 THE NEW ADDITION STAIR ENCLOSURE SHOWS A
 ROOF ELEVATION OF 21'-6" THE CUT SECTION B / A8.0
 INDICATES A ROOF HEIGHT OF 13'-0" IS THIS A WRONG
 SECTION?
  
 8) THE ROOF HEIGHT OF 21'-6" THE NEGATIVE PRESSURES FOR
 THE BUILDING SHOUD BE TAKEN AT THAT HEIGHT AND
 PRESSURES FOR THE END ZONES FOR THE SHOW ROOM APPEAR
 ALITTLE LOW FOR THE NEGATIVE PRESSURES.
  
 9) SHEET A9.0 THE ROOF PLAN DOES NOT PROVIDE TTHE ROOF
 PRESSURES FOR ROOF ZONES 1,2 & 3, PLEASE PROVIDE
 PRESURES FOR THESE ZONES. 1609.6.4.1/ COMPONENTS &
 CLADDING. THE ROOFING SPEC FOUND ON THAT PAGE INDICATES
 A MIAMI-DADE NOA 10-0408.05 A 60 PAGE REPORT. PLEASE
 PROVIDE THE FIRST 7 SHEETS FROM THE PRODUCT APPROVAL,
 THE SHEETS THAT ARE APPLICABLE TO THE SUB-SYSTEM TO BE
 INSTALLED, NOTE THE MAXIMUM PRESSURE, WHICH LIMITATION
 EITHER 7 OR 9 AND LAST PAGE OF THE REPORT. IF ENHANCED
 FASTENING IS REQUIRED FOLLOW THE INSTRUCTIONS UNDER
 LIMITATION NUMBER 7.
  
 10) SHEET A-6.0 THE HANDICAPPED RESTROOMS HAVE
 DIMENSIONAL PROBLEMS IN THE LENGTH, THE MINIMUM
 DIMENSION FOR FIXTURES THAT SET ON THE SAME WALL
 WITHOUT AN OFFSEET IS 7'-0 1/2".
 PLEASE REVIEW 2010 ACCESSIBILITY CODE 604.3.2 THE WATER
 CLOSET REQUIRING A 60" CLEAR SPACE AND FIGURE
 604.8.1.6.
  
 11) SHEET A-6.0 NEXT TO THE HANDICAPPED ENCLOSURE THERE
 ARE WHAT APPEARS TO BE AMBULATORY STALLS WITH A WIDTH
 OF 3'-6" PLEASE REVIEW FIGURE 604.8.2 35-37 INCHES.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-03-27 Cont ID  
Sent By rlecky Date 2013-03-27 Time 13:28 Rev Time 0.00
Received By rlecky Date 2013-03-26 Time 16:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-05-11 Cont ID  
Sent By wjolin Date 2013-05-11 Time 19:13 Rev Time 0.00
Received By wjolin Date 2013-05-11 Time 17:57 Sent To  
Notes
2013-05-11 19:07:362707 OKEECHOBEE BOULEVARD
 PERMIT #13030497
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A2.1: THE AREA OF REFUGE SHALL COMPLY WITH ALL
 REQUIREMENTS OF 7.2.12.2 AND 7.2.12.3 OF NFPA 101 (2009
 EDITION WITH FLORIDA AMENDMENTS).
  
 PER NFPA 101
 7.2.12.2.5 THE AREA OF REFUGE SHALL BE PROVIDED WITH A
 TWO-WAY COMMUNICATION SYSTEM FOR COMMUNICATION BETWEEN
 THE AREA OF REFUGE AND A CENTRAL CONTROL POINT. THE
 DOOR OPENING TO THE STAIR ENCLOSURE AND THE ASSOCIATED
 PORTION OF THE AREA OF REFUGE THAT THE STAIR ENCLOSURE
 DOOR OPENING SERVES SHALL BE IDENTIFIED BY SIGNAGE.
 7.2.12.2.6 INSTRUCTIONS FOR SUMMONING ASSISTANCE, VIA
 THE TWO-WAY COMMUNICATION SYSTEM, AND WRITTEN
 IDENTIFICATION OF THE AREA OF REFUGE LOCATION SHALL BE
 POSTED ADJACENT TO THE TWO-WAY COMMUNICATION SYSTEM.
 7.2.12.3.5 EACH AREA OF REFUGE SHALL BE IDENTIFIED BY A
 SIGN THAT READS AS THE FOLLOWS:AREA OF REFUGE
 7.2.12.3.5.1 THE SIGNS SHALL CONFORM TO THE
 REQUIREMENTS OF ICC/ANSI A117.1, AMERICAN NATIONAL
 STANDARD FOR ACCESSIBLE AND USABLE BUILDINGS AND
 FACILITIES, FOR SUCH SIGNAGE AND SHALL DISPLAY THE
 INTERNATIONAL SYMBOL OF ACCESSIBILITY.
 SIGNS ALSO SHALL BE LOCATED AS FOLLOWS:
 (1) AT EACH DOOR OPENING PROVIDING ACCESS TO THE AREA
 OF REFUGE
 (2) AT ALL EXITS NOT PROVIDING AN ACCESSIBLE MEANS OF
 EGRESS,
 (3) WHERE NECESSARY TO INDICATE CLEARLY THE DIRECTION
 TO AN AREA OF REFUGE, SIGNS SHALL BE ILLUMINATED AS
 REQUIRED FOR EXIT SIGNS WHERE EXIT SIGN ILLUMINATION IS
 REQUIRED.
 7.2.12.3.6 TACTILE SIGNAGE COMPLYING WITH ICC/ANSI
 A117.1, AMERICAN NATIONAL STANDARD FOR ACCESSIBLE AND
 USABLE BUILDINGS AND FACILITIES, SHALL BE LOCATED AT
 EACH DOOR OPENING TO AN AREA OF REFUGE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-03-23 Cont ID  
Sent By wjolin Date 2013-03-23 Time 12:20 Rev Time 0.00
Received By wjolin Date 2013-03-21 Time 13:17 Sent To  
Notes
2013-03-21 14:21:002707 OKEECHOBEE BOULEVARD
 PERMIT #13030497
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: ALL CONSTRUCTION AND DEMOLITION WORK SHALL
 CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH AND
 CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 SHEET A1.0: UPDATE THE CODE LIST TO REFERENCE THE 2010
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 SHEET A1.0: FIRE LANES SHALL HAVE AN UNOBSTRUCTED WIDTH
 OF NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL
 CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES PER SECTION
 18.2.3.4.1.1 OF THE FLORIDA FIRE PREVENTION CODE - NFPA
 1 UNIFORM FIRE CODE.
  
 SHEET A1.0: THE EXISTING UNMARKED FIRE LANE IS
 CONTINUOUSLY ENCROACHED UPON BY PARKED VEHICLES. FIRE
 LANES SHALL BE MARKED WITH PAINTED STRIPING AND
 FREESTANDING SIGNS READING, "FIRE LANE - NO PARKING BY
 ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL BE 12" X 18"
 WITH A WHITE BACKGROUND AND RED LETTERS AND SHALL BE A
 MAXIMUM OF SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE
 SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW
 AND BE SPACED A MAXIMUM OF 60 FEET APART. FLORIDA FIRE
 PREVENTION CODE SECTION 18.2.3.5.3.
  
 SHEET A1.1: PLEASE INDICATE THE FIRE RESISTANCE RATINGS
 OF NEW/EXISTING FIRE BARRIERS.
  
 SHEET A1.1: THE SECOND FLOOR BREAK ROOM AREA APPEARS TO
 BE APPROXIMATELY 900 SQ.FT. WITH AN OCCUPANT LOAD OF 60
 PERSON (15 SQ.FT. PER PERSON) RESULTING IN AN ASSEMBLY
 OCCUPANCY.
  
 SHEET A1.1: THE SECOND FLOOR STORAGE ROOMS HAVE
 UNPROTECTED VERTICAL OPENINGS BETWEEN THE FIRST AND
 SECOND FLOOR. THESE OPENINGS ARE NOT PERMITTED TO BE
 UNPROTECTED PER SECTION 42.3.1(2) OF NFPA 101 (2009
 EDITION WITH FLORIDA AMENDMENTS).
  
 SHEET A1.1: SHEET A1.0 INDICATES A SEPARATED USE
 DESIGN; HOWEVER, THREE REAR EXITS APPEAR TO LEAD
 INTO/THROUGH THE INDUSTRIAL OCCUPANCY (SERVICE BAYS).
 DOORS AND WINDOWS APPEAR TO BE UNRATED/UNPROTECTED
 ALONG THE REAR WALL OF THE BUILDING.
  
 SHEET A2.1: THE AREA OF REFUGE SHALL COMPLY WITH ALL
 REQUIREMENTS OF 7.2.12.2 AND 7.2.12.3 OF NFPA 101 (2009
 EDITION WITH FLORIDA AMENDMENTS).
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-16 Cont ID  
Sent By jwitmer Date 2013-05-16 Time 07:53 Rev Time 0.00
Received By jwitmer Date 2013-05-01 Time 17:18 Sent To  
Notes
2013-05-02 17:18:35SENT TO C12 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-17 Cont ID  
Sent By hmoser Date 2013-04-12 Time 11:31 Rev Time 0.00
Received By lmartine Date 2013-03-18 Time 10:36 Sent To  
Notes
2013-03-19 10:38:19C--12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2013-05-30 Cont ID  
Sent By jwitmer Date 2013-05-30 Time 16:14 Rev Time 0.00
Received By jwitmer Date 2013-05-30 Time 16:12 Sent To  
Notes
2013-05-30 16:13:48PBC IMPACT FEE ASSESSMENT
 MU-2013-01122-0000
 RECEIPT # 2013-0531-49
 $5,157.73

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-05-14 Cont ID  
Sent By jwitmer Date 2013-05-14 Time 14:22 Rev Time 0.00
Received By jwitmer Date 2013-05-14 Time 14:22 Sent To  
Notes
2013-05-14 14:23:10BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-04-01 Cont ID  
Sent By jwitmer Date 2013-04-01 Time 09:56 Rev Time 0.00
Received By jwitmer Date 2013-04-01 Time 09:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-05-16 Cont ID  
Sent By hmoser Date 2013-05-16 Time 12:03 Rev Time 0.00
Received By hmoser Date 2013-05-16 Time 12:03 Sent To  
Notes
2013-05-02 17:20:05NEW SHEETS SUBMITTED. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-04-01 Cont ID  
Sent By hmoser Date 2013-04-01 Time 13:32 Rev Time 0.00
Received By hmoser Date 2013-04-01 Time 10:52 Sent To  
Notes
2013-04-01 13:32:17PASS PROVISO
 1) REFER TO SECTION 601.4 BALANCED RETURN AIR.
 2010 FBC (M)
 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS.
 FOR FRESH AIR AND EXHAUST 2010 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-05-08 Cont ID  
Sent By lwagner Date 2013-05-08 Time 09:56 Rev Time 0.00
Received By lwagner Date   Time   Sent To  
Notes
2013-05-02 17:19:05NEW SHEETS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-03-26 Cont ID  
Sent By lwagner Date 2013-03-26 Time 13:51 Rev Time 0.00
Received By lwagner Date 2013-03-25 Time 10:08 Sent To  
Notes
2013-03-26 13:38:09***PROVISO***
 THE RESTROOMS AND ACCESSIBLE STALLS SHOWN ON A6.0 ARE
 ALL REQUIRED TO BE A MINIMUM OF 7'-1" WIDE TO ACHIEVE
 THE REQUIRED 60" CLEAR SPACE FOR THE WATER CLOSET.
 FBC ACCESSIBILITY CODE 2010 604.3.1 SIZE. CLEARANCE
 AROUND A WATER CLOSET SHALL BE 60 INCHES (1525 MM)
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL.
 FBC ACCESSIBILITY CODE 2010 604.3.2 THE LAVATORY WILL
 NOT BE PERMITTED IN THE 60" SPACE.
 PLEASE ALSO SEE FIGURE 604.8.1.6
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2013-05-14 Cont ID  
Sent By jwitmer Date 2013-05-14 Time 14:21 Rev Time 0.00
Received By jwitmer Date 2013-05-14 Time 14:21 Sent To  
Notes
2013-05-14 14:22:11PROVISO: 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2013-04-01 Cont ID  
Sent By jwitmer Date 2013-04-01 Time 09:57 Rev Time 0.00
Received By jwitmer Date 2013-04-01 Time 09:57 Sent To  
Notes
2013-04-01 09:57:36ROOF

Review Stop Z ZONING
Rev No 2 Status P Date 2013-05-15 Cont ID  
Sent By jroach Date 2013-05-15 Time 17:14 Rev Time 0.00
Received By jroach Date 2013-05-14 Time 10:37 Sent To  
Notes
2013-05-15 17:14:27ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.15.2013
 PERMIT NO.: 13030497
 ADDRESS: 2707 OKEECHOBEE BOULEVARD
 CONTRACTOR/CONTACT: ALAN COTRILL
 TELEPHONE NO.: 305.804.4051
 SCOPE OF REVIEW: INTERIOR RENOVATIONS TO EXISTING CAR
 SALES FACILITY.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THIS APPROVAL IS FOR INTERIOR WORK ONLY! SEPARATE
 PERMITS REQUIRED FOR SITE AND LANDSCAPE WORK. PLEASE
 NOTE THAT THE FOLLOWING WILL NEED TO BE CORRECTED PRIOR
 SUBMITTING PLANS FOR THE SITE AND/OR LANDSCAPE PERMITS:
  
 A. THE DUMPSTER ENCLOSURE PROPOSED IN THE NORTHWEST
 CORNER OF THE PROPERTY WILL NEED TO BE CONSTRUCTED
 UTILIZING AN OPAQUE SCREENING MATERIAL, NOT CHAIN LINK
 OR CHAIN LINK WITH SLATS.
  
 B. THE DUMPSTER ENCLOSURE PROPOSED IN THE NORTHWEST
 CORNER OF THE PROPERTY WILL NEED TO HAVE LANDSCAPE
 ISLANDS ON EITHER SIDE THAT ARE A MINIMUM OF FIVE (5)
 FEET IN WIDTH, PROTECTED FROM VEHICULAR ENCROACHMENT
 UTILIZING D-CURB OR SIMILAR, AND SHALL CONTAIN A
 SHADE/FLOWERING TREE IN EACH ISLAND. THE ENCLOSURE
 SHALL ALSO BE SURROUNDED ON THE THREE (3) SIDES WITH
 SHRUBS PLANTED AT 2-FOOT INTERVALS.
  
 C. THE LANDSCAPE BUFFER ALONG OKEECHOBEE BOULEVARD
 SHALL BE EXPANDED TO AT LEAST FIVE (5) FEET IN WIDTH.
  
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2013-04-12 Cont ID  
Sent By jroach Date 2013-04-12 Time 04:47 Rev Time 0.00
Received By jroach Date 2013-04-11 Time 13:32 Sent To  
Notes
2013-04-12 04:47:33ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.12.2013
 PERMIT NO.: 13030497
 ADDRESS: 2707 OKEECHOBEE BOULEVARD
 CONTRACTOR/CONTACT: ALAN COTTRILL
 TELEPHONE NO.: 904.422.5988
 SCOPE OF REVIEW: DEMOLITION, RENOVATION, ETC. FOR NEW
 CAR SALES FACILITY.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO SECTION 94-441(C) OF THE CITY?S ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDRS), BECAUSE THE
 SCOPE OF THE WORK EXCEEDS 50 PERCENT OF THE VALUE OF
 THE BUILDING, THE ENTIRE SITE SHALL BE BROUGHT INTO
 COMPLIANCE WITH ARTICLE XIV (LANDSCAPING) OF THE ZLDRS.
 PLEASE PROVIDE A COST BREAKDOWN TO SHOW THE VALUE OF
 THE WORK BEING DONE ON THE BUILDING, AS COMPARED TO THE
 VALUE OF THE SITE WORK (I.E. PROPOSED LANDSCAPING) THAT
 IS BEING DONE.
 2. EVEN IF IT IS DETERMINED THAT THE SCOPE DOES NOT
 EXCEED 50 PERCENT, STAFF WOULD LIKE TO WORK WITH THE
 TENANT TO ACHIEVE AS MUCH LANDSCAPING ON THE PROPERTY
 AS POSSIBLE, SUCH AS BUFFERS ALONG OKEECHOBEE
 BOULEVARD, ETC.
 3. LANDSCAPING ISLANDS WILL NEED TO BE INSTALLED AT THE
 EAST ENDS OF THE PARKING ROWS LOCATED BETWEEN
 OKEECHOBEE BOULEVARD AND THE NEW CHAIN LINK FENCE.
 4. PLEASE PROVIDE A DETAIL OF THE PROPOSED CHAIN LINK
 FENCE, INCLUDING HEIGHT.
 5. THE PARKING SPACE THAT CONTAINS AN EXISTING LIGHT
 POLE IN THE MIDDLE OF IT WILL NEED TO BE STRIPED SUCH
 THAT THERE IS NO PARKING.
 6. PLEASE PROVIDE TWO (2) COPIES OF A CURRENT AND
 ACCURATE SURVEY.
 7. PLEASE CLARIFY REUSE OF THE EXISTING SIGN. IS THE
 SIGN TO REMAIN IN ITS CURRENT LOCATION, OR IS IT BEING
 REUSED ELSEWHERE ON THE PROPERTY. IF THE SIGN IS
 RELOCATED, IT WILL NEED TO CONFORM TO ARTICLE XIII OF
 THE ZLDRS.
 8. DUMPSTER ENCLOSURES SHALL CONFORM TO THE
 REQUIREMENTS OF SECTION 94-444 OF THE ZLDRS, INCLUDING
 THE FACT THAT SCREENING SHALL BE OPAQUE AND NOT
 CHAINLINK. ADDITIONALLY, LANDSCAPING SHALL BE INSTALLED
 AROUND THE ENCLOSURE, CONSISTING OF SHURBS OR HEDGES
 PLANTED AT 2-FOOT INTERVALS.
 9. LANDSCAPE PLANS WILL NEED TO BE SUBMITTED UNDER A
 SEPARATE PERMIT APPLICATION AND SHALL BE ACCOMPANIED BY
 A CERTIFIED COST ESTIMATE.
 10. PLEASE NOTE THAT PURSUANT TO SECTION 94-443(C)(3)
 OF THE ZLDRS, LANDSCAPE ISLANDS IN THE PARKING LOT ARE
 TO CONSIST OF SHADE/FLOWERING TREES, NOT PALMS. PALMS
 MAY ONLY BE SUBSTITUTED FOR UP TO 35% OF THE REQUIRED
 SHADE/FLOWERING TREES ON THE SITE.
 11. BASED UPON THE PARKING CALCULATIONS PROVIDED, THERE
 SHOULD BE 79 SPACES LEFT OPEN AS ?NON-DISPLAY? SPACES.
 NON-DISPLAY SPACES SHOULD BE IN CONFORMANCE WITH THE
 ZLDRS WITH ITEMS SUCH AS LANDSCAPE ISLANDS, NO MORE
 THAN 10 CONSECUTIVE SPACES, ETC.
 12. A LANDSCAPE ISLAND NEEDS TO BE PLACED ON THE NORTH
 SIDE OF THE 2 PARKING SPACES IN THE FAR SOUTHWEST
 CORNER OF THE PROPERTY.
  
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  
2013-03-22 16:05:443/22/13


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved