Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-03-21 Cont ID  
Sent By rlecky Date 2013-03-21 Time 14:27 Rev Time 0.00
Received By rlecky Date 2013-03-21 Time 14:27 Sent To FIRE
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-04-11 Cont ID  
Sent By wjolin Date 2013-04-11 Time 14:31 Rev Time 0.00
Received By wjolin Date 2013-04-11 Time 14:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-03-25 Cont ID  
Sent By rferguso Date 2013-03-25 Time 12:51 Rev Time 0.00
Received By rferguso Date 2013-03-25 Time 12:51 Sent To  
Notes
2013-03-25 13:13:49425 24TH STREET
 PERMIT #13030435
  
  
 PLAN REVIEW COMMENTS FOR WEST PALM BEACH FIRE RESCUE
  
 * THE INFORMATION BELLOW MUST BE INDICATED ON THE
 PLANS.
  
 * PLAN REVIEW COMMENTS FORSECTION 7.2.1.6.2 OF NFPA 101
 FLORIDA EDITION 2009 ALLOWS ACCESS CONTROLLED EGRESS
 DOORS PROVIDED THAT ALL SEVEN OF THE FOLLOWING CRITERIA
 ARE MET:
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
  
  
  
 CAPTAIN RONALD E. FERGUSON, ASSITANT FIRE MARSHAL
 BUREAU OF FIRE PREVENTION
 WEST PALM BEACH FIRE RESCUE
 PHONE #(561) 804-4756
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-03-19 Cont ID  
Sent By ddaniels Date 2013-03-19 Time 13:03 Rev Time 0.00
Received By ddaniels Date 2013-03-19 Time 13:03 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-11 Cont ID  
Sent By rlecky Date 2013-04-11 Time 14:35 Rev Time 0.00
Received By rmcdouga Date 2013-03-14 Time 16:48 Sent To  
Notes
2013-03-21 14:37:18SENT TO FIRE FOR COMMENTS.
2013-03-14 16:49:08IN FIRE BOX


Account Summary | Usage Policy | Privacy Policy