Plan Review Details - Permit 13030290
Plan Review Stops For Permit 13030290
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-11 Cont ID  
Sent By shill Date 2013-03-11 Time 15:42 Rev Time 0.00
Received By shill Date 2013-03-11 Time 15:42 Sent To FIRE
Notes
2013-03-11 16:14:15****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE A SURVEY FOR THIS PROPERTY. IT APPEARS THAT
 THE BACK OF THE BUILDING SITS ON THE PROPERTY LINE, BUT
 ONE OF THE PROPOSED DOORS APPEARS TO ENCROACH THE
 PROPERTY LINE. ADDITIONALLY, IT APPEARS THAT PLAYGROUND
 EQUIPMENT WAS INSTALLED WITHOUT A PERMIT ON THE
 ADJACENT FEC EASEMENT. APPLY FOR PERMIT.
 IMPROVEMENTS/ENCROACHMENTS ONTO PROPERTY OTHER THAN
 THIS PARCEL ARE TO BE ON SEPARATE PERMITS, SIGNED BY
 THE OWNER OF THE PROPERTY.
  
 2. THIS PROPERTY HAS A NUMBER OF EXPIRED PERMITS.
 PLEASE ADDRESS. PLEASE EMAIL [email protected] FOR THE
 PROCEDURE TO CLOSE OUT THE EXPIRED PERMITS.
  
 3. THERE HAS BEEN WORK DONE ON THIS BUILDING AND
 PROPERTY WHICH WAS DONE WITHOUT PERMITS. APPLY FOR
 PERMIT FOR ALL UNPERMITTED WORK.
  
 4. THE PRODUCT APPROVAL SUBMITTED IS EXPIRED. A VALID
 CURRENT FLORIDA STATE OR LOCAL PRODUCT APPROVAL IS
 REQUIRED FAC9N-3.
  
 5. IT IS NOT CLEAR WHETHER THIS IS A DAY CARE OR
 EDUCATIONAL OCCUPANCY. SEE FBC CHAPTER 3.
  
 6. SEE FBC 1031 AND FBC 1037 FOR HARDWARE REQUIREMENTS.
 REVISE PLAN TO SHOW COMPLIANCE.
  
 7. PROVIDE A STRUCTURAL DETAIL FOR PROPOSED NEW
 DOORWAYS FBC 1609. THIS SHOULD INCLUDE WIND DESIGN
 CRITERIA FBC 1603.4.1.
  
 8. OWNER IS TO IMMEDIATELY ADDRESS ISSUES ABOVE OR WILL
 BE ISSUED A CEASE AND DESIST (FROM FIRE) AND AN STOP
 WORK ORDER WITH FINES (FROM BUILDING). PLEASE ADVISE AS
 TO PLAN FOR BRINGING THIS STRUCTURE INTO COMPLIANCE.
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-03-12 Cont ID  
Sent By wjolin Date 2013-03-12 Time 14:04 Rev Time 0.00
Received By wjolin Date 2013-03-12 Time 13:53 Sent To  
Notes
2013-03-12 14:04:432821 PINEWOOD AVENUE
 PERMIT #13030290
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NEW EXIT DOORS WILL REQUIRE ILLUMINATED EXIT SIGNS AND
 EMERGENCY LIGHTING. PROVIDE FIRE ALARM PULL STATIONS A
 NEW EXIT DOOR LOCATIONS.
  
 THE INFANT AREA EXIT DOOR (INSTALLED W/O PERMIT) NEEDS
 TO LEAD TO THE PUBLIC WAY; THE CURRENT EXIT DISCHARGE
 IS ENCLOSED BY A FENCED-IN PLAY AREA.
  
 CONVERTING THE CURRENT STORAGE ROOM INTO AN
 "AFTERSCHOOL CARE FOR 3-4-5" YEAR OLDS WILL INCREASE
 THE OCCUPANT LOAD TO GREATER THAN 50 PERSONS WHEREBY
 THE DOORS IN THE MEANS OF EGRESS SHALL SWING IN THE
 DIRECTION TRAVEL. THIS AFFECT THE DOUBLE-DOORS
 SOUTHWEST OF THE KITCHEN AND THE MAIN ENTRY VESTIBULE
 DOOR.
  
 OWNER WAS DIRECTED TO SUBMIT PLANS FOR PERMIT FOR ALL
 UNPERMITTED WORK INCLUDING NEW BATHROOM LOCATED IN
 INFANT'S AREA. NOTHING SUBMITTED.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-18 Cont ID  
Sent By shill Date 2013-03-18 Time 13:58 Rev Time 0.00
Received By shill Date 2013-03-11 Time 14:46 Sent To  
Notes
2013-03-11 16:38:513/11 TO FIRE
  
2013-03-11 14:47:04MISC. #1