Plan Review Details - Permit 13030266
Plan Review Stops For Permit 13030266
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-03-11 Cont ID  
Sent By rferguso Date 2013-03-11 Time 14:02 Rev Time 0.00
Received By rferguso Date 2013-03-11 Time 14:02 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-19 Cont ID  
Sent By hmoser Date 2013-03-19 Time 08:50 Rev Time 0.00
Received By hmoser Date 2013-03-08 Time 18:00 Sent To  
Notes
2013-03-08 18:00:55TO FIRE
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-03-19 Cont ID  
Sent By hmoser Date 2013-03-19 Time 08:49 Rev Time 0.00
Received By hmoser Date 2013-03-19 Time 08:49 Sent To  
Notes
2013-03-19 09:04:24PROVISO - FBC M 507.2.1.1 TYPE I HOOD SYSTEMS SHALL BE
 DESIGNED AND INSTALLED TO AUTOMATICALLY ACTIVATE THE
 EXHAUST FAN WHENEVER COOKING OPERATIONS OCCUR. THE
 ACTIVATION OF THE EXHAUST FAN SHALL OCCUR THROUGH AN
 INTERLOCK WITH THE COOKING APPLIANCES, BY MEANS OF HEAT
 SENSORS OR BY MEANS OF OTHER APPROVED METHODS
  