| Plan Review Stops For Permit 13030210 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2013-03-12 |
|
|
Cont ID |
|
| Sent By |
ddaniels |
Date |
2013-03-12 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
ddaniels |
Date |
2013-03-11 |
Time |
21:34 |
Sent To |
|
|
| Notes |
| 2013-03-12 14:48:02 | FIRE PLAN REVIEW | | | PERMIT # 13030210 | | | ADDRESS: 105 EVERNIA STREET | | | CONTRACTOR: YACHTING PROMOTIONS INC. | | | PHONE: 954-764-7642 | | | ACTION: PASSED | | | | | | FLORIDA FIRE PREVENTION CODE 2010 EDITION | | | | | | 1. PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | 2. LEGEND INDICATES 79 PORTABLE FIRE EXTINGUISHERS | | | PLANS SHOW 73. | | | | | | 3. TENT SHALL BE OF THE OPEN AREA/NO SIDES TYPE, | | | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS | | | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | | | | | 4. POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | | LOCATIONS. | | | | | | | | | DERRICK L. DANIELS, BATTALION CHIEF / FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | OFFICE OF THE FIRE MARSHAL | | | (561) 804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-03-11 |
|
|
Cont ID |
|
| Sent By |
ddaniels |
Date |
2013-03-11 |
Time |
21:35 |
Rev Time |
0.00 |
| Received By |
ddaniels |
Date |
2013-03-07 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2013-03-11 13:03:00 | GAVE TO WESLEY, 3/11/13 |
|
|
|