Plan Review Details - Permit 13030091
Plan Review Stops For Permit 13030091
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-07-05 Cont ID  
Sent By shill Date 2013-07-05 Time 09:11 Rev Time 0.00
Received By shill Date 2013-07-05 Time 09:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-07-01 Cont ID  
Sent By shill Date 2013-07-01 Time 09:02 Rev Time 0.00
Received By shill Date 2013-07-01 Time 09:02 Sent To  
Notes
2013-07-01 09:07:02****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ONE SET OF THE THREE SUBMITTED HAVE ALL OF THE MOST
 CURRENT SHEETS. THE OTHER TWO SETS HAVE OLDER VERSIONS
 OF MANY SHEETS. THREE IDENTICAL SETS OF PLANS REQUIRED
 FOR PERMIT ISSUANCE FBC 107.
  
 CONTRACTOR MAY DO ONE OF THE FOLLOWING:
  
 SUBMIT TWO ADDITIONAL COMPLETE CURRENT SETS. THEY WILL
 BE SEEN BY ALL TRADES AND STAMPED BY ALL TRADES; OR
  
 PAY FEES, HAVE CONTRACTOR SUBMIT APPLICATION, AND
 PERMIT CARD WILL BE ISSUED. AFTER PLANS ARE SCANNED
 (WITHIN 3 BUSINESS DAYS), A CD WILL BE MADE AVAILABLE.
 CONTRACTOR IS TO HAVE TWO ADDITIONAL SETS OF PLANS
 PRINTED AND THEN RETURN TO THE BUILDING DIVISION FOR
 ORIGINAL PERMIT # STAMP (1 BUSINESS DAY).
  
 2. SEE JIM WITMER'S PLAN REVIEW COMMENTS REGARDING
 THRESHOLD.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-06-20 Cont ID  
Sent By jwitmer Date 2013-06-20 Time 14:53 Rev Time 0.00
Received By jwitmer Date 2013-06-20 Time 14:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-22 Cont ID  
Sent By jwitmer Date 2013-03-22 Time 08:31 Rev Time 0.00
Received By jwitmer Date 2013-03-21 Time 15:45 Sent To  
Notes
2013-03-22 07:56:34BUILDING PLAN REVIEW
 PERMIT: 13030091
 ADD: 600 S ROSEMARY SUITE # 170
 CONT: TBD
 TEL: (561)856-6655
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MARCH 22/2013
 ACTION: DENIED
  
 1) PLANS REQUIRE CITY PLACE REVIEW STAMP OF APPROVAL
 BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT. CITY
 ATTORNEYS.
  
 2) SHEET D-1 INDICATES THE REMOVAL OFEXTERIOR DOOR #5 &
 21SEE NOTE # 5 & 21. SHEET A1 INDICATES THESE DOORS
 WILL BE REPLACED WITH EXTERIOR FOLDING TYPE DOORS. NO
 PRODUCT APPROVALS WERE SUBMITTED FOR THIS REVIEW.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) SHEET S-2 INDICATES THE MAX. MEAN ROOF HEIGHT OF
 20'-0". PLEASE SEE ORIGINAL FOUNDATION & SHELL PERMIT
 99071297 SHEETS 12/42 & 13/ 42 THAT PROVIDE A MEAN ROOF
 HEIGHT OF APPROXIMATELY 80 FEET, PLEASE RECALULATE
 PRESSURES FOR A MEAN ROOF HEIGHT OF 80'-0" USING ASCE
 7-10 BUILDINGS WITH A MEAN ROOF HEIGHT OF < THAN 60
 FEET.
  
 5) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING WITH
 A HEIGHT GREATER THAN 50'-0". SEE DEFINITION FOR
 THRESHOLD BUILDING.
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 5A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 5B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. CONTACT KEN CONRAD MANAGER OF
 THE SPECIAL INSPECTOR PROGRAM AT (561)805-6666 FOR
 FURTHER INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 5C) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B.
 AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 5D) THREE SETS OF PLANS WILL NEED TO BE PROVIDED A
 THIRD SET OF PLANS FOR THE THRESHOLD INSPECTOR.
  
 5E) A THRESHOLD PLAN REVIEW STOP WILL BE PUT ON THIS
 PROJECT UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY
 THE CHIEF BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 6) SHEET E-3 INDICATES EXIT LIGHTS OVER THE EAST AND
 WEST END BIFOLD SETS OF DOORS, 1008.1.2 REQUIRES EGRESS
 DOORS TO BE PIVOTED OR SIDE SWINGING. EGRESS DOORS ALSO
 ARE REQUIRED TO BE A MINIMUM CLEAR WIDTH OF 32" (
 1008.1.1) PLEASE PROVIDE WHAT THE CLEAR WIDTH OF THE
 EGRESS DOOR?
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-03-19 Cont ID  
Sent By rlecky Date 2013-03-19 Time 10:29 Rev Time 0.00
Received By rlecky Date 2013-03-18 Time 16:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-06-26 Cont ID  
Sent By wjolin Date 2013-06-26 Time 13:09 Rev Time 0.00
Received By wjolin Date 2013-06-26 Time 12:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-03-19 Cont ID  
Sent By wjolin Date 2013-03-19 Time 14:17 Rev Time 0.00
Received By wjolin Date 2013-03-19 Time 11:52 Sent To  
Notes
2013-03-19 14:17:46600 SOUTH ROSEMARY AVENUE - #170
 PERMIT #13030091
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED.WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 SHEET A-0: PLAN INDICATES A MERCATILE OCCUPANCY WHICH
 SHOULD BE CORRECTED TO AN ASSEMBLY OCCUPANCY.
  
 SHEET A-2: CONFIRM EXISTING EXIT DOORS ARE EQUIPPED
 WITH PANIC HARDWARE. NOTE: FOR OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS, PANIC HARDWARE
 SHALL BE PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH.
 NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT
 BE RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR
 PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE
 AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A
 READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN
 UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS
 SHALL BE AT LEAST 1 INCH IN HEIGHT. A THUMB TURN STYLE
 LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED
 LOCK.
  
 SHEET A-2: PRIVATE DINING "A" & "B" (DOOR #13 AND #14)
 HAS DOORS THAT ARE PART OF THE EXIT ACCESS AND ARE
 REQUIRED TO BE SIDE-SWINGING IN LIEU OF SLIDING POCKET
 DOORS.
  
 SHEET E-3: NO EXIT SIGNS SHOWN IN PRIVATE DINING "A" OR
 "B"; REFER TO LIFE SAFETY PLAN FOR EXIT SIGN LOCATIONS.
  
 SHEET K1.1: BURNER RANGE #105 DOES NOT APPEAR TO BE
 LOCATED UNDER THE KITCHEN EXHAUST HOOD OR PROTECTED BY
 THE WET-CHEMICAL EXTINGUISHING SYSTEM.
  
 CONFIRM PIZZA OVEN IS GAS FUELED ONLY (NO SOLID FUEL;
 IE WOOD).
  
 SEPARATE PLANS AND PERMIT NEEDED TO ENSURE EXISTING
 KITCHEN HOOD SUPPRESSION SYSTEM IS PROPERLY PROTECTING
 NEW COOKING EQUIPMENT.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-01 Cont ID  
Sent By shill Date 2013-06-26 Time 09:02 Rev Time 0.00
Received By shill Date 2013-06-17 Time 15:46 Sent To  
Notes
2013-06-18 15:48:06*EXPEDITED*
 C--34

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-22 Cont ID  
Sent By hmoser Date 2013-03-22 Time 14:32 Rev Time 0.00
Received By hmoser Date 2013-03-05 Time 14:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-03-22 Cont ID  
Sent By hmoser Date 2013-03-22 Time 14:32 Rev Time 0.00
Received By hmoser Date 2013-03-22 Time 10:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-03-11 Cont ID  
Sent By lwagner Date 2013-03-11 Time 11:36 Rev Time 0.00
Received By lwagner Date 2013-03-08 Time 13:56 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2013-07-05 Cont ID  
Sent By shill Date 2013-07-05 Time 09:12 Rev Time 0.00
Received By shill Date 2013-03-22 Time 08:19 Sent To  
Notes
2013-07-05 09:12:53OK PER KEN CONRAD
  
  
2013-03-22 08:19:48THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING WITH A
 HEIGHT GREATER THAN 50'-0". SEE DEFINITION FOR
 THRESHOLD BUILDING.
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 1A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. CONTACT KEN CONRAD MANAGER OF
 THE SPECIAL INSPECTOR PROGRAM AT (561)805-6666 FOR
 FURTHER INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 1C) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B.
 AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 1D) THREE SETS OF PLANS WILL NEED TO BE PROVIDED A
 THIRD SET OF PLANS FOR THE THRESHOLD INSPECTOR.
  
 1E) A THRESHOLD PLAN REVIEW STOP WILL BE PUT ON THIS
 PROJECT UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY
 THE CHIEF BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2013-06-26 Cont ID  
Sent By eschneid Date 2013-06-26 Time 17:49 Rev Time 1.00
Received By eschneid Date 2013-06-26 Time 17:49 Sent To  
Notes
2013-06-26 19:17:11THE REVISED CANOPY, AWNINGS AND SIGNS REQUIRE SEPARATE
 PERMITS.
  
  
2013-06-24 17:58:556/24/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-03-18 Cont ID  
Sent By Eschneid Date 2013-03-18 Time 11:42 Rev Time 3.00
Received By eschneid Date 2013-03-15 Time 08:50 Sent To  
Notes
2013-03-18 11:52:14FAILED
  
 1) THE PLANS REQUIRE THE CITYPLACE APPROVAL STAMP.
  
 2) THE CHANGES TO THE EXTERIOR FACADE OF THE BUILDING
 REQUIRE THE APPROVAL OF A MINOR PLANNED DEVELOPMENT
 AMENDMENT. PLEASE NOTE THAT ZONING STAFF HAS DETERMINED
 THAT THE REMOVAL OF THE STONE COLUMNS AND THE ARCHWAYS
 ON THE SOUTH FACADE OF THE BUILDING DO NOT MEET THE
 MASTER DESIGN GUIDELINES FOR CITYPLACE, AND STAFF WILL
 NOT APPROVE A MINOR AMENDMENT FOR THE PLANS AS
 CURRENTLY SUBMITTED.
  
 3) THE STONE AND TILE APPLICATIONS TO THE SOUTH SIDE OF
 THE BUILDING ARE OUT OF PLACE ON THIS BUILDING, SINCE
 THE REMAINDER OF THE BUILDING IS STUCCO.
  
 4) THE WALK-UP BAR IS NOT A PERMITTED USE FOR THE
 BUILDING AND SHALL BE REMOVED FROM THE PLANS.
  
 5) THE REVISED CANOPY, AWNINGS AND SIGNS REQUIRE
 SEPARATE PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
2013-03-07 14:30:503/7/13