Plan Review Details - Permit 13030087
Plan Review Stops For Permit 13030087
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-03-12 Cont ID  
Sent By ddaniels Date 2013-03-12 Time 14:55 Rev Time 0.00
Received By ddaniels Date 2013-03-12 Time 14:54 Sent To M
Notes
2013-03-12 14:59:20FIRE PLAN REVIEW
 PERMIT # 13030087
 ADDRESS: 1901 PALM BEACH LAKES BOULEVARD
 CONTRACTOR: AB FIRE EQUIPMENT
 PHONE: 954-570-9860
 ACTION: PASSED
  
 FLORIDA FIRE PREVENTION CODE 2010 EDITION
  
  
 1. A MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG
 THE EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A
 MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE
 DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE THE FLOOR
 AND SHALL CLEARLY IDENTIFY THE HAZARD PROTECTED PER FBC
 904.11.1.
  
 DERRICK L. DANIELS, BATTALION CHIEF / FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-14 Cont ID  
Sent By shill Date 2013-03-14 Time 14:17 Rev Time 0.00
Received By shill Date 2013-03-05 Time 13:47 Sent To  
Notes
2013-03-05 13:47:56TO FIRE
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-03-14 Cont ID  
Sent By hmoser Date 2013-03-14 Time 11:08 Rev Time 0.00
Received By hmoser Date 2013-03-14 Time 11:08 Sent To  
Notes
2013-03-14 14:15:59PROVISO - REMOTE PULL STATION SHOULD BE 42 - 48 INCHES
 ABOVE THE FINISHED FLOOR IN THE MAIN PATH OF EGRESS, A
 MINIMUM OF 10 FEET FROM THE HAZARD, AND A MAXIMUM OF 20
 FEET.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved