Plan Review Details - Permit 13030068
Plan Review Stops For Permit 13030068
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-03-18 Cont ID  
Sent By shill Date 2013-03-18 Time 18:17 Rev Time 0.00
Received By shill Date 2013-03-18 Time 18:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-05 Cont ID  
Sent By shill Date 2013-03-05 Time 08:37 Rev Time 0.00
Received By shill Date 2013-03-05 Time 08:37 Sent To  
Notes
2013-03-05 08:40:52****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. VALUE IS TO INCLUDE LABOR AND MATERIALS, FBC 109.
 ADJUST VALUE OR PROVIDE RECEIPT FOR MATERIALS.
  
 2. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-03-18 Cont ID  
Sent By shill Date 2013-03-18 Time 18:17 Rev Time 0.00
Received By shill Date 2013-03-18 Time 16:37 Sent To  
Notes
2013-03-18 16:37:57GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-05 Cont ID  
Sent By shill Date 2013-03-05 Time 08:41 Rev Time 0.00
Received By shill Date 2013-03-04 Time 16:26 Sent To  
Notes
2013-03-04 16:26:28SENT TO MISC 1 BOX