Plan Review Details - Permit 13030034
Plan Review Stops For Permit 13030034
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-04-17 Cont ID  
Sent By shill Date 2013-04-17 Time 17:00 Rev Time 0.00
Received By shill Date 2013-04-17 Time 17:00 Sent To  
Notes
2013-04-17 17:12:24****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LISTS:
  
 1. FOR THE WINDOWS : REVISE THE PLAN TO SHOW ROOM
 DESIGNATIONS. NOTE EXISTING CONDITIONS (TYPE OF WINDOW)
 AND OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1.
 THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%.
  
 FIRST PLAN SHOWED 60" WINDOW AT BEDROOM, SECOND SHOWS A
 48". IF THIS WINDOW IS 48" HIGH, REVISE PLAN TO INCLUDE
 TYPE OF WINDOW THAT IS EXISTING.
  
 3RD REVIEW, A PLAN SUBMITTED WITH NO WINDOWS SHOWN, AND
 DOES NOT CORRELATE WITH ELEVATIONS AS THERE IS NO
 COMPASS NORTH ON THE PLAN. TYPE OF EXISTING WINDOWS NOT
 PROVIDED.
  
 2. FOR THE SHUTTERS:
  
 THE INSTALLATION SCHEDULE SUBMITTED DOES NOT INCLUDE
 THE INFORMATION "SHUTTER MOUNTING CONNECTIN TYPE", SEE
 SHEETS 12 THROUGH 15 OF THE NOA. FOR INSTANCE,
 "ALTERNATIVE 1" WOULD REQUIRED 6" OC ANCHOR SPACING,
 SEE DETAIL. MOST OF THE CONNECTION TYPES APPEAR TO
 REQUIRE 6" SPACING, BUT 8" IS PROPOSED. HOWEVER WITHOUT
 KNOWING WHICH INSTALLATION METHOD (CONNECTION TYPE) IS
 PROPOSED, COMPLIANCE CANNOT BE DETERMINED.
  
 PRESSURES ARE TOO HIGH FOR THE SHUTTERS WHICH ARE
 LIMITED TO -72PSF. IT IS NOT CLEAR WHY YOU HAVE
 SPECIFIED THESE PRESSURES: +-45 WOULD MEET MINIMUM CODE
 COMPLIANCE FOR ALL OPENINGS. FBC R 301
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-03-13 Cont ID  
Sent By shill Date 2013-03-13 Time 15:16 Rev Time 0.00
Received By shill Date 2013-03-13 Time 15:16 Sent To  
Notes
2013-03-13 15:20:29****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. FOR THE WINDOWS : REVISE THE PLAN TO SHOW ROOM
 DESIGNATIONS. NOTE EXISTING CONDITIONS (TYPE OF WINDOW)
 AND OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1.
 THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%.
  
 FIRST PLAN SHOWED 60" WINDOW AT BEDROOM, SECOND SHOWS A
 48". IF THIS WINDOW IS 48" HIGH, REVISE PLAN TO INCLUDE
 TYPE OF WINDOW THAT IS EXISTING.
  
 2. FOR THE SHUTTERS:
  
 COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 2ND REVIEW, NOT ADDRESSED. A BLANK INSTALLATION
 SCHEDULE WAS SUBMITTED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-04 Cont ID  
Sent By shill Date 2013-03-04 Time 08:44 Rev Time 0.00
Received By shill Date 2013-03-04 Time 08:44 Sent To  
Notes
2013-03-04 08:46:24****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FOR THE WINDOWS : REVISE THE PLAN TO SHOW ROOM
 DESIGNATIONS. NOTE EXISTING CONDITIONS (TYPE OF WINDOW)
 AND OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1.
 THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%.
  
 2. FOR THE SHUTTERS:
  
 COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2013-03-01 Cont ID  
Sent By fmittner Date 2013-03-01 Time 14:44 Rev Time 0.00
Received By fmittner Date 2013-03-01 Time 14:21 Sent To  
Notes
2013-03-01 14:45:05APPROVED FOR 6/6 SH, CLEAR GLASS WHITE FRAMES.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-04-17 Cont ID  
Sent By shill Date 2013-04-17 Time 17:12 Rev Time 0.00
Received By shill Date 2013-04-11 Time 13:15 Sent To  
Notes
2013-04-12 13:15:23SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-03-13 Cont ID  
Sent By shill Date 2013-03-13 Time 15:20 Rev Time 0.00
Received By shill Date 2013-03-11 Time 08:58 Sent To  
Notes
2013-03-12 08:58:49GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-04 Cont ID  
Sent By shill Date 2013-03-04 Time 08:46 Rev Time 0.00
Received By shill Date 2013-03-04 Time 08:46 Sent To  
Notes
***NONE***