Plan Review Details - Permit 13030020
Plan Review Stops For Permit 13030020
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-09-23 Cont ID  
Sent By shill Date 2013-09-23 Time 16:38 Rev Time 0.00
Received By shill Date 2013-09-23 Time 16:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-09-14 Cont ID  
Sent By shill Date 2013-09-14 Time 11:28 Rev Time 0.00
Received By shill Date 2013-09-14 Time 11:28 Sent To  
Notes
2013-09-14 11:30:19****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 9. CONTRACTOR INFORMED THAT NO MECHANICAL WORK IS
 PROPOSED, ALL EXISTING. THERE IS NO RECORD OF AIR
 CONDITIONING INSTALLED AT THIS LOCATION. PLEASE
 ADDRESS. FBC 107
  
 SHEET 1 STATES THAT THERE IS NO A/C EXISTING IN THIS
 RESIDENCE. ALL THREE SHEETS ARE MARKED SHEET 1, BUT
 FIRST SUBMITTAL HAD THREE PAGES. SECOND PAGE HAS
 MECHANICAL DETAILS. THIRD PAGE, ELECTRICAL PLAN SHOWS
 AHU. PLEASE ADDRESS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-06-29 Cont ID  
Sent By shill Date 2013-06-29 Time 07:46 Rev Time 0.00
Received By shill Date 2013-06-29 Time 07:46 Sent To  
Notes
2013-06-29 07:52:00****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1-2. OK
  
 3. BEDROOM #1 DOES NOT EMERGENCY MEANS OF ESCAPE AND
 RESCUE WHICH COMPLIES WITH FBC R 310. IT APPEARS THAT
 THIS WAS CONVERTED FROM A PORCH TO A BEDROOM WITHOUT A
 PERMIT. PROVIDE AN EGRESS OPENING.
  
 2ND REVIEW - WINDOW SIZE INCREASED BUT NO DETAIL
 PROVIDED FOR NEW ENLARGED OPENING, FBC 109, FBC 2010
 RESIDENTIAL 301.
  
 4. OK
  
 5. PROVIDE A STRUCTURAL DETAIL FOR THE INFILL FBC R
 301, FBC 107.
  
 NOT ADDRESSED.
  
 6. OK
  
 7. AS IT APPEARS THAT UNINHABITABLE SPACE WAS CONVERTED
 TO HABITABLE SPACE, IMPACT FEE ASSESSMENT REQUIRED.
 CONTACT 561-233-5025 FOR MORE INFORMATION. REVISE PLAN
 TO REFLECT CONVERSION OF PORCH TO LIVING SPACE WITH
 APPLICABLE DETAILS.
  
 NEW COMMENTS:
  
 8. SHUTTER PRODUCT APPROVALS SUBMITTED ON 2ND REVIEW.
 COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 9. CONTRACTOR INFORMED THAT NO MECHANICAL WORK IS
 PROPOSED, ALL EXISTING. THERE IS NO RECORD OF AIR
 CONDITIONING INSTALLED AT THIS LOCATION. PLEASE
 ADDRESS. FBC 107
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-21 Cont ID  
Sent By shill Date 2013-03-21 Time 13:34 Rev Time 0.00
Received By shill Date 2013-03-21 Time 12:53 Sent To  
Notes
2013-03-21 13:40:47****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED,DATED ORIGINALS
 FS471.
  
 2. REVISE ASCE7 STANDARD TO CURRENT, FBC R CHAPTER 43.
  
 3. BEDROOM #1 DOES NOT EMERGENCY MEANS OF ESCAPE AND
 RESCUE WHICH COMPLIES WITH FBC R 310. IT APPEARS THAT
 THIS WAS CONVERTED FROM A PORCH TO A BEDROOM WITHOUT A
 PERMIT. PROVIDE AN EGRESS OPENING.
  
 4. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FAC9N-3 FOR ALL COMPONENTS AND CLADDING.
  
 5. PROVIDE A STRUCTURAL DETAIL FOR THE INFILL FBC R
 301, FBC 107.
  
 6. WALL CONSTRUCTION NOT CLEAR; ONE DETAIL SHOWS A 4X
 FRAME WALL, MECHANICAL PLAN SHOWS AN 8" WALL. IF THIS
 IS BLOCK, PROVIDE A DETAIL FOR BUCK INSTALLATION.
  
 7. AS IT APPEARS THAT UNINHABITABLE SPACE WAS CONVERTED
 TO HABITABLE SPACE, IMPACT FEE ASSESSMENT REQUIRED.
 CONTACT 561-233-5025 FOR MORE INFORMATION. REVISE PLAN
 TO REFLECT CONVERSION OF PORCH TO LIVING SPACE WITH
 APPLICABLE DETAILS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-03-18 Cont ID  
Sent By rlecky Date 2013-03-18 Time 16:33 Rev Time 0.00
Received By rlecky Date 2013-03-18 Time 16:25 Sent To  
Notes
2013-03-18 16:33:4313030020
 3219 PINEWOOD AVENUE
 REMODEL
  
 THE FOLLOWING CODE REQUIREMENTS WERE NOTED ON THE PLAN.
  
 PROVISO
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-09-14 Cont ID  
Sent By shill Date 2013-09-14 Time 11:30 Rev Time 0.00
Received By shill Date 2013-09-05 Time 08:05 Sent To  
Notes
2013-09-06 08:06:40SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-18 Cont ID  
Sent By hmoser Date 2013-07-18 Time 14:40 Rev Time 0.00
Received By hmoser Date 2013-06-07 Time 10:51 Sent To  
Notes
2013-06-25 11:55:12TO R09
  
2013-06-10 10:51:46SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-21 Cont ID  
Sent By shill Date 2013-03-21 Time 13:41 Rev Time 0.00
Received By shill Date 2013-03-01 Time 09:38 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2013-09-23 Cont ID  
Sent By shill Date 2013-09-23 Time 16:37 Rev Time 0.00
Received By shill Date 2013-09-23 Time 16:37 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-06-29 Cont ID  
Sent By shill Date 2013-06-29 Time 07:56 Rev Time 0.00
Received By shill Date 2013-06-29 Time 07:56 Sent To  
Notes
2013-06-29 07:56:13SEE BUILDING COMMENTS
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-03-21 Cont ID  
Sent By shill Date 2013-03-21 Time 13:41 Rev Time 0.00
Received By shill Date 2013-03-21 Time 13:40 Sent To  
Notes
2013-03-21 13:41:17SEE BUILDING COMMENTS
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2013-09-14 Cont ID  
Sent By shill Date 2013-09-14 Time 11:19 Rev Time 0.00
Received By shill Date 2013-09-14 Time 11:19 Sent To  
Notes
2013-09-14 11:19:29PER PLAN, NO MECHANICAL IN THIS BUILDING IS EXISTING
 AND NONE PROPOSED
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-07-18 Cont ID  
Sent By hmoser Date 2013-07-18 Time 14:39 Rev Time 0.00
Received By hmoser Date 2013-07-18 Time 14:31 Sent To  
Notes
2013-07-18 14:39:47DENIED
 NO PLANS ENERGY CALCULATIONS OR ARI PAGE
 SUBMITTED WITH RE-SUBMITTAL.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-03-21 Cont ID  
Sent By hmoser Date 2013-03-21 Time 09:53 Rev Time 0.00
Received By hmoser Date 2013-03-21 Time 09:53 Sent To  
Notes
2013-03-21 12:41:02****CORRECTIONS****
  
 1. ENERGY CALCS REQUIRED FBC 2010 ENERGY CONSERVATION
 103.2.1.
  
 2. EQUIPMENT SCHEDULE, MANUAL J, ARI INFORMATION
 REQUIRED FBC 2010 ENERGY CONSERVATION 103.2.2.
  
 3. PROVIDE MANUAL D, FBC 2010 ENERGY CONSERVATION
 403.2.5.
  
 4. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471.
  
 5. PROVIDE DUCT SIZES: RIGID DUCT FROM AHU, DUCT TO BR
 2.
  
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732
  
  