Plan Review Details - Permit 13020827
| Plan Review Stops For Permit 13020827 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2013-04-08 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2013-04-08 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2013-04-08 |
Time |
14:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2013-04-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-04-01 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-04-01 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2013-04-01 14:37:06 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | FROM PREVIOUS LISTS: | | | | | | 2. ENHANCE FASTENING TO BE IN ACCORDANCE WITH RAS 117 | | | AND TO BE DONE BY AN ARCHITECT, ENGINEER, OR REGISTERED | | | ROOF CONSULTANT, SEE GENERAL LIMITATION #7 OF THE NOA. | | | | | | 2ND & 3RD REVIEWS - NOT ADDRESSED. | | | | | | A COPY OF RAS 117 WAS PROVIDED. THIS DOES NOT ADDRESS | | | THE COMMENT. THE CALCULATIONS ARE TO BE PREPARED BY AN | | | ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2013-03-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-03-22 |
Time |
18:56 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-03-22 |
Time |
18:56 |
Sent To |
|
|
| Notes |
| 2013-03-22 18:57:08 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. OK | | | | | | 2. ENHANCE FASTENING TO BE IN ACCORDANCE WITH RAS 117 | | | AND TO BE DONE BY AN ARCHITECT, ENGINEER, OR REGISTERED | | | ROOF CONSULTANT, SEE GENERAL LIMITATION #7 OF THE NOA. | | | | | | 2ND REVIEW - NOT ADDRESSED. | | | | | | 3-4 OK | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-02-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-02-28 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-02-28 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2013-02-28 10:50:47 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. SEE SHEET 31 OF THE NOA. THE ASSEMBLY SELECTED | | | REFERS TO GENERAL LIMITATION #9, NO ENHANCED FASTENING | | | ALLOWED. PLEASE SELECT ANOTHER ASSEMBLY WHICH EITHER | | | MEETS MINIMUM DESIGN PRESSURES FOR ZONES 2/3 OR REFERS | | | TO GENERAL LIMITATION #7, SEE SHEET 38. | | | | | | 2. ENHANCE FASTENING TO BE IN ACCORDANCE WITH RAS 117 | | | AND TO BE DONE BY AN ARCHITECT, ENGINEER, OR REGISTERED | | | ROOF CONSULTANT, SEE GENERAL LIMITATION #7 OF THE NOA. | | | | | | 3. INDICATE METHOD OF ATTACHMENT FOR THE TILE, FBC R | | | 301. IF AN ADHESIVE IS PROPOSED, PROVIDE PRODUCT | | | APPROVAL. | | | | | | 4. PROVIDE A COPY OF A VERIFIABLE CONTRACT FOR THIS | | | JOB, FBC 109. | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-04-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-04-01 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-03-28 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2013-03-29 09:23:37 | SENT TO SAMANTHA'S DESK FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-03-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-03-22 |
Time |
18:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-03-22 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2013-03-22 09:57:31 | GAVE TO SAMANTHA |
|
|
|