Plan Review Details - Permit 13020827
Plan Review Stops For Permit 13020827
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-04-08 Cont ID  
Sent By lmartine Date 2013-04-08 Time 14:58 Rev Time 0.00
Received By lmartine Date 2013-04-08 Time 14:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-04-01 Cont ID  
Sent By shill Date 2013-04-01 Time 14:35 Rev Time 0.00
Received By shill Date 2013-04-01 Time 14:35 Sent To  
Notes
2013-04-01 14:37:06****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LISTS:
  
 2. ENHANCE FASTENING TO BE IN ACCORDANCE WITH RAS 117
 AND TO BE DONE BY AN ARCHITECT, ENGINEER, OR REGISTERED
 ROOF CONSULTANT, SEE GENERAL LIMITATION #7 OF THE NOA.
  
 2ND & 3RD REVIEWS - NOT ADDRESSED.
  
 A COPY OF RAS 117 WAS PROVIDED. THIS DOES NOT ADDRESS
 THE COMMENT. THE CALCULATIONS ARE TO BE PREPARED BY AN
 ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-03-22 Cont ID  
Sent By shill Date 2013-03-22 Time 18:56 Rev Time 0.00
Received By shill Date 2013-03-22 Time 18:56 Sent To  
Notes
2013-03-22 18:57:08****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. OK
  
 2. ENHANCE FASTENING TO BE IN ACCORDANCE WITH RAS 117
 AND TO BE DONE BY AN ARCHITECT, ENGINEER, OR REGISTERED
 ROOF CONSULTANT, SEE GENERAL LIMITATION #7 OF THE NOA.
  
 2ND REVIEW - NOT ADDRESSED.
  
 3-4 OK
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-28 Cont ID  
Sent By shill Date 2013-02-28 Time 10:47 Rev Time 0.00
Received By shill Date 2013-02-28 Time 10:47 Sent To  
Notes
2013-02-28 10:50:47****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. SEE SHEET 31 OF THE NOA. THE ASSEMBLY SELECTED
 REFERS TO GENERAL LIMITATION #9, NO ENHANCED FASTENING
 ALLOWED. PLEASE SELECT ANOTHER ASSEMBLY WHICH EITHER
 MEETS MINIMUM DESIGN PRESSURES FOR ZONES 2/3 OR REFERS
 TO GENERAL LIMITATION #7, SEE SHEET 38.
  
 2. ENHANCE FASTENING TO BE IN ACCORDANCE WITH RAS 117
 AND TO BE DONE BY AN ARCHITECT, ENGINEER, OR REGISTERED
 ROOF CONSULTANT, SEE GENERAL LIMITATION #7 OF THE NOA.
  
 3. INDICATE METHOD OF ATTACHMENT FOR THE TILE, FBC R
 301. IF AN ADHESIVE IS PROPOSED, PROVIDE PRODUCT
 APPROVAL.
  
 4. PROVIDE A COPY OF A VERIFIABLE CONTRACT FOR THIS
 JOB, FBC 109.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-04-01 Cont ID  
Sent By shill Date 2013-04-01 Time 14:37 Rev Time 0.00
Received By shill Date 2013-03-28 Time 09:23 Sent To  
Notes
2013-03-29 09:23:37SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-22 Cont ID  
Sent By shill Date 2013-03-22 Time 18:57 Rev Time 0.00
Received By shill Date 2013-03-22 Time 09:43 Sent To  
Notes
2013-03-22 09:57:31GAVE TO SAMANTHA