| 2013-02-28 14:37:58 | BUILDING PLAN REVIEW |
| | PERMIT: 13020795 |
| | ADD: 143 S. SEQEUOIA DR. |
| | CONT: OWNER/BUILDER |
| | MARILYN & WINSTON MCARTHUR |
| | TEL: (561)471-3173 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE- BUILDING. |
| | |
| | BUILDING PROVISO: SLOPE NOT PROVIDED. |
| | 2010 FBC-B R905.2 ASPHALT SHINGLES. |
| | |
| | R905.2.2 SLOPE. |
| | ASPHALT SHINGLES SHALL ONLY BE USED ON ROOF SLOPES OF |
| | TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) OR |
| | GREATER. FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 |
| | UNITS HORIZONTAL (2:12) UP TO FOUR UNITS VERTICAL IN 12 |
| | UNITS HORIZONTAL (4:12), TWO LAYERS OF UNDERLAYMENT |
| | COMPLYING WITH ASTM D 226, TYPE I OR TYPE II, ASTM D |
| | 4869, TYPE I OR TYPE II OR ASTM D 6757 IS REQUIRED IN |
| | ACCORDANCE WITH SECTION R905.2.7. |
| | |
| | R905.2.7 UNDERLAYMENT APPLICATION. |
| | FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS |
| | HORIZONTAL (17-PERCENT SLOPE), UP TO FOUR UNITS |
| | VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE), TWO |
| | LAYERS OF UNDERLAYMENT COMPLYING WITH ASTM D 226 TYPE I |
| | OR TYPE II, ASTM D 4869 TYPE I OR TYPE II, OR ASTM D |
| | 6757 SHALL BE APPLIED IN THE FOLLOWING MANNER: |
| | 1. APPLY A MINIMUM 19-INCH-WIDE (483 MM) STRIP OF |
| | UNDERLAYMENT FELT PARALLEL WITH AND STARTING AT THE |
| | EAVES. |
| | 2. STARTING AT THE EAVE, APPLY 36-INCH-WIDE (914 MM) |
| | SHEETS OF UNDERLAYMENT OVERLAPPING SUCCESSIVE SHEETS 19 |
| | INCHES (483 MM). DISTORTIONS IN THE UNDERLAYMENT SHALL |
| | NOT INTERFERE WITH THE ABILITY OF THE SHINGLES TO SEAL. |
| | 3. END LAPS SHALL BE OFFSET BY 6 FEET (1829 MM). |
| | 4. CORROSION RESISTANT FASTENERS ARE TO BE APPLIED |
| | ALONG THE OVERLAP AT A MAXIMUM SPACING OF 36 INCHES |
| | (914 MM) ON CENTER. |
| | FOR ROOF SLOPES OF FOUR UNITS VERTICAL IN 12 UNITS |
| | HORIZONTAL (33-PERCENT SLOPE) OR GREATER, ONE LAYER OF |
| | UNDERLAYMENT COMPLYING WITH ASTM D 226 TYPE I OR TYPE |
| | II, ASTM D 4869 TYPE I OR TYPE II, OR ASTM D 6757 SHALL |
| | BE APPLIED IN THE FOLLOWING MANNER: |
| | |
| | 1. UNDERLAYMENT SHALL BE APPLIED SHINGLE FASHION, |
| | PARALLEL TO AND STARTING FROM THE EAVE AND LAPPED 2 |
| | INCHES (51 MM). |
| | 2. END LAPS SHALL BE OFFSET BY 6 FEET (1829 MM). |
| | 3. CORROSION RESISTANT FASTENERS ARE TO BE APPLIED |
| | ALONG THE OVERLAP AT A MAXIMUM SPACING OF 36 INCHES |
| | (914 MM) ON CENTER. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |