Plan Review Details - Permit 13020690
Plan Review Stops For Permit 13020690
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-03-07 Cont ID  
Sent By shill Date 2013-03-07 Time 17:46 Rev Time 0.00
Received By shill Date 2013-03-07 Time 17:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-03-04 Cont ID  
Sent By shill Date 2013-03-04 Time 11:13 Rev Time 0.00
Received By shill Date 2013-03-04 Time 11:13 Sent To  
Notes
2013-03-04 11:30:57****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. SEE THE INSTALLATION SCHEDULE:
  
 BLOCK SUBSTRATE (BOTTOM) TO USETHE SPACING FOR
 "SUBSTRATE BLOCK" ON SHEET 4 OF THE PRODUCT APPROVAL.
 9" DOES NOT COMPLY. PLEASE REVISE ANCHOR SPACING.
  
 COMMENT FROM PREVIOUS LIST:
  
 2. REVISE FLOOR PLAN TO SHOW ROOM DESIGNATION FOR THE
 EMERGENCY MEANS OF ESCAPE, FBC R310.4. THIS CANNOT BE
 LOCATED IN A ROOM WHICH CAN BE LOCKED.
  
 2ND REVIEW, ROOM DESIGNATIONS NOT PROVIDED. THE FRONT
 DOOR WAS HIGHLIGHTED; IS THIS AN INSWING OR OUTSWING
 DOOR? REVISE PLAN.
  
 IF THIS IS AN OUTSWING DOOR, THIS CANNOT OPERATE WITH
 THE SHUTTERS IN PLACE. THE TWO OTHER OPENINSG (9 AND
 10) DO NOT INCLUDE ROOM DESIGNATIONS. A TERRACE IS
 SHOWN; THIS APPEARS TO BE A PORCH, NOT A ROOM. IT IS
 NOT CLEAR WHETHER THE TERRACE IS LOCATED ADJACENT TO A
 ROOM WHICH CAN BE LOCKED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-26 Cont ID  
Sent By shill Date 2013-02-26 Time 14:38 Rev Time 0.00
Received By shill Date 2013-02-26 Time 14:38 Sent To  
Notes
2013-02-26 14:39:07****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 2. REVISE FLOOR PLAN TO SHOW ROOM DESIGNATION FOR THE
 EMERGENCY MEANS OF ESCAPE, FBC R310.4. THIS CANNOT BE
 LOCATED IN A ROOM WHICH CAN BE LOCKED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-03-07 Cont ID  
Sent By shill Date 2013-03-07 Time 17:46 Rev Time 0.00
Received By shill Date 2013-03-07 Time 14:36 Sent To  
Notes
2013-03-07 14:38:23GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-03-04 Cont ID  
Sent By shill Date 2013-03-04 Time 11:13 Rev Time 0.00
Received By shill Date 2013-03-04 Time 11:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-26 Cont ID  
Sent By shill Date 2013-02-26 Time 14:39 Rev Time 0.00
Received By shill Date 2013-02-25 Time 16:29 Sent To  
Notes
2013-02-25 16:40:56SENT TO MISC 1 BOX.