| Plan Review Stops For Permit 13020619 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2013-03-04 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2013-03-04 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2013-03-04 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2013-03-04 11:05:25 | 13020619 | | | 952 32ND STREET | | | RESIDENTIAL WIRING | | | | | | PROVISO | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|
|