| Plan Review Stops For Permit 13020518 |
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2013-06-25 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
2013-06-25 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2013-06-25 |
Time |
|
Sent To |
I |
|
| Notes |
| 2013-06-25 11:33:07 | SOURCE WATER IS AVAILABLE AND PERMITTED THRU ESD |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2013-02-25 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2013-02-25 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2013-02-25 |
Time |
|
Sent To |
M |
|
| Notes |
| 2013-02-25 15:31:05 | PLEASE PROVIDE PLAN SHOWING SOURCE FOR FIRELINE. | | | IT IS UNDERSTOOD THAT WATER STUB AND WATER SOURCE COULD | | | BE ALREADY EXISTING HOWEVER IT MUST BE INCLUDED TO | | | ALLOW THE PERMIT TO BE ISSUED | | | AND INSPECTED AS A WHOLE. | | | PLEASE HAVE CONSTRUCTION SERVICES DEPT. DEDUCT WATER | | | TAP CONSTRUCTION IF THE PRIOR WORK WAS DONE UNDER AN | | | ENGINEERING PERMIT. | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2013-07-27 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2013-07-27 |
Time |
12:44 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2013-07-27 |
Time |
11:41 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2013-06-20 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2013-06-20 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2013-06-20 |
Time |
13:56 |
Sent To |
ENG |
|
| Notes |
| 2013-06-20 14:29:28 | 6801 NORTH JOG ROAD | | | PERMIT #13020518 | | | (SEE ALSO PERMIT #13020494) | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FAIL COMMENTS: | | | REPEAT COMMENT: THE PERMIT APPLICATION ADDRESS (6801 N | | | JOG ROAD) DOES NOT MATCH THE CORRECT ADDRESS (6610 N | | | JOG ROAD) INDICATED ON THE PLANS. | | | | | | REPEAT COMMENT: THE PLANS INDICATE THE DRAWING SCALE TO | | | BE 1/8"=1'-0"; HOWEVER, THE ACTUAL SCALE APPEARS TO BE | | | 3/16"=1'-0". PLANS STILL INDICATE 1/8"=1'-0. | | | | | | REPEAT COMMENT: THE PLANS INCORRECTLY INDICATE TWO | | | HYDRAULIC NODES AS "A3" AND THESE FLOWING NODES CANNOT | | | BE LOCATED IN THE HYDRAULIC CALCULATIONS. ALSO THE | | | HYDRAULIC CALCULATIONS INDICATE NODE 4 TO BE A FLOWING | | | NODE WHICH IS INACCURATE. NODES B9, B10 AND 11 ARE NOT | | | SHOWN ON THE PLANS. | | | | | | NEW COMMENT: THE FIRE DEPARTMENT CONNECTION SHOULD NO | | | LONGER BE SHOWN ADJACENT TO THE BACKFLOW PREVENTER AS | | | THE UNDERGROUND CONTRACTOR HAS RELOCATED THIS DEVICE. | | | | | | | | | FIELD NOTES: | | | FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED | | | SUPERVISING STATION IN ACCORDANCE WITH NFPA 72. | | | | | | PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE | | | DEPARTMENT CONNECTION. | | | | | | IN ADDITION TO TAMPER SWITCHES, PROVIDE CHAIN WITH LOCK | | | FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN | | | POSITION. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2013-02-23 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2013-02-23 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2013-02-23 |
Time |
12:43 |
Sent To |
ENG |
|
| Notes |
| 2013-02-23 12:51:47 | 6801 (6610) NORTH JOG ROAD | | | PERMIT #13020518 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE PERMIT APPLICATION ADDRESS DOES NOT MATCH THE | | | CORRECT ADDRESS INDICATED ON THE PLANS. | | | | | | THE PLANS INDICATE THE DRAWING SCALE TO BE 1/8"=1'-0"; | | | HOWEVER, THE ACTUAL SCALE APPEARS TO BE 3/16"=1'-0". | | | | | | THE PLANS INCORRECTLY INDICATE TWO HYDRAULIC NODES AS | | | "A3." ALSO, THESE FLOWING NODES CANNOT BE LOCATED IN | | | THE HYDRAULIC CALCULATIONS. | | | | | | PROVIDE A RISER DETAIL(S). | | | | | | FIRE DEPARTMENT CONNECTION SHALL BE LOCATED WITHIN 150 | | | FEET OF A FIRE HYDRANT. | | | | | | PLANS DO NOT INDICATE WHAT PIPING MATERIAL WILL BE USED | | | FOR THE UNDERGROUND INSTALLATION. | | | | | | PLANS DO NOT INDICATE THE PIPING MATERIAL OF THE | | | EXISTING 4" WATER MAIN. | | | | | | THE PLANS ARE NOT CLEAR HOW THE PIPING IS BEING ROUTED | | | FROM THE "SUB CONTRACTOR" TRAILER TO THE "MATERIAL | | | RECEIVING" TRAILER. | | | | | | SUBMIT PRODUCT DATA FOR THE CPVC PIPING AND BACKFLOW | | | PREVENTER TO BE INSTALLED. PROVIDE DOCUMENTATION | | | SUPPORTING THE USE OF EXPOSED CPVC PIPING. | | | | | | FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED | | | SUPERVISING STATION IN ACCORDANCE WITH NFPA 72. | | | | | | PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE | | | DEPARTMENT CONNECTION. | | | | | | IN ADDITION TO TAMPER SWITCHES, PROVIDE CHAIN WITH LOCK | | | FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN | | | POSITION. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2013-07-29 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-07-29 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-07-27 |
Time |
12:44 |
Sent To |
|
|
| Notes |
| 2013-07-20 14:32:40 | INCOMING SENT TO FIRE BOX . JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-06-25 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-06-25 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-06-07 |
Time |
08:31 |
Sent To |
|
|
| Notes |
| 2013-06-25 13:29:18 | TO MECHANICAL | | 2013-06-07 08:31:56 | TO ENGINEERING | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-03-04 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-03-04 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-02-19 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2013-02-19 16:41:08 | INCOMING SENT TO FIRE BOX. JW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2013-07-29 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-07-29 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-07-29 |
Time |
09:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2013-06-25 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-06-25 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-06-25 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2013-06-25 15:49:03 | PLANS DENIED | | | ADDRESS ON PLANS IS 6610 N. JOG RD. | | | ADDRESS ON APPLICATION IS 6801 N JOG RD. | | | ADDRESS DO NOT MATCH .PER SECTION 107 | | | FBC 2010 . | | | PLAN REVIEW BY HAROLD MOSER. | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2013-03-04 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-03-04 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-03-04 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2013-03-04 14:42:35 | PLANS DENIED | | | 1) ADDRESS ON APPLICATION AND PLANS DO NOT MATCH. | | | PER SECTION 107 FBC. 2010 | | | 2) NO 2X2X2 TEE ON PLANS. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|
|