Plan Review Details - Permit 13020494
Plan Review Stops For Permit 13020494
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2013-06-25 Cont ID  
Sent By Mgonzale Date 2013-06-25 Time   Rev Time 1.00
Received By mgonzale Date 2013-06-25 Time   Sent To I
Notes
2013-06-25 11:35:12NO OBJECTION - SOURCE WATER WAS PERMITTED THRU ESD

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2013-02-25 Cont ID  
Sent By mgonzale Date 2013-02-25 Time   Rev Time 0.25
Received By mgonzale Date 2013-02-25 Time   Sent To M
Notes
2013-02-25 15:29:59PLEASE PROVIDE PLAN SHOWING SOURCE FOR FIRELINE.
 IT IS UNDERSTOOD THAT WATER STUB AND WATER SOURCE COULD
 BE ALREADY EXISTING HOWEVER IT MUST BE INCLUDED TO
 ALLOW THE PERMIT TO BE ISSUED
 AND INSPECTED AS A WHOLE.
 PLEASE HAVE CONSTRUCTION SERVICES DEPT. DEDUCT WATER
 TAP CONSTRUCTION IF THE PRIOR WORK WAS DONE UNDER AN
 ENGINEERING PERMIT.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-06-20 Cont ID  
Sent By wjolin Date 2013-06-20 Time 14:51 Rev Time 0.00
Received By wjolin Date 2013-06-20 Time 13:53 Sent To ENG
Notes
2013-06-20 13:55:116801 (6610) NORTH JOG ROAD
 PERMIT #13020494
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 IN ADDITION TO TAMPER SWITCHES, PROVIDE CHAIN WITH LOCK
 FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-02-23 Cont ID  
Sent By wjolin Date 2013-02-23 Time 12:26 Rev Time 0.00
Received By wjolin Date 2013-02-23 Time 11:40 Sent To ENG
Notes
2013-02-23 12:26:426801 (6610) NORTH JOG ROAD
 PERMIT #13020494
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION ADDRESS DOES NOT MATCH THE
 CORRECT ADDRESS INDICATED ON THE PLANS.
  
 PROVIDE A RISER DETAIL(S).
  
 FIRE DEPARTMENT CONNECTION SHALL BE LOCATED WITHIN 150
 FEET OF A FIRE HYDRANT.
  
 PLANS DO NOT INDICATE WHAT PIPING MATERIAL WILL BE USED
 FOR THE UNDERGROUND INSTALLATION.
  
 PLANS DO NOT INDICATE THE PIPING MATERIAL OF THE
 EXISTING 4" WATER MAIN.
  
 THE PLANS ARE NOT CLEAR HOW THE PIPING IS BEING ROUTED
 FROM THE "SUB CONTRACTOR" TRAILER TO THE "MATERIAL
 RECEIVING" TRAILER.
  
 SUBMIT PRODUCT DATA FOR THE CPVC PIPING AND BACKFLOW
 PREVENTER TO BE INSTALLED. PROVIDE DOCUMENTATION
 SUPPORTING THE USE OF EXPOSED CPVC PIPING.
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 IN ADDITION TO TAMPER SWITCHES, PROVIDE CHAIN WITH LOCK
 FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-25 Cont ID  
Sent By hmoser Date 2013-06-25 Time 14:14 Rev Time 0.00
Received By hmoser Date 2013-06-20 Time 13:53 Sent To  
Notes
2013-06-25 13:16:58TO MECHANICAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-04 Cont ID  
Sent By hmoser Date 2013-03-04 Time 11:07 Rev Time 0.00
Received By hmoser Date 2013-02-19 Time 16:41 Sent To  
Notes
2013-02-19 16:41:52INCOMING SENT TO FIRE BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-06-25 Cont ID  
Sent By hmoser Date 2013-06-25 Time 14:14 Rev Time 0.00
Received By hmoser Date 2013-06-25 Time 14:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-03-04 Cont ID  
Sent By hmoser Date 2013-03-04 Time 11:07 Rev Time 0.00
Received By hmoser Date 2013-03-04 Time 10:44 Sent To  
Notes
2013-03-04 11:07:14PLANS DENIED
 1) ADDRESS ON THE APPLICATION AND PLANS DO NOT MATCH.
 PER SECTION 107 FBC.
 2) APPLICATION HAS A 2X2X2 TEE CAN NOT FIND THE TEE ON
 THE PLANS .
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]