| 2013-02-27 18:38:41 | REVISION BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- MEANS OF EGRESS IS AFFECTED WHEN REPLACING MASTER |
| | BEDROOM WINDOW. SPECIFY EXISTING WINDOW TYPE AND SIZE |
| | TO BE REPLACED AND PROPOSED WINDOW TYPE AND SIZE TO BE |
| | INSTALLED TO VERIFY COMPLIANCE WITH SEC. 604.1 OF 2010 |
| | FBC-EXISTING BUILDING. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) STRUCTURAL CONNECTOR "HGHAN" SPECIFIED ON NEW COLUMN |
| | TRIM DETAIL ON SHEET A1. |
| | |
| | B) SIMPSON STRUCTURAL CONNECTORS PRODUCT APPROVALS |
| | SUBMITTED. PLEASE PROVIDE FLORIDA PRODUCT APPROVAL |
| | COVER AND ONLY THE PAGE SHOWING THE CONNECTORS THAT |
| | WERE SPECIFIED BY THE ENGINEER. UNABLE TO FIND SOME |
| | CONNECTORS ON PRODUCT APPROVALS SUBMITTED. SEC. 107.2.1 |
| | CITY AMENDMENTS TO FBC. |
| | |
| | 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY MENDMENTS TO FBC. |
| | ***NOTE: A GENERAL STATEMENT SAYING THAT "DESIGNER OF |
| | RECORD ROBERT CURIE HAS REVIEWED + APPROVED ALL PRODUCT |
| | APPROVALS ON THESE PLANS" IS NOT ACCEPTABLE. DESIGNER |
| | OF RECORD MAY USE A REVIEW AND APPROVED STAMP ON EACH |
| | PRODUCT APPROVAL OR A LETTER FROM THE DESIGNER OF |
| | RECORD LISTING EACH SPECIFIC PRODUCT APPROVAL NUMBER |
| | MAY BE PROVIDED. |
| | |
| | 4- DESIGNER OF RECORD TO SPECIFY THE CALCULATED DESIGN |
| | PRESSURES FOR DOORS AND WINDOWS TO BE REPLACED TO |
| | VERIFY COMPLIANCE WITH THE PRODUCT APPROVALS SUBMITTED. |
| | NOTE: ACCORDING TO SEC. R301.2.1.4.3 OF 2010 |
| | FBC-RESIDENTIAL THIS BUILDING IS LOCATED ON EXPOSURE |
| | "D". |
| | |
| | 5- NEED TO SPECIFY VENTILATION FOR NEW BATHROOMS AS |
| | REQUIRED BY SEC. R303.3. NOTE: THAT ONE BATHROOM HAS NO |
| | WINDOWS AND THE OTHER ONE ONE WINDOW WAS BLOCKED. |
| | |
| | 6- SPECIFY SIZE OF NEW ATTIC ACCESS. SEC. R807.1. |
| | |
| | ***REMAINDER*** |
| | NOTICE OF COMMENCEMENT IS REQUIRED IN ORDER TO CALL FOR |
| | INSPECTIONS. WE HAVE NO NOTICE OF COMMENCEMENT ON FILE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |