Plan Review Details - Permit 13020330
Plan Review Stops For Permit 13020330
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-04-16 Cont ID  
Sent By jgomez Date 2013-04-16 Time 14:09 Rev Time 0.00
Received By jgomez Date 2013-04-16 Time 14:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-19 Cont ID  
Sent By jgomez Date 2013-03-18 Time 16:54 Rev Time 0.00
Received By jgomez Date 2013-03-18 Time 15:18 Sent To  
Notes
2013-03-19 11:12:21RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- SPECIFY THE CALCULATED DESIGN PRESSURES FOR ALL NEW
 WINDOWS AS REQUIRED BY SEC. R301.1 OF FBC-RESIDENTIAL.
 ***NOTE: ACCORDING TO SEC. R301.2.1.4.3 THIS BUILDING
 IS LOCATED IN EXPOSURE "C". TAKE THIS INTO
 CONSIDERATION WHEN DOING THE CALCULATIONS.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR ALL STRUCTURAL FASTENERS SPECIFIED ON
 THE FRAMING DETAILS REQUESTED ON ITEM #2 ABOVE.
 ***NOTE; PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 3- SPECIFY ALL HURRICANE CONNECTORS AT THE ENDS OF THE
 EACH STRUCTURAL MEMBER IN WINDOW OPENING DETAIL,
 SECTION A AND SECTION B DETAILS TO VERIFY COMPLIANCE
 WITH THE WIND LOADS OF SEC. R301.2.1.4.3.
  
 4- DESIGN OF RECORD TO REVIEW AND APPROVE IN WRITING
 THE WINDOW PRODUCT APPROVALS AND THE STRUCTURAL
 CONNECTORS SPECIFIED ON FRAMING DETAILS AS REQUIRED BY
 SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 5- PROVIDE MANUFACTURER'S CUT SHEETS FOR THE BEDROOM
 EGRESS WINDOW SIZE SPECIFIED ON PLANS TO VERIFY
 COMPLIANCE WITH SEC. R310. NOA 06-0608.03 SUBMITTED
 DON'T SHOW SIZES AND SHOWS SINGLE HUNG WINDOW WITH THE
 LOWER SASH SMALLER THAN THE TOP. NEED TO VERIFY EGRESS
 CLEAR OPENING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2014-07-17 Cont ID  
Sent By dhayes Date   Time 16:52 Rev Time 0.00
Received By dhayes Date   Time 16:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-03-08 Cont ID  
Sent By rlecky Date 2013-03-08 Time 12:37 Rev Time 0.00
Received By rlecky Date 2013-03-08 Time 12:30 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2013-02-13 Cont ID  
Sent By fmittner Date 2013-02-13 Time 11:54 Rev Time 0.00
Received By fmittner Date 2013-02-13 Time 11:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-04-17 Cont ID  
Sent By shill Date 2013-04-17 Time 10:19 Rev Time 0.00
Received By shill Date 2013-04-12 Time 15:04 Sent To  
Notes
2013-04-12 15:04:58SENT TO JULIO'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-18 Cont ID  
Sent By jgomez Date 2013-03-18 Time 16:54 Rev Time 0.00
Received By jgomez Date 2013-02-13 Time 16:33 Sent To  
Notes
2013-03-04 16:34:17SENT TO R10 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-04-17 Cont ID  
Sent By hmoser Date 2013-04-17 Time 09:58 Rev Time 0.00
Received By hmoser Date 2013-04-17 Time 09:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-03-19 Cont ID  
Sent By hmoser Date 2013-03-15 Time 15:12 Rev Time 0.00
Received By hmoser Date 2013-03-15 Time 15:03 Sent To  
Notes
2013-03-19 10:08:20PLANS DENIED
 PROVIDE A FULL SET OF ENERGY CALCULATIONS
 WITH THE PLANS PER SECTION M 104.3 SIZING
 2010 FBC RESIDENTIAL CODE
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-04-16 Cont ID  
Sent By jgomez Date 2013-04-16 Time 15:16 Rev Time 0.00
Received By jgomez Date 2013-04-16 Time 15:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-03-19 Cont ID  
Sent By jgomez Date 2013-03-18 Time 16:54 Rev Time 0.00
Received By jgomez Date 2013-03-18 Time 16:13 Sent To  
Notes
2013-03-19 11:29:01RESIDENTIAL (R3) ALTERATION PLUMBING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROPOSED LOCATION OF NEW WATER HEATER IS NOT
 ALLOWED. SEC. P2801.3 OF 2010 FBC-RESIDENTIAL. PROPOSED
 LOCATION DOESN'T ALLOW FOR INSPECTION SERVICE, REPAIR
 AND REPLACEMENT. SEE SEC. M1305. REVISE PLANS AS
 REQUIRED.
  
 2- REVISE PLUMBING RISER DIAGRAM. EACH WET-VENTED
 FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO THE
 HORIZONTAL WET VENT AS REQUIRED BY SEC. P3108.1 OF 2010
 FBC-RESIDENTIAL. BATHROOM TUB DRAIN NEEDS TO CONNECT
 DIRECTLY TO THE HORIZONTAL WET VENT.
  
 IF YOU HAVE ANY QUESTION, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 1 Status P Date 2013-02-13 Cont ID  
Sent By fmittner Date 2013-02-13 Time 11:54 Rev Time 0.00
Received By fmittner Date 2013-02-13 Time 11:54 Sent To  
Notes
***NONE***