Plan Review Details - Permit 13020312
Plan Review Stops For Permit 13020312
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-03-18 Cont ID  
Sent By shill Date 2013-03-18 Time 08:37 Rev Time 0.00
Received By shill Date 2013-03-18 Time 08:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-25 Cont ID  
Sent By shill Date 2013-02-25 Time 15:53 Rev Time 0.00
Received By shill Date 2013-02-25 Time 15:53 Sent To FIRE
Notes
2013-02-25 15:53:59****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FOR THE FLOORING UNDERLAYMENT, PROVIDE INFORMATION
 WHICH SHOWS COMPLIANCE WITH THE FOLLOWING:
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-03-15 Cont ID  
Sent By ddaniels Date 2013-03-15 Time 12:01 Rev Time 0.00
Received By ddaniels Date 2013-03-15 Time 11:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-02-26 Cont ID  
Sent By ddaniels Date 2013-02-26 Time 15:42 Rev Time 0.00
Received By ddaniels Date 2013-02-26 Time 15:42 Sent To  
Notes
2013-02-26 15:49:5002/26/2013 PLANS REVIEWED BY FIRE ***DENIED***
  
 1. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 2. ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
  
 3. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
  
 DERRICK L. DANIELS, BATTALION CHIEF / FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 804-4909
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-03-18 Cont ID  
Sent By shill Date 2013-03-18 Time 08:37 Rev Time 0.00
Received By shill Date 2013-03-14 Time 09:08 Sent To  
Notes
2013-03-14 09:09:09TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-06 Cont ID  
Sent By shill Date 2013-03-06 Time 13:57 Rev Time 0.00
Received By shill Date 2013-02-12 Time 16:21 Sent To  
Notes
2013-02-12 16:22:09TO PLUMBING

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-02-13 Cont ID  
Sent By lwagner Date 2013-02-13 Time 15:22 Rev Time 0.00
Received By lwagner Date 2013-02-13 Time 14:40 Sent To B
Notes
***NONE***