Plan Review Details - Permit 13020274
Plan Review Stops For Permit 13020274
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-02-12 Cont ID  
Sent By wjolin Date 2013-02-12 Time 12:14 Rev Time 0.00
Received By wjolin Date 2013-02-12 Time 11:07 Sent To M
Notes
2013-02-12 12:14:35428 10TH STREET
 PERMIT #13020274
 MASTER #12060308
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 PROVIDE A LOCAL WATERFLOW ALARM TO ALERT BUILDING
 OCCUPANTS.
  
 INDICATE THE PIPE TYPE TO BE USED FOR THE UNDERGROUND
 INSTALLATION.
  
 SPRINKLER DESIGN SHALL CONFORM TO THE 2007 EDITION OF
 NFPA 13R IN LIEU OF THE 2002 EDITION INDICATED ON THE
 PLANS.
  
 ADD THE DOMESTIC WATER DEMAND TO THE OVERALL SYSTEM
 DEMAND SHOWN IN THE HYDRAULIC CALCULATIONS.
  
 SUBMIT PRODUCT DATA FOR BACKFLOW PREVENTER, CPVC PIPE,
 AND SPRINKLERS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-19 Cont ID  
Sent By hmoser Date 2013-02-19 Time 11:20 Rev Time 0.00
Received By hmoser Date 2013-02-12 Time 09:23 Sent To  
Notes
2013-02-12 09:23:51TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-02-19 Cont ID  
Sent By hmoser Date 2013-02-19 Time 11:20 Rev Time 0.00
Received By hmoser Date 2013-02-19 Time 11:09 Sent To  
Notes
***NONE***