Plan Review Details - Permit 13020244
Plan Review Stops For Permit 13020244
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-04-25 Cont ID  
Sent By rmcdouga Date 2013-04-25 Time 10:45 Rev Time 0.00
Received By rmcdouga Date 2013-04-24 Time 13:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-10 Cont ID  
Sent By rmcdouga Date 2013-03-10 Time 17:48 Rev Time 0.00
Received By rmcdouga Date 2013-03-07 Time 14:30 Sent To  
Notes
2013-03-10 17:48:352010 FBC
  
 DENIED BY BUILDING
  
 1) ON SHEET 7 OF 9 THE WALL SECTIONS SHOW SPRAY FOAM
 INSULATION AND SPECIFY SOFFIT VENTS AND THE ENERGY
 CALCULATIONS SPECIFY AN UNVENTED ATTIC. PLEASE CLARIFY.
 CITY AMENDMENTS 107.2.1
  
 2) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE
 SPRAY FOAM INSULATION THAT WILL BE INSTALLED. FBCR 316
  
 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS, AS REQUIRED
 BY DCA RULE 9N-3, FOR THE STRUCTURAL MULLIONS, FIXED
 GLASS WINDOWS, AND THE WOOD FRONT DOOR ( A CUSTOM DOOR
 REQUIRES SITE SPECIFIC ENGINEERING).
  
 4) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 SLIDING GLASS DOOR, REQUIRES THE DOOR TO HAVE IMPACT
 PROTECTION. SUBMIT TWO COPIES OF THE PRODUCT APPROVAL
 FOR THE IMPACT PROTECTION SYSTEM THAT WILL BE INSTALLED
 FOR THIS DOOR. PROVIDE AN INSTALLATION SCHEDULE
 SPECIFYING THE TYPE OF MOUNT, THE FASTENER TYPE,
 FASTENER SPACING, PANEL SPAN, GLASS SEPARATION AND ANY
 OTHER INFORMATION FROM THE PRODUCT APPROVAL TO
 DETERMINE THAT THE INSTALLATION WILL BE CODE COMPLIANT.
 FBCR301.2.1.2
  
 5) THE PRODUCT APPROVAL SUBMITTED FOR THE SINGLE HUNG
 WINDOWS HAS MAXIMUM DESIGN PRESSURES OF + 60, - 60 PSF.
 THE SINGLE HUNG WINDOW IN THE SECOND FLOOR BATHROOM HAS
 A NEGATIVE PRESSURE OF - 69.6 PSF WHICH IS MORE THAN
 THE PROPOSED WINDOW IS RATED FOR. PLEASE PROVIDE A
 PRODUCT APPROVAL THAT MEETS THE WINDLOAD REQUIREMENTS
 FOR THIS WINDOW AS REQUIRED BY FBCR 301.2.1.
  
 6) ALL OF THE ADDITIONAL PRODUCT APPROVALS THAT
 SUBMITTED ARE REQUIRED TO BE REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD. CITY AMENDMENTS 107.3.4.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-04-24 Cont ID  
Sent By rmcdouga Date 2013-04-24 Time 13:56 Rev Time 0.00
Received By rmcdouga Date 2013-04-24 Time 13:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-03-07 Cont ID  
Sent By rmcdouga Date 2013-03-07 Time 13:40 Rev Time 0.00
Received By rmcdouga Date 2013-03-07 Time 13:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-04-29 Cont ID  
Sent By mdekle Date 2013-04-29 Time   Rev Time 0.00
Received By mdekle Date 2013-04-04 Time 10:24 Sent To  
Notes
2013-04-05 10:25:17SENT TO R1 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-03-10 Cont ID  
Sent By rmcdouga Date 2013-03-10 Time 17:48 Rev Time 0.00
Received By rmcdouga Date 2013-02-12 Time 10:56 Sent To  
Notes
2013-02-12 10:56:22R21

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2013-04-24 Cont ID  
Sent By rmcdouga Date 2013-04-24 Time 13:58 Rev Time 0.00
Received By rmcdouga Date 2013-04-24 Time 13:58 Sent To  
Notes
2013-04-24 13:59:04MU-2013-5291

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-03-07 Cont ID  
Sent By rmcdouga Date 2013-03-07 Time 09:23 Rev Time 0.00
Received By rmcdouga Date 2013-03-07 Time 09:23 Sent To  
Notes
2013-03-07 09:24:14AN IMPACT FEE REVIEW BY PALM BEACH COUNTY WILL BE
 REQUIRED.

Review Stop L LANDSCAPING
Rev No 1 Status N Date 2013-04-29 Cont ID  
Sent By mdekle Date 2013-04-29 Time   Rev Time 0.00
Received By mdekle Date 2013-04-29 Time   Sent To  
Notes
2013-04-29 16:18:17SEPERATE LANDSCAPING PERMIT REQURIED. SEE ZONING
 COMMENTS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-03-07 Cont ID  
Sent By rmcdouga Date 2013-03-07 Time 14:30 Rev Time 0.00
Received By rmcdouga Date 2013-03-07 Time 11:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-04-24 Cont ID  
Sent By rmcdouga Date 2013-04-24 Time 13:50 Rev Time 0.00
Received By rmcdouga Date 2013-04-24 Time 13:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-03-07 Cont ID  
Sent By rmcdouga Date 2013-03-07 Time 11:55 Rev Time 0.00
Received By rmcdouga Date 2013-03-07 Time 09:24 Sent To  
Notes
2013-03-07 11:57:342010 FBC
  
 1) THE WATER CLOSET ON THE FIRST FLOOR CAN NOT BE
 VENTED BY THE WASTE STACK FROM THE SECOND FLOOR. FBCR
 3109.2
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2013-04-25 Cont ID  
Sent By rmcdouga Date 2013-04-25 Time 10:53 Rev Time 0.00
Received By rmcdouga Date 2013-04-25 Time 10:49 Sent To  
Notes
2013-04-25 10:53:30ROOF - EAGLE FLAT CONCRETE ROOF TILE FL7473-R5 / 3M
 COMPANY FL6332-R3

Review Stop Z ZONING
Rev No 2 Status P Date 2013-04-29 Cont ID  
Sent By mdekle Date 2013-04-29 Time   Rev Time 0.00
Received By mdekle Date 2013-04-29 Time   Sent To  
Notes
2013-04-29 14:36:49ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 4.29.2013
 PERMIT NO.: 13020244
 ADDRESS: 339 E. LAKEWOOD ROAD
 CONTRACTOR/CONTACT: ELOINE & CARY SABOL
 TELEPHONE NO.: 305.951.7500
 SCOPE OF REVIEW: CONSTRUCTION OF NEW SINGLE FAMILY HOME
 ___________________________________________
  
 REVIEW STATUS: PASSED W/PROVISO
 ___________________________________________
 I. THE APPLICANT MUST OBTAIN A SEPARATE PERMIT FOR THE
 FOLLOWING IMPROVEMENTS:
 A. LANDSCAPING
 B. SWIMMING POOL
 C. DRIVEWAY
  
 MURRIAH DEKLE, MPA, PLANNER
 PLANNING & ZONING DIVISION
 EMAIL: [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2013-02-21 Cont ID  
Sent By mdekle Date 2013-02-21 Time   Rev Time  
Received By mdekle Date 2013-02-21 Time   Sent To  
Notes
2013-02-21 16:10:53ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 2.21.2013
 PERMIT NO.: 13020244
 ADDRESS: 339 E. LAKEWOOD ROAD
 CONTRACTOR/CONTACT: ELOINE & CARY SABOL
 TELEPHONE NO.: 305.951.7500
 SCOPE OF REVIEW: CONSTRUCTION OF NEW SINGLE FAMILY HOME
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
 I. THE APPLICANT MUST SUBMIT TWO COPIES OF A LANDSCAPE
 PLAN, DEMONSTRATING COMPLIANCE WITH THE FOLLOWING
 PROVISIONS:
  
 SEC. 94-442. - OPEN SPACE LANDSCAPE REQUIREMENTS.
  
 (A)INTENT. THE INTENT OF THIS SECTION IS TO PROVIDE
 STANDARDS FOR LANDSCAPING OPEN SPACE AREAS WHEN
 REQUIRED BY THIS CHAPTER. LANDSCAPE PLANS, EXCLUDING
 THOSE PREPARED FOR SINGLE-FAMILY DWELLING UNITS, SHALL
 BE PREPARED BY PERSONS AS AUTHORIZED BY F.S. CH. 481,
 PT. II (LANDSCAPE ARCHITECTURE).
  
 (B)GENERAL STANDARDS. ALL OPEN SPACE, AS REQUIRED BY
 THIS CHAPTER, SHALL BE LANDSCAPED AS PROVIDED IN THIS
 SECTION.
  
 (1)LANDSCAPING GENERALLY. ALL OPEN SPACE, EXCLUDING
 VEHICULAR AND PEDESTRIAN CIRCULATION FEATURES AND
 SURFACE PARKING, SHALL BE COVERED WITH GRASS, GROUND
 COVER, SHRUBBERY, OR OTHER SUITABLE PLANT MATERIAL, OR
 MAY HAVE PAVED ACTIVE RECREATION AREAS, PATIOS,
 TERRACES, PEDESTRIAN CIRCULATION AREAS, SWIMMING POOLS,
 WATER FEATURES, AND SIMILAR SITE COMPONENTS
 INCORPORATED IN THE OPEN SPACE DESIGNS.
  
 (2)GENERAL LANDSCAPING STANDARDS FOR SINGLE-FAMILY
 DWELLING UNITS AND ALL OTHER DEVELOPMENTS. GENERAL
 LANDSCAPING STANDARDS FOR SINGLE-FAMILY DWELLING UNITS
 AND ALL OTHER DEVELOPMENTS SHALL BE AS FOLLOWS:
 A.SINGLE-FAMILY DWELLING UNITS. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
  
 II. THE WIDTH OF THE WESTERN PORTION OF THE CIRCULAR
 DRIVEWAY MUST BE REDUCED TO TEN FEET TO ACHIEVE
 COMPLIANCE WITH SECTION 94-482.
  
 III. PLEASE BE ADVISED; THE 'FUTURE SWIMMING POOL' AS
 DEPICTED ON THE SITE PLAN MUST BE PROCESS VIA A
 SEPERATE PERMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AND/OR
 CONSULT THE CITY?S ZONING AND LAND DEVELOPMENT
 REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
 MURRIAH DEKLE, MPA, PLANNER
 PLANNING & ZONING DIVISION
 EMAIL: [email protected]
  
  
  
2013-02-14 14:23:182/14/13