Plan Review Details - Permit 13020224
Plan Review Stops For Permit 13020224
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-05-28 Cont ID  
Sent By jwitmer Date 2013-05-28 Time 07:35 Rev Time 0.00
Received By skennedy Date 2016-05-02 Time 10:19 Sent To  
Notes
2016-05-02 10:19:51PERMIT RE-ISSUED USING 13020224 NUMBER & PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-03-12 Cont ID  
Sent By jwitmer Date 2013-03-12 Time 09:59 Rev Time 0.00
Received By jwitmer Date 2013-03-12 Time 09:06 Sent To  
Notes
2013-03-12 09:59:31BUILDING PLAN REVIEW
 PERMIT: 13020224
 ADD: 429 BELVEDERE RD 1ST & 2ND FLOOR
 CONT: BESSENROTH BUILDERS INC.
 TEL: (561)324-4871
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 12010122 EXPIRED 2ND FL REMODEL
 11080145 EXPIRED WINDOW REPLACEMENT
 09110339 EXPIRED 1ST & 2ND FLOOR REMODEL
 1ST REVIEW
 DATE: MARCH 12/ 2013
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES UNDER THE HEADING
 WORK DESCRIPTION REMODEL 2ND & 1ST FLOOR. PLEASE NOTE
 THE WINDOW PERMIT 11080145 HAS NEVER RECEIVED A FINAL,
 PLEASE PROVIDE PRODUCT APPROVALS FOR THE WINDOWS THAT
 WERE INSTALLED, 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING, FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 2) THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 3) STORM SHUTTERS WILL BE REQUIRED IF WINDOW PRODUCT
 APPROVALS DO NOT INCLUDE LARGE MISSILE IMPACT TESTING.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (31)(E) SHUTTERS
  
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4.
  
 FL BLD CODE 2010 SECTION 106.3.3, 1609.1.4, 1714.5.1 &
 EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A COMPLETE
 INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING
 SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS,
 WALL PRESSURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION TO FACILITATE
 PLAN REVIEW AND PERMIT ISSUANCE.
  
 4) THE PERMIT APPLICATION DESSCRIPTION OF WORK
 INDICATES WORK TO BE COMPLETED OF BOTH THE 2ND FLOOR AS
 WELL AS THE FIRST FLOOR, NO PLANS WERE SUBMITTED FOR
 THE FIRST FLOOR.
 PLEASE PROVIDE OCCUPANCY SEPERATION BETWEEN THE FIRST
 FLOOR AND SECOND FLOOR SINCE THE FIRST FLOOR IS
 CONSIDERED BUSINESS OR MERCANTILE AND THE SECOND AS
 RESIDENTIAL UNIT. 2010 FBC-B TABLE 508.4 2 HR FOR
 NON-SPRINKLERED AND ONE HOUR FOR FIRE SPRINKLERED
 BUILDINGS. PLEASE PROVIDE FIRE RATED ASSEMBLIES FOR
 THROUGH PENETRATIONS. 712.4.1.1.
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 5) SHEET 1.1 INDICATES THE UNDER THE PROJECT DATA THIS
 PLAN IS DESIGNED UNDER THE 2007/09 FBC. MARCH 01/2012
 THE 2010 FBC WAS ADOPTED STATEWIDE.
  
 6) SHEET 1.1 BATHROOM WINDOW MAY OR MAY NOT NEED TO
 MEET THE REQUIREMENTS OF 2010 FBC-B 2406.4(5) HAZARDOUS
 LOCATION, NOTE TEMPERED GLASS WILL ALSO MEET THE
 REQUIREMENTS OF 1026.6 FOR EXTERIOR STAIR PROTECTION
 REQUIRED BY 1022.1.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-05-31 Cont ID  
Sent By dharvey Date 2013-05-31 Time 14:27 Rev Time 0.00
Received By dharvey Date 2013-05-31 Time 14:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-03-07 Cont ID  
Sent By rlecky Date 2013-03-07 Time 10:50 Rev Time 0.00
Received By rlecky Date 2013-03-07 Time 08:48 Sent To  
Notes
2013-03-07 10:52:3713020224
 429 BELVEDERE ROAD
 APARTMENT INTERIOR REMODEL
 CHANGE OF USE
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 ELECTRICAL SERVICE AND SWITCH GEAR. NEC 110.9, 110.10
  
 VERIFY ALL EXTERIOR SERVICE EQUIPMENT IS RATED FOR A
 WET LOCATION. NEC 306.9
  
 PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH
 PROTECTION, HIGH-LEG MARKING AT THE PANEL BOARDS AND
 THE MAIN DISCONNECTING MEANS. NEC 110.22, 110.16,
 110.22
  
 A GFCI PROTECTED RECEPTACLE IS REQUIRED ON THE ROOF FOR
 SERVICING THE AIR CONDITIONING EQUIPMENT. NEC 210.63,
 210.8(B)
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE BRANCH
 CIRCUITS. NEC 210.52
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-06-05 Cont ID  
Sent By wjolin Date 2013-06-05 Time 08:31 Rev Time 0.00
Received By wjolin Date 2013-06-05 Time 08:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-03-16 Cont ID  
Sent By wjolin Date 2013-03-16 Time 17:24 Rev Time 0.00
Received By wjolin Date 2013-03-16 Time 17:02 Sent To B
Notes
2013-03-16 17:24:08429 BELVEDERE ROAD
 PERMIT #13020224
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION INDICATES REMODEL WORK ON BOTH
 THE FIRST AND SECOND FLOOR; HOWEVER, NO WORK IS BEING
 SHOWN ON THE FIRST FLOOR.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 THE RESIDENTIAL OCCUPANCY IS REQUIRED TO BE SEPARATED
 FROM OTHER OCCUPANCY TYPES WITH AT LEAST A 2-HOUR
 FIRE-RATED BARRIER. NO FLOOR/CEILING FIRE RATING IS
 INDICATED. PENETRATIONS SHALL BE PROTECTED WITH A
 LISTED ASSEMBLY.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-05 Cont ID  
Sent By wjolin Date 2013-06-05 Time 08:31 Rev Time 0.00
Received By wjolin Date 2013-05-21 Time 12:04 Sent To  
Notes
2013-05-22 13:12:41B--1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-22 Cont ID  
Sent By lmartine Date 2013-03-16 Time 12:04 Rev Time 0.00
Received By lmartine Date 2013-02-08 Time 12:04 Sent To  
Notes
2013-02-11 13:52:02C07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2013-06-06 Cont ID  
Sent By jwitmer Date 2013-06-06 Time 09:27 Rev Time 0.00
Received By jwitmer Date 2013-06-06 Time 09:27 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-05-28 Cont ID  
Sent By jwitmer Date 2013-05-28 Time 07:34 Rev Time 0.00
Received By jwitmer Date 2013-05-28 Time 07:33 Sent To  
Notes
2013-05-28 07:34:17BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-03-12 Cont ID  
Sent By jwitmer Date 2013-03-12 Time 10:04 Rev Time 0.00
Received By jwitmer Date 2013-02-08 Time 13:48 Sent To  
Notes
2013-03-12 10:04:47BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-05-28 Cont ID  
Sent By jwitmer Date 2013-05-28 Time 07:35 Rev Time 0.00
Received By jwitmer Date 2013-05-28 Time 07:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-03-06 Cont ID  
Sent By hmoser Date 2013-03-06 Time 13:58 Rev Time 0.00
Received By hmoser Date 2013-03-06 Time 12:23 Sent To  
Notes
2013-03-06 13:58:33PASS PROVISO
 1) PROVIDE A LETTER FROM THE ENGINEER SHOWING THE
 BOLT SIZE FROM THE PRE-ENGINEERED STAND TO THE EXISTING
 STEEL AT 1ST INSPECTION PER SECTION 301.12 WIND
 RESISTANCE
 2010 FBC (M)
 2) PROVIDE A LETTER FROM THE ENGINEER SHOWING THE
 MODEL NUMBER OF THE EQUIPMENT .PER SECTION 107
 2010 FBC.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-05-28 Cont ID  
Sent By jwitmer Date 2013-05-28 Time 07:34 Rev Time 0.00
Received By jwitmer Date 2013-05-28 Time 07:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-03-06 Cont ID  
Sent By lwagner Date 2013-03-06 Time 09:07 Rev Time 0.00
Received By lwagner Date 2013-03-06 Time 08:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-03-11 Cont ID  
Sent By ajones Date 2013-03-11 Time 10:39 Rev Time 0.00
Received By ajones Date 2013-03-11 Time 10:39 Sent To  
Notes
***NONE***