| Plan Review Stops For Permit 13020217 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2013-09-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-09-26 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-09-26 |
Time |
10:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2013-08-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-08-22 |
Time |
19:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-08-22 |
Time |
19:14 |
Sent To |
|
|
| Notes |
| 2013-08-22 19:26:51 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | FROM PREVIOUS LIST: | | | | | | 1-2. OK | | | | | | 3. PROVIDE A STRUCTURAL DETAILS FOR GABLE REPAIR (SEE | | | FBC R 703.6.3 REGARDING BOND BREAK). GABLE BRACING, | | | SHOW SOFFIT VENTILATION. | | | | | | 2ND REVIEW, DETAIL PROVIDED BUT PLEASE REVISE PER FBC | | | 2010 RESIDENTIAL 703.6.3, BOND BREAK REQUIRED. | | | | | | 4. OK | | | | | | 5. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPOVAL FOR | | | THE SINGLES AND THE FLAT DECK. PROVIDE ROOF HEIGHT AND | | | SLOPE. FOR THE ROOF, INDICATE WHICH APPROVED ASSEMBLY | | | IS PROPOSED AND PROVIDE ENGINEERING IF REQUIRED OR | | | OTHERWISE SPECIFY ENHANCED FASTENING, SEE LIMITATIONS | | | ON THE PRODUCT APPROVAL. A SEPARATE ROOF SUB PERMIT IS | | | REQUIRED. | | | | | | 2ND REVIEW, WIND SPEED MINIMUM PER | | | WWW.ATCOUNCIL.ORG/WINDSPEED SHOULD BE 169MPH. PLAN | | | STATES DESIGN CRITEIA IS 165MPH, S100. PRESSURES APPEAR | | | LOW. EITHER CONTACT ME TO INFORM HOW WIND SPEED WAS | | | DETERMINED OR REVISE DESIGN CRITERIA AND DESIGN | | | PRESSURES ACCORDINGLY. | | | | | | THE RAS117 CALCULATIONS ON S200 REFER TO 07-1219.09, | | | BUT THE NOA REVIEWED BY ARCHITECT AND SUBMITTED BY | | | CONTRACTOR IS 07-1219.09. | | | | | | 6-8. OK | | | | | | NEW COMMENTS BASED ON NEW PLAN PROVIDED: | | | | | | 9. S100, A/C SLAB SHOWN SMALLER THAN THE UNIT. NO | | | FASTENING OF UNIT TO SLAB SPECIFIED. PLEASE REVISE, FBC | | | 2010 RESIDENTIAL 301. | | | | | | 10. PROVIDE A DETAIL FOR BLOCK INFILL SHOWN ON A-100 | | | (BR1, BR2, KITCHEN). FBC 107, FBC 2010 RESIDENTIAL 301. | | | | | | 11. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY | | | REQUIRED. THE PLANS ARE TO BE STAMPED AND THE RECEIPT, | | | IF FEES WERE DUE, TO BE SUBMITTED AS EVIDENCE THAT THE | | | FEES WERE PAID. 233-5025 FOR MORE INFORMATION | | | | | | **UPON REQUEST, ALL ITEMS CAN BE PROVISO ITEMS - | | | REVISION REQUIRED (WITH FEES), ISSUED AT CONTRACTOR'S | | | RISK** | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-02-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-02-12 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-02-12 |
Time |
10:42 |
Sent To |
Z |
|
| Notes |
| 2013-02-12 11:01:53 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | | | | 1. SEE FBC 107.2.1: | | | | | | INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION | | | DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE | | | MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED | | | WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION | | | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE | | | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED | | | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS | | | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH | | | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES | | | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE | | | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE | | | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN. (SEE ALSO SECTION 107.3.5). | | | | | | NO PLAN SUBMITTED. | | | | | | 2. PLEASE DO NOT SUBMIT DOCUMENTS NOT REQUIRED TO SHOW | | | CODE COMPLIANCE. FOR INSTANCE, THE DOCUMENT REGARDING | | | LEAD BASED PAINT. | | | | | | 3. PROVIDE A STRUCTURAL DETAILS FOR GABLE REPAIR (SEE | | | FBC R 703.6.3 REGARDING BOND BREAK). GABLE BRACING, | | | SHOW SOFFIT VENTILATION. | | | | | | 4. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR | | | THE DOORS AND WINDOWS, FAC9N-3. | | | | | | 5. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPOVAL FOR | | | THE SINGLES AND THE FLAT DECK. PROVIDE ROOF HEIGHT AND | | | SLOPE. FOR THE ROOF, INDICATE WHICH APPROVED ASSEMBLY | | | IS PROPOSED AND PROVIDE ENGINEERING IF REQUIRED OR | | | OTHERWISE SPECIFY ENHANCED FASTENING, SEE LIMITATIONS | | | ON THE PRODUCT APPROVAL. A SEPARATE ROOF SUB PERMIT IS | | | REQUIRED. | | | | | | 6. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, | | | SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING | | | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR | | | BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING | | | CANNOT BE REDUCED BY MORE THAN 5%. INCLUDE DOOR | | | LOCATIONS FOR DOORS TO BE REPLACED AS WELL AS DOOR | | | SIZE. | | | | | | 7. PROVIDE A STRUCTURAL PLAN FOR THE NEW ADDITION. NOT | | | ENOUGH INFORMATION PROVIDE TO SHOW CODE COMPLIANCE. | | | | | | 8. PROVIDE A SITE PLAN SHOWING PROPOSED ADDITION | | | INCLUDING DISTANCE TO PROPERTY LINES, FBC R 302. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2013-10-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-10-04 |
Time |
07:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-10-04 |
Time |
06:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2013-08-26 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-08-26 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-08-26 |
Time |
15:54 |
Sent To |
|
|
| Notes |
| 2013-08-26 16:14:13 | PROVIDE INTERSYSTEM BONDING POINT AT SERVICE 250.94 | | | BATHROOM RECEPTACLE CIRCUIT TO BE 20 AMP RATED 210.11 C | | | 3 | | | SEE 210.52 C 3&5 FOR PENINSULAR COUNTER TO ENSURE | | | COMPLIANCE | | | PLANS SPECIFY "CONDUIT" FOR THE WIRING METHOD. PLEASE | | | CONFIRM | | | PLANS CALL FOR FOUNDATION STEEL TO BE ATTACHED TO THE | | | GROUNDING ELECTRODE SYSTEM. THIS A RENOVATION. IS | | | FOOTER STEEL AVAILABLE? | | | SMOKE/CO ALARMS SHOULD BE LOCATED PERMANUFACTURERS | | | INSTRUCTIONS AND TO PROVIDE THE BEST COVERAGE, NOT | | | NECESSARILY AT THE BEDROOM ENTRY. 110.3 | | | EGRESS LIGHT IS REQUIRED AT FRONT DOOR (FAN IS NOT | | | ILLUMINATION) 210.70 | | | PLEASE PROVIDE AVAIALBLE FAULT CURRENT AT THE SERVICE | | | TO ENSURE COORDINATION OF ELECTRICAL EQUIPMENT 110.9 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-02-20 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2013-02-20 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2013-02-20 |
Time |
16:29 |
Sent To |
P |
|
| Notes |
| 2013-02-20 16:31:28 | 13020217 | | | 1028 19TH STREET | | | RESIDENTIAL REPAIR | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | ELECTRICAL PLANS ARE REQUIRED. PROVIDE AN ELECTRICAL | | | RISER PLAN SHOWING THE PANEL, MAIN BREAKER, GROUNDING, | | | FEEDERS AND BRANCH CIRCUITS. INCLUDE A LOAD CALCULATION | | | AND PANEL DIRECTORY. SHOW LOCATION OF THE ELECTRICAL | | | PANEL WITH REQUIRED SAFE WORKING CLEARANCES. | | | INDICATE THE SIZE AND LOCATION OF THE ELECTRICAL PANEL. | | | ON A FLOOR PLAN SHOW THE LOCATION OF ALL NEW LIGHTING | | | OUTLETS, RECEPTACLE OUTLETS AND SMOKE DETECTORS. NEC | | | 215.5, 210.50, 110.26 | | | | | | SHOW SAFETY CLEARANCES AND LOCATIONS OF ALL APPLIANCES, | | | PANEL BOARDS, METERS ETC. FBC 107.2.1 | | | | | | SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI | | | PROTECTED. NEC 210.8 | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 | | | | | | THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH | | | CIRCUIT. NEC 210.11 (C) (3) | | | | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE | | | FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1) | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2013-10-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-10-04 |
Time |
07:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-09-10 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2013-09-16 10:46:38 | PLANS STAMPED BY PB COUNTY IMPACT ROUTED TO R3 | | | | | 2013-09-11 09:25:08 | INCOMING SENT TO BOX R03. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-08-27 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2013-08-27 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2013-08-06 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2013-08-06 15:22:24 | INCOMING SENT TO R02. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-02-25 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-02-25 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-02-08 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2013-02-12 11:03:18 | 2/11 TO ZONING | | | | | 2013-02-11 10:27:19 | SENT TO MISC 1 BOX PER L MARTINEZ. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2013-09-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-09-26 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-09-26 |
Time |
16:08 |
Sent To |
|
|
| Notes |
| 2013-09-26 10:55:58 | MU2013-18808 | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2013-09-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-09-26 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-09-26 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2013-09-26 10:36:46 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FROM PREVIOUS LIST: | | | | | | 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED. | | | 561-233-5025. THE PLAN IS TO BE STAMPED AND THE | | | RECEIPT, IF FEES WERE DUE, TO BE SUBMITTED AS EVIDENCE | | | THAT IMPACT FEES WERE PAID. | | | | | | 2ND IMPACT FEE REVIEW - AS FEES WERE DUE, THE RECEIPT | | | SHOWING THAT FEES WERE PAID IS TO BE SUBMITTED. | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2013-08-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-08-22 |
Time |
18:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-08-22 |
Time |
18:44 |
Sent To |
|
|
| Notes |
| 2013-08-22 18:45:17 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED. | | | 561-233-5025. THE PLAN IS TO BE STAMPED AND THE | | | RECEIPT, IF FEES WERE DUE, TO BE SUBMITTED AS EVIDENCE | | | THAT IMPACT FEES WERE PAID. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2013-08-26 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-08-26 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-08-26 |
Time |
15:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2013-02-25 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-02-25 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-02-25 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2013-02-25 13:21:26 | DENIED | | | 1) ANY NEW MECHANICAL WORK REQUIRES A | | | MECHANICAL PLAN. PER SECTION 107.3.5.3 | | | (10) AND (13) 2010 FBC. | | | 2) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. | | | 2010 FBC. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2013-10-03 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2013-10-03 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2013-10-03 |
Time |
14:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2013-08-27 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2013-08-27 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2013-08-27 |
Time |
09:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2013-02-22 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2013-02-22 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2013-02-22 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2013-02-22 14:29:30 | FBC 2010 EXISTING BUILDING CODE | | | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | NEW PLUMBING PIPEING REQUIRES A DRAWING. | | | FBC 107.3.5.3 (11) PLUMBING RISER | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2013-08-23 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2013-08-23 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2013-08-23 |
Time |
14:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2013-02-11 |
|
|
Cont ID |
|
| Sent By |
mdekle |
Date |
2013-02-11 |
Time |
|
Rev Time |
|
| Received By |
mdekle |
Date |
2013-02-11 |
Time |
|
Sent To |
E |
|
| Notes |
|
|