Plan Review Details - Permit 13020217
Plan Review Stops For Permit 13020217
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-09-26 Cont ID  
Sent By shill Date 2013-09-26 Time 10:54 Rev Time 0.00
Received By shill Date 2013-09-26 Time 10:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-08-22 Cont ID  
Sent By shill Date 2013-08-22 Time 19:14 Rev Time 0.00
Received By shill Date 2013-08-22 Time 19:14 Sent To  
Notes
2013-08-22 19:26:51****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1-2. OK
  
 3. PROVIDE A STRUCTURAL DETAILS FOR GABLE REPAIR (SEE
 FBC R 703.6.3 REGARDING BOND BREAK). GABLE BRACING,
 SHOW SOFFIT VENTILATION.
  
 2ND REVIEW, DETAIL PROVIDED BUT PLEASE REVISE PER FBC
 2010 RESIDENTIAL 703.6.3, BOND BREAK REQUIRED.
  
 4. OK
  
 5. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPOVAL FOR
 THE SINGLES AND THE FLAT DECK. PROVIDE ROOF HEIGHT AND
 SLOPE. FOR THE ROOF, INDICATE WHICH APPROVED ASSEMBLY
 IS PROPOSED AND PROVIDE ENGINEERING IF REQUIRED OR
 OTHERWISE SPECIFY ENHANCED FASTENING, SEE LIMITATIONS
 ON THE PRODUCT APPROVAL. A SEPARATE ROOF SUB PERMIT IS
 REQUIRED.
  
 2ND REVIEW, WIND SPEED MINIMUM PER
 WWW.ATCOUNCIL.ORG/WINDSPEED SHOULD BE 169MPH. PLAN
 STATES DESIGN CRITEIA IS 165MPH, S100. PRESSURES APPEAR
 LOW. EITHER CONTACT ME TO INFORM HOW WIND SPEED WAS
 DETERMINED OR REVISE DESIGN CRITERIA AND DESIGN
 PRESSURES ACCORDINGLY.
  
 THE RAS117 CALCULATIONS ON S200 REFER TO 07-1219.09,
 BUT THE NOA REVIEWED BY ARCHITECT AND SUBMITTED BY
 CONTRACTOR IS 07-1219.09.
  
 6-8. OK
  
 NEW COMMENTS BASED ON NEW PLAN PROVIDED:
  
 9. S100, A/C SLAB SHOWN SMALLER THAN THE UNIT. NO
 FASTENING OF UNIT TO SLAB SPECIFIED. PLEASE REVISE, FBC
 2010 RESIDENTIAL 301.
  
 10. PROVIDE A DETAIL FOR BLOCK INFILL SHOWN ON A-100
 (BR1, BR2, KITCHEN). FBC 107, FBC 2010 RESIDENTIAL 301.
  
 11. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY
 REQUIRED. THE PLANS ARE TO BE STAMPED AND THE RECEIPT,
 IF FEES WERE DUE, TO BE SUBMITTED AS EVIDENCE THAT THE
 FEES WERE PAID. 233-5025 FOR MORE INFORMATION
  
 **UPON REQUEST, ALL ITEMS CAN BE PROVISO ITEMS -
 REVISION REQUIRED (WITH FEES), ISSUED AT CONTRACTOR'S
 RISK**
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-12 Cont ID  
Sent By shill Date 2013-02-12 Time 10:42 Rev Time 0.00
Received By shill Date 2013-02-12 Time 10:42 Sent To Z
Notes
2013-02-12 11:01:53****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. SEE FBC 107.2.1:
  
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED
 WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 NO PLAN SUBMITTED.
  
 2. PLEASE DO NOT SUBMIT DOCUMENTS NOT REQUIRED TO SHOW
 CODE COMPLIANCE. FOR INSTANCE, THE DOCUMENT REGARDING
 LEAD BASED PAINT.
  
 3. PROVIDE A STRUCTURAL DETAILS FOR GABLE REPAIR (SEE
 FBC R 703.6.3 REGARDING BOND BREAK). GABLE BRACING,
 SHOW SOFFIT VENTILATION.
  
 4. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR
 THE DOORS AND WINDOWS, FAC9N-3.
  
 5. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPOVAL FOR
 THE SINGLES AND THE FLAT DECK. PROVIDE ROOF HEIGHT AND
 SLOPE. FOR THE ROOF, INDICATE WHICH APPROVED ASSEMBLY
 IS PROPOSED AND PROVIDE ENGINEERING IF REQUIRED OR
 OTHERWISE SPECIFY ENHANCED FASTENING, SEE LIMITATIONS
 ON THE PRODUCT APPROVAL. A SEPARATE ROOF SUB PERMIT IS
 REQUIRED.
  
 6. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%. INCLUDE DOOR
 LOCATIONS FOR DOORS TO BE REPLACED AS WELL AS DOOR
 SIZE.
  
 7. PROVIDE A STRUCTURAL PLAN FOR THE NEW ADDITION. NOT
 ENOUGH INFORMATION PROVIDE TO SHOW CODE COMPLIANCE.
  
 8. PROVIDE A SITE PLAN SHOWING PROPOSED ADDITION
 INCLUDING DISTANCE TO PROPERTY LINES, FBC R 302.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-10-04 Cont ID  
Sent By rmcdouga Date 2013-10-04 Time 07:29 Rev Time 0.00
Received By rmcdouga Date 2013-10-04 Time 06:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-08-26 Cont ID  
Sent By dharvey Date 2013-08-26 Time 16:14 Rev Time 0.00
Received By dharvey Date 2013-08-26 Time 15:54 Sent To  
Notes
2013-08-26 16:14:13PROVIDE INTERSYSTEM BONDING POINT AT SERVICE 250.94
 BATHROOM RECEPTACLE CIRCUIT TO BE 20 AMP RATED 210.11 C
 3
 SEE 210.52 C 3&5 FOR PENINSULAR COUNTER TO ENSURE
 COMPLIANCE
 PLANS SPECIFY "CONDUIT" FOR THE WIRING METHOD. PLEASE
 CONFIRM
 PLANS CALL FOR FOUNDATION STEEL TO BE ATTACHED TO THE
 GROUNDING ELECTRODE SYSTEM. THIS A RENOVATION. IS
 FOOTER STEEL AVAILABLE?
 SMOKE/CO ALARMS SHOULD BE LOCATED PERMANUFACTURERS
 INSTRUCTIONS AND TO PROVIDE THE BEST COVERAGE, NOT
 NECESSARILY AT THE BEDROOM ENTRY. 110.3
 EGRESS LIGHT IS REQUIRED AT FRONT DOOR (FAN IS NOT
 ILLUMINATION) 210.70
 PLEASE PROVIDE AVAIALBLE FAULT CURRENT AT THE SERVICE
 TO ENSURE COORDINATION OF ELECTRICAL EQUIPMENT 110.9
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-02-20 Cont ID  
Sent By rlecky Date 2013-02-20 Time 16:31 Rev Time 0.00
Received By rlecky Date 2013-02-20 Time 16:29 Sent To P
Notes
2013-02-20 16:31:2813020217
 1028 19TH STREET
 RESIDENTIAL REPAIR
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 ELECTRICAL PLANS ARE REQUIRED. PROVIDE AN ELECTRICAL
 RISER PLAN SHOWING THE PANEL, MAIN BREAKER, GROUNDING,
 FEEDERS AND BRANCH CIRCUITS. INCLUDE A LOAD CALCULATION
 AND PANEL DIRECTORY. SHOW LOCATION OF THE ELECTRICAL
 PANEL WITH REQUIRED SAFE WORKING CLEARANCES.
 INDICATE THE SIZE AND LOCATION OF THE ELECTRICAL PANEL.
 ON A FLOOR PLAN SHOW THE LOCATION OF ALL NEW LIGHTING
 OUTLETS, RECEPTACLE OUTLETS AND SMOKE DETECTORS. NEC
 215.5, 210.50, 110.26
  
 SHOW SAFETY CLEARANCES AND LOCATIONS OF ALL APPLIANCES,
 PANEL BOARDS, METERS ETC. FBC 107.2.1
  
 SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI
 PROTECTED. NEC 210.8
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE
 FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1)
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-10-04 Cont ID  
Sent By rmcdouga Date 2013-10-04 Time 07:29 Rev Time 0.00
Received By rmcdouga Date 2013-09-10 Time 09:22 Sent To  
Notes
2013-09-16 10:46:38PLANS STAMPED BY PB COUNTY IMPACT ROUTED TO R3
  
2013-09-11 09:25:08INCOMING SENT TO BOX R03. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-27 Cont ID  
Sent By lwagner Date 2013-08-27 Time 09:36 Rev Time 0.00
Received By lwagner Date 2013-08-06 Time 13:16 Sent To  
Notes
2013-08-06 15:22:24INCOMING SENT TO R02. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-25 Cont ID  
Sent By hmoser Date 2013-02-25 Time 13:21 Rev Time 0.00
Received By hmoser Date 2013-02-08 Time 10:27 Sent To  
Notes
2013-02-12 11:03:182/11 TO ZONING
  
2013-02-11 10:27:19SENT TO MISC 1 BOX PER L MARTINEZ.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2013-09-26 Cont ID  
Sent By shill Date 2013-09-26 Time 16:08 Rev Time 0.00
Received By shill Date 2013-09-26 Time 16:08 Sent To  
Notes
2013-09-26 10:55:58MU2013-18808
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-09-26 Cont ID  
Sent By shill Date 2013-09-26 Time 10:36 Rev Time 0.00
Received By shill Date 2013-09-26 Time 10:36 Sent To  
Notes
2013-09-26 10:36:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED.
 561-233-5025. THE PLAN IS TO BE STAMPED AND THE
 RECEIPT, IF FEES WERE DUE, TO BE SUBMITTED AS EVIDENCE
 THAT IMPACT FEES WERE PAID.
  
 2ND IMPACT FEE REVIEW - AS FEES WERE DUE, THE RECEIPT
 SHOWING THAT FEES WERE PAID IS TO BE SUBMITTED.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-08-22 Cont ID  
Sent By shill Date 2013-08-22 Time 18:44 Rev Time 0.00
Received By shill Date 2013-08-22 Time 18:44 Sent To  
Notes
2013-08-22 18:45:17****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED.
 561-233-5025. THE PLAN IS TO BE STAMPED AND THE
 RECEIPT, IF FEES WERE DUE, TO BE SUBMITTED AS EVIDENCE
 THAT IMPACT FEES WERE PAID.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-08-26 Cont ID  
Sent By hmoser Date 2013-08-26 Time 15:25 Rev Time 0.00
Received By hmoser Date 2013-08-26 Time 15:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-02-25 Cont ID  
Sent By hmoser Date 2013-02-25 Time 13:21 Rev Time 0.00
Received By hmoser Date 2013-02-25 Time 13:12 Sent To  
Notes
2013-02-25 13:21:26DENIED
 1) ANY NEW MECHANICAL WORK REQUIRES A
 MECHANICAL PLAN. PER SECTION 107.3.5.3
 (10) AND (13) 2010 FBC.
 2) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 2010 FBC.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2013-10-03 Cont ID  
Sent By lwagner Date 2013-10-03 Time 14:37 Rev Time 0.00
Received By lwagner Date 2013-10-03 Time 14:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-08-27 Cont ID  
Sent By lwagner Date 2013-08-27 Time 09:35 Rev Time 0.00
Received By lwagner Date 2013-08-27 Time 09:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-02-22 Cont ID  
Sent By lwagner Date 2013-02-22 Time 14:26 Rev Time 0.00
Received By lwagner Date 2013-02-22 Time 14:08 Sent To  
Notes
2013-02-22 14:29:30FBC 2010 EXISTING BUILDING CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 NEW PLUMBING PIPEING REQUIRES A DRAWING.
 FBC 107.3.5.3 (11) PLUMBING RISER
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 2 Status P Date 2013-08-23 Cont ID  
Sent By ajones Date 2013-08-23 Time 14:27 Rev Time 0.00
Received By ajones Date 2013-08-23 Time 14:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-02-11 Cont ID  
Sent By mdekle Date 2013-02-11 Time   Rev Time  
Received By mdekle Date 2013-02-11 Time   Sent To E
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved