Plan Review Details - Permit 13020070
Plan Review Stops For Permit 13020070
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-02-05 Cont ID  
Sent By jwitmer Date 2013-02-05 Time 09:23 Rev Time 0.00
Received By jwitmer Date 2013-02-05 Time 09:23 Sent To  
Notes
2013-02-05 10:32:47BUILDING PLAN REVIEW
 PERMIT: 13020070
 ADD: 3210 VINCENT RD
 CONT: WATERPROOFING &
 ROOFING DESIGN
 TEL: (561)741-8919
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 ROOFING PERMIT
 PROVISO:
  
 2010 FBC-R R905.2.7 UNDERLAYMENT APPLICATION.
 FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (17-PERCENT SLOPE), UP TO FOUR UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE), TWO
 LAYERS OF UNDERLAYMENT COMPLYING WITH ASTM D 226 TYPE I
 OR TYPE II, ASTM D 4869 TYPE I OR TYPE II, OR ASTM D
 6757 SHALL BE APPLIED IN THE FOLLOWING MANNER:
  
 1. APPLY A MINIMUM 19-INCH-WIDE (483 MM) STRIP OF
 UNDERLAYMENT FELT PARALLEL WITH AND STARTING AT THE
 EAVES.
  
 2. STARTING AT THE EAVE, APPLY 36-INCH-WIDE (914 MM)
 SHEETS OF UNDERLAYMENT OVERLAPPING SUCCESSIVE SHEETS 19
 INCHES (483 MM). DISTORTIONS IN THE UNDERLAYMENT SHALL
 NOT INTERFERE WITH THE ABILITY OF THE SHINGLES TO SEAL.
  
 3. END LAPS SHALL BE OFFSET BY 6 FEET (1829 MM).
  
 4. CORROSION RESISTANT FASTENERS ARE TO BE APPLIED
 ALONG THE OVERLAP AT A MAXIMUM SPACING OF 36 INCHES
 (914 MM) ON CENTER.
  
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]