| 2013-02-05 13:38:26 | 933 45TH STREET |
| | PERMIT #13020028 |
| | MASTER #12100245 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE ENGINEERED CONSTRUCTION DOCUMENTS INDICATE THAT ALL |
| | AREAS ABOVE THE CEILING ARE COMPOSED OF CONCEALED |
| | COMBUSTIBLE CONSTRUCTION. AREAS WILL REQUIRE SPRINKLER |
| | PROTECTION PER 8.15.1 (NFPA 13 - 2007 EDITION). |
| | |
| | SPRINKLERS SHALL BE LOCATED WITHIN 3' OF THE PEAKED |
| | CEILING PER 8.6.4.1.3 (NFPA 13 - 2007 EDITION). |
| | |
| | THE KITCHEN AREA HYDRAULIC PLAN DATA INDICATES AN AREA |
| | OF 1500 SQ.FT. WAS CALCULATED ALTHOUGH THE ACTUAL |
| | CALCULATION AREA APPEARS TO BE APPROXIMATELY 1100 |
| | SQ.FT. IF THE HYDRAULIC AREA HAS BEEN REDUCED USING THE |
| | AREA REDUCTION METHOD FOR QUICK RESPONSE SPRINKLERS |
| | PLEASE INDICATE THIS ON THE PLANS. |
| | |
| | THE DINING AREA HYDRAULIC PLAN DATA INDICATES AN AREA |
| | OF 1500 SQ.FT. WAS CALCULATED ALTHOUGH THE ACTUAL |
| | CALCULATION AREA APPEARS TO BE APPROXIMATELY 1600 |
| | SQ.FT. HYDRAULIC AREAS SHALL BE INCREASED BY 30% WHEN |
| | THE CEILING SLOPE EXCEEDS 1 IN 6 PER 11.2.3.2.4 (NFPA |
| | 13 - 2007 EDITION). AFTER THE 30% INCREASE HAS BEEN |
| | ADDED, THE AREA MAY THEN BE REDUCED USING THE AREA |
| | REDUCTION METHOD FOR QUICK RESPONSE SPRINKLERS PLEASE |
| | INDICATE THIS ON THE PLANS. |
| | |
| | FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED |
| | SUPERVISING STATION IN ACCORDANCE WITH NFPA 72. |
| | |
| | PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR |
| | SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN |
| | POSITION. |
| | |
| | PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE |
| | DEPARTMENT CONNECTION. |
| | |