Plan Review Details - Permit 13020028
Plan Review Stops For Permit 13020028
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-02-04 Cont ID  
Sent By wjolin Date 2014-01-31 Time 09:51 Rev Time 0.00
Received By wjolin Date 2014-01-31 Time 09:37 Sent To M
Notes
2014-01-31 09:51:065200 EAST AVENUE
 PERMIT #13020028
 MASTER #12100245
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT - SECTION A-A: SPRINKLERS ARE NOT
 LOCATED WITHIN 3' (VERTICAL) OF THE PEAK FOR THE SLOPED
 CEILING PER 8.6.4.1.3 (NFPA 13 - 2007 EDITION). THIS
 SITUATION OCCURS IN THE HYDRAULIC AREA SO ADDITIONAL
 SPRINKLERS WILL AFFECT THE CALCULATIONS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-02-05 Cont ID  
Sent By wjolin Date 2013-02-05 Time 13:38 Rev Time 0.00
Received By wjolin Date 2013-02-05 Time 12:57 Sent To M
Notes
2013-02-05 13:38:26933 45TH STREET
 PERMIT #13020028
 MASTER #12100245
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ENGINEERED CONSTRUCTION DOCUMENTS INDICATE THAT ALL
 AREAS ABOVE THE CEILING ARE COMPOSED OF CONCEALED
 COMBUSTIBLE CONSTRUCTION. AREAS WILL REQUIRE SPRINKLER
 PROTECTION PER 8.15.1 (NFPA 13 - 2007 EDITION).
  
 SPRINKLERS SHALL BE LOCATED WITHIN 3' OF THE PEAKED
 CEILING PER 8.6.4.1.3 (NFPA 13 - 2007 EDITION).
  
 THE KITCHEN AREA HYDRAULIC PLAN DATA INDICATES AN AREA
 OF 1500 SQ.FT. WAS CALCULATED ALTHOUGH THE ACTUAL
 CALCULATION AREA APPEARS TO BE APPROXIMATELY 1100
 SQ.FT. IF THE HYDRAULIC AREA HAS BEEN REDUCED USING THE
 AREA REDUCTION METHOD FOR QUICK RESPONSE SPRINKLERS
 PLEASE INDICATE THIS ON THE PLANS.
  
 THE DINING AREA HYDRAULIC PLAN DATA INDICATES AN AREA
 OF 1500 SQ.FT. WAS CALCULATED ALTHOUGH THE ACTUAL
 CALCULATION AREA APPEARS TO BE APPROXIMATELY 1600
 SQ.FT. HYDRAULIC AREAS SHALL BE INCREASED BY 30% WHEN
 THE CEILING SLOPE EXCEEDS 1 IN 6 PER 11.2.3.2.4 (NFPA
 13 - 2007 EDITION). AFTER THE 30% INCREASE HAS BEEN
 ADDED, THE AREA MAY THEN BE REDUCED USING THE AREA
 REDUCTION METHOD FOR QUICK RESPONSE SPRINKLERS PLEASE
 INDICATE THIS ON THE PLANS.
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-02-24 Cont ID  
Sent By skennedy Date 2014-02-24 Time 09:39 Rev Time 0.00
Received By skennedy Date 2014-01-21 Time 15:42 Sent To  
Notes
2014-01-22 15:42:37RESUBMITTAL SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-06 Cont ID  
Sent By hmoser Date 2013-02-06 Time 13:54 Rev Time 0.00
Received By hmoser Date 2013-02-01 Time 09:56 Sent To  
Notes
2013-02-04 09:56:23SENT TO FIRE BOX.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-02-24 Cont ID  
Sent By wjolin Date 2014-02-04 Time 15:37 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-02-06 Cont ID  
Sent By hmoser Date 2013-02-06 Time 13:53 Rev Time 0.00
Received By hmoser Date 2013-02-06 Time 13:51 Sent To  
Notes
2013-02-06 13:53:35PLAN DENIED
 SEE COMMENTS FROM FIRE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]