Plan Review Details - Permit 13010898
Plan Review Stops For Permit 13010898
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-03-18 Cont ID  
Sent By jgomez Date 2013-03-18 Time 10:24 Rev Time 0.00
Received By jgomez Date 2013-03-18 Time 10:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-11 Cont ID  
Sent By jgomez Date 2013-02-11 Time 10:51 Rev Time 0.00
Received By jgomez Date 2013-02-11 Time 10:40 Sent To  
Notes
2013-02-11 11:04:47RESIDENTIAL (R3) ALTERATIONS BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE FRAMING DETAILS FOR THE
 INSTALLATION OF NEW DOOR AND WINDOW. SPECIFY ALL
 FRAMING MEMBERS AND FASTENERS TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3 OF
 2010 FBC-RESIDENTIAL.
 ***NOTE; TAKE INTO CONSIDERATION THAT THIS BUILDING IS
 LOCATED IN EXPOSURE "C".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-03-12 Cont ID  
Sent By rlecky Date 2013-03-12 Time 10:14 Rev Time 0.00
Received By rlecky Date 2013-03-12 Time 10:08 Sent To  
Notes
2013-03-12 10:18:16TO JG

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-02-11 Cont ID  
Sent By rlecky Date 2013-02-11 Time 11:47 Rev Time 0.00
Received By rlecky Date 2013-02-11 Time 11:37 Sent To  
Notes
2013-02-11 11:48:3213010898
 508 52ND STREET
 RESIDENTIAL REPAIR
  
 THE SCOPE OF THE ELECTRICAL WORK WAS NOT ADEQUATELY
 DESCRIBED. PLEASE PROVIDE A FLOOR PLAN SHOWING THE
 SCOPE OF WORK INTENDED OR A SEPARATE DOCUMENT ON THE
 COMPANY LETTER HEAD OUTLINING THE ELECTRICAL WORK
 PROPOSED. INCLUDE THE FOLLOWING ITEMS WHERE
 APPROPRIATE.
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 GFCI PROTECTION IS REQUIRED FOR ALL OUTDOOR
 RECEPTACLES. NEC 210.8
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2013-01-30 Cont ID  
Sent By fmittner Date 2013-01-30 Time 13:04 Rev Time 0.00
Received By fmittner Date 2013-01-30 Time 13:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-03-18 Cont ID  
Sent By jgomez Date 2013-03-18 Time 10:56 Rev Time 0.00
Received By jgomez Date 2013-03-07 Time 12:40 Sent To  
Notes
2013-03-07 12:40:36IN ELECTRIC BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-11 Cont ID  
Sent By rlecky Date 2013-02-11 Time 11:48 Rev Time 0.00
Received By rlecky Date 2013-01-30 Time 16:49 Sent To  
Notes
2013-01-31 16:50:09SENT TO R6 SHELF FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-02-11 Cont ID  
Sent By jgomez Date 2013-02-11 Time 10:45 Rev Time 0.00
Received By jgomez Date 2013-02-11 Time 10:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-01-30 Cont ID  
Sent By fmittner Date 2013-01-30 Time 13:04 Rev Time 0.00
Received By fmittner Date 2013-01-30 Time 13:04 Sent To  
Notes
***NONE***