Plan Review Details - Permit 13010847
Plan Review Stops For Permit 13010847
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-03-15 Cont ID  
Sent By jwitmer Date 2013-03-15 Time 16:57 Rev Time 0.00
Received By jwitmer Date 2013-03-15 Time 16:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-03-06 Cont ID  
Sent By shill Date 2013-03-06 Time 17:16 Rev Time 0.00
Received By shill Date 2013-03-06 Time 06:36 Sent To  
Notes
2013-03-06 17:18:22****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PLANS APPEAR CODE COMPLIANT.
  
 WHEN RESUBMITTING, PLEASE CREATE TWO (OR THREE)
 COLLATED SETS OF PLANS WHICH INCLUDE THE MOST CURRENT
 SHEETS FOR PERMIT ISSUANCE. REMOVED (OLD/PREVIOUS
 VERSION) SHEETS ARE TO REMAIN WITH THE PERMIT
 APPLICATION FOR REFERENCE AND SHOULD BE VOIDED.
  
 PLEASE CONTACT ME IF YOU NEED ASSISTANCE.
  
 2. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED,
 561-233-5025 FOR MORE INFORMATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-07 Cont ID  
Sent By jwitmer Date 2013-02-07 Time 16:24 Rev Time 0.00
Received By jwitmer Date 2013-02-07 Time 16:24 Sent To  
Notes
2013-02-07 16:34:45BUILDING PLAN REVIEW
 PERMIT: 13010847
 ADD: 550 S ROSEMARY # 158
 CONT: GREATER BAY INC
 TEL: (813)267-7391
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 FEB. 07/2013
 ACTION: DENIED
  
 1) PLEASE CORRECT THE ADDRESS ON THE PLANS TO 550 S
 ROSEMARY # 158 ON BOTH THE PLANS AND ENERGY
 CALCULATIONS.
  
 2) PLEASE CORRECT THE MINIMUM TYPE CONSTRUCTION, THIS
 BUILDING WAS BUILT UNDER THE 1994 SSBC CODE AS A TYPE
 II UNDER THE 2010 FBCTHE COMPARISON IS A TYPE I-B.
 PLEASE CORRECT ALL SHEETS THAT INDICATE THE 1994 SSBC
 TYPE II.
  
 3) SHEET A0.1 WINDICATES THE WIND DESIGN AS A 170 MPH
 ZONE BUT DOES NOT PROVIDE THE EXPOSURE TYPE NOR DOES
 THE PLANS PROVIDE PRESSURES POSITIVE/ NEGATIVE.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 3.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP.
  
 5) THE FLORIDA PRODUCT APPROVAL SUBMITTED FL 13407.R2
 SHEET 2 OF 10 PROVIDES TWO DESIN PRESSURES, ONE THAT IS
 FLUSH WITH SILL AND THE OTHER IS NOT, WHICH UNIT IS TO
 BE INSTALLED, THE PRESSURES ARE DIFFERENT. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) THE DOOR SCHEDULE IS FOUND ON A.01 DOOR # 6 IS A
 FIRE RATED DOOR THAT LEADS INTO A EXIT PASSAGE WAY, NO
 FIRE RATING HAS BEEN PROVIDED. 2010 FBC-B TABLE 715.4.
  
 7) SHEET A.02 PROVIDES DETAILS FOR FIRE RATED WALLS,
 BUT THE DETAILS DO NOT PROVIDE THE REQUIRED FIRE RATING
 FOR THE STRUCTURAL COLUMNS SEE 2010 FBC-B TABLE 601
 PRIMARY FRAMING MEMBERS 2 HR FOR TYPE IB.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-03-14 Cont ID  
Sent By rlecky Date 2013-03-14 Time 10:27 Rev Time 0.00
Received By rlecky Date 2013-03-14 Time 10:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-02-22 Cont ID  
Sent By rlecky Date 2013-02-22 Time 16:07 Rev Time 0.00
Received By rlecky Date 2013-02-22 Time 15:05 Sent To  
Notes
2013-02-22 16:07:1313010847
 550 S. ROSEMARY AVE. #158
 THE BRASS TAP
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 COMMENTS WHICH WERE NOT ADDRESSED ADEQUATELY WITHIN THE
 SECOND SUBMITTAL. IF REQUIRED PLEASE CALL FOR FURTHER
 CLARIFICATION.
  
 INDICATE THE SIZE OF THE PAD MOUNTED TRANSFORMER. NEC
 215.5
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS.
 THE DESIGNER NEEDS TO PROVIDE THE WORDING, SIZE AND
 LOCATIONS FOR ALL ELECTRICAL SAFETY SIGNAGE REQUIRED BY
 THE NATIONAL ELECTRICAL CODE. NEC 110.22, 110.16,
 110.22
  
 PROVIDE A LIGHTING DENSITY SUMMARY (ON THE PLANS)
 SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. THE LIGHTING SUMMARY REQUIRED WILL
 SHOW EACH AREA OF USE IN A TABLE FORMAT VERIFYING
 COMPLIANCE WITH THE ENERGY CODE FOR THE AREA AND IN
 TOTAL. FBC ENERGY CONSERVATION 505.3
  
 VERIFY SERVICE CAPACITY FROM THE MAIN SERVICE FOR THIS
 OCCUPANCY BY CALCULATION. INCLUDE EXISTING AND
 POTENTIAL FUTURE OCCUPANCY LOADS WHICH WILL BE SUPPLIED
 FROM THE EXISTING SERVICE. THE EXISTING SERVICE WHICH
 FORMERLY SERVED PREDOMINANTLY BUSINESS USES IS NOW
 BEING UTILIZED FOR SEVERAL NEW OR FUTURE RESTAURANTS.
 SERVICE CAPACITY NEEDS TO BE VERIFIED. NEC 215.2
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-02-13 Cont ID  
Sent By rlecky Date 2013-02-13 Time 11:18 Rev Time 0.00
Received By rlecky Date 2013-02-12 Time 12:51 Sent To  
Notes
2013-02-13 11:20:1813010847
 550 S. ROSEMARY AVE. #158
 THE BRASS TAP
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE AN ELECTRICAL RISER PLAN WHICH INCLUDES PANEL
 ?HV?. INDICATE THE SIZE OF THE PAD MOUNTED TRANSFORMER.
 PROVIDE A SYSTEM GROUNDING AND BONDING CONDUCTOR FOR
 THE TRANSFORMER. NEC 215.5
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS.
 NEC 110.22, 110.16, 110.22
  
 PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE
 WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC
 ENERGY CONSERVATION 505.3
  
 PROVIDE SAFE WORKING CLEARANCES AND DEDICATED WORKING
 SPACE AT ALL ELECTRICAL PANEL BOARDS AND TRANSFORMERS.
 INDICATE LOCATION OF TRANSFORMERS. PROVIDE A STRUCTURAL
 SUPPORT DETAIL FOR WALL OR CEILING MOUNTED
 TRANSFORMERS. NEC 110.26, 240.24
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS MUST
 BE GFCI PROTECTED. NEC 210.8
  
 INDICATE THE REQUIRED SAFE CLEARANCES TO THE CEILING
 FANS. NEC 110.3
  
 PROVIDE A STRUCTURAL DETAIL FOR SUPPORT OF THE HANGING
 TELEVISIONS. FBC 1604.1
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR VOICE/DATA,
 CABLE, POS, AND FIRE ALARM SYSTEMS.
  
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-03-20 Cont ID  
Sent By wjolin Date 2013-03-20 Time 13:19 Rev Time 0.00
Received By wjolin Date 2013-03-19 Time 14:35 Sent To  
Notes
2013-03-19 14:42:34550 SOUTH ROSEMARY AVENUE - SUITE #158
 PERMIT #13010847
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT (X2): ENGINEERED FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT. SECTION 105.3.1.2(2) OF
 THE FLORIDA BUILDING CODE REQUIRES SEALED FIRE
 PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OR
 ALTERATION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER
 FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-02-25 Cont ID  
Sent By wjolin Date 2013-02-25 Time 13:09 Rev Time 0.00
Received By wjolin Date 2013-02-25 Time 12:59 Sent To  
Notes
2013-02-25 13:09:28550 SOUTH ROSEMARY AVENUE - SUITE #158
 PERMIT #13010847
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: ENGINEERED FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT. SECTION 105.3.1.2(2) OF THE FLORIDA
 BUILDING CODE REQUIRES SEALED FIRE PROTECTION
 CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF
 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-02-02 Cont ID  
Sent By wjolin Date 2013-02-02 Time 19:40 Rev Time 0.00
Received By wjolin Date 2013-02-02 Time 19:10 Sent To  
Notes
2013-02-02 19:27:49550 SOUTH ROSEMARY AVENUE - SUITE #158
 PERMIT #13010847
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS. PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
 SHEET A1.1: PROVIDE FLOOR PAINT OR BARRIER AT OUTSIDE
 PATIO INDICATING THAT THIS IS A DESIGNATED EXIT PATH
 FROM INTERIOR EXIT DOOR #8 TO THE EXTERIOR GATE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-03-20 Cont ID  
Sent By jwitmer Date 2013-03-20 Time 13:44 Rev Time 0.00
Received By jwitmer Date 2013-03-19 Time 15:38 Sent To  
Notes
2013-03-19 15:39:28INCOMING SENT TO FIRE DESK FIRE SPRINKLER PLANS FOR
 MASTER. JW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-03-20 Cont ID  
Sent By jwitmer Date 2013-03-20 Time 13:44 Rev Time 0.00
Received By jwitmer Date 2013-03-11 Time 12:47 Sent To  
Notes
2013-03-12 12:50:22EXPEDITED, 3RD RUN
 C--5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-03-06 Cont ID  
Sent By shill Date 2013-03-06 Time 17:19 Rev Time 0.00
Received By shill Date 2013-02-20 Time 14:24 Sent To  
Notes
2013-02-21 14:37:24EXPEDITED, 2ND RUN
 C--5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-14 Cont ID  
Sent By eschneid Date 2013-02-14 Time 13:41 Rev Time 0.00
Received By lmartine Date 2013-01-29 Time 16:17 Sent To  
Notes
2013-01-29 16:19:43EXPEDITED
 C--5

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status N Date 2013-03-18 Cont ID  
Sent By jwitmer Date 2013-03-18 Time 14:53 Rev Time 0.00
Received By jwitmer Date 2013-03-18 Time 14:53 Sent To  
Notes
2013-03-18 14:54:45IMPACT FEE ASSESSMENT NO FEES DUE. SEE MUNICIPAL IMPACT
 FEE QUESTIONAIRE. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2013-03-15 Cont ID  
Sent By jwitmer Date 2013-03-15 Time 16:57 Rev Time 0.00
Received By jwitmer Date 2013-03-15 Time 16:57 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-03-15 Cont ID  
Sent By jwitmer Date 2013-03-15 Time 16:56 Rev Time 0.00
Received By jwitmer Date 2013-03-15 Time 16:56 Sent To  
Notes
2013-03-15 16:57:14BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-03-06 Cont ID  
Sent By shill Date 2013-03-06 Time 17:31 Rev Time 0.00
Received By shill Date 2013-03-06 Time 17:31 Sent To  
Notes
2013-03-06 17:40:40****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED.
 PLEASE CALL 561-233-5025 FOR MORE INFORMATION.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-02-25 Cont ID  
Sent By hmoser Date 2013-02-25 Time 10:39 Rev Time 0.00
Received By hmoser Date 2013-02-25 Time 10:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-02-01 Cont ID  
Sent By hmoser Date 2013-02-01 Time 15:22 Rev Time 0.00
Received By hmoser Date 2013-02-01 Time 13:07 Sent To  
Notes
2013-02-01 15:22:32MECHANICAL PLANS DENIED
 1) NOTE 21 ON PAGE M1.2 REQUEST THAT YOU PAINT EXPOSED
 DUCT.
 FIBERGLASS, FLEX OR DUCT WRAP CAN NOT BE PAINTED.
 PER SECTION 603.5 NONMETALLIC DUCT. AND THE MANUFACTURE
 OF THE DUCT .
 2) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS.
 FOR OUT DOOR AIR AND EXHAUST 2010 FBC (M) .
 3) ADDRESS ON THE ENERGY CALCULATION AND PLANS DO NOT
 MATCH.
 4) PROVIDE PRODUCT APPROVALS FOR THE FRESH AIR AND
 EXHAUST
 OUTSIDE LOUVERS.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-03-01 Cont ID  
Sent By lwagner Date 2013-03-01 Time 11:19 Rev Time 0.00
Received By lwagner Date 2013-03-01 Time 10:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-02-05 Cont ID  
Sent By lwagner Date 2013-02-05 Time 10:14 Rev Time 0.00
Received By lwagner Date 2013-02-05 Time 08:50 Sent To  
Notes
2013-02-05 10:13:06FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. THE BAR EQUIPMENT (HAND SINKS, ICE BINS, FLOOR
 DRAINS, BEER RINSE, ETC.) ARE NOT REQUIRED TO BE
 CONNECTED TO THE GREASE SYSTEM. PLEASE CONNECT TO THE
 SANITARY. PLEASE LEAVE THE KITCHEN ON THE INTERCEPTOR.
 FBC 2010 PLUMBING 2010 1003.2 APPROVAL:
 .....WASTES THAT DO NOT REQUIRE TREATMENT OR SEPARATION
 SHALL NOT BE DISCHARGED INTO ANY INTERCEPTOR OR
 SEPARATOR.
  
 2. A VENT IS REQUIRED BETWEEN THE LAST 2 WATER CLOSETS
 (THE H.C. CLOSETS) ON THE CIRCUIT VENT SYSTEM.
 911.2 VENT CONNECTION.
 THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN
 THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE
 SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR
 WASTE.911.2 VENT CONNECTION.
  
 3. SHEET P1.1 THE COLD WATER MAIN WILL BE REQUIRED TO
 BE 1" TO THE LAST FIXTURE IN THE RESTROOMS PER TABLE
 603.1 (OR PLEASE SHOW ALL FLOW CALCULATIONS ON PLAN).
 604.1 GENERAL.
 THE DESIGN OF THE WATER DISTRIBUTION SYSTEM SHALL
 CONFORM TO ACCEPTED ENGINEERING PRACTICE. METHODS
 UTILIZED TO DETERMINE PIPE SIZES SHALL BE APPROVED.
  
 4. PLEASE INCLUDE THE LOCATION AND SIZE OF THE WATER
 HEATER.
 107.3.5.1.3 PLUMBING 5. WATER HEATERS
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-02-14 Cont ID  
Sent By Eschneid Date 2013-02-14 Time 12:01 Rev Time 1.00
Received By eschneid Date 2013-02-14 Time 12:01 Sent To  
Notes
2013-02-14 13:38:50PASSED
  
 ****PLEASE BE AWARE THAT THIS USE IS AN ALCOHOLIC
 BEVERAGE ESTABLISHMENT******
2013-01-30 10:06:381/28/13


Account Summary | Usage Policy | Privacy Policy