2013-01-30 16:15:30BUILDING PLAN REVIEW
 PERMIT: 13010708
 ADD: 4115 GEORGIA AVE
 CONT: BAYSHORE OF SOUTH FLORIDA
 TEL: (561)691-9508
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A1:
  
 1A) BUILDING DATA UNDER THE HEADING OCCUPANCY GROUP IS
 LISTED AS A A-3 OCCUPANCY AND THE OCCUPANCY LOAD IS
 INDICATED AS 50 GROSS /W EQUIPMENT. NEITHER SHEET A1
 NOR A2 SHOW THE EQUIPMENT LAYOUT, NOR DOES THE PLAN
 INDICATE WHICH AREAS OF THE BUILDING WILL MAKE UP THE
 5846 SQ FT OF THE GYM. 2010 FBC TABLE 1004.1.1. THE
 PLANS AS NOT HAVING EQUIPMENT SHOWN WE SHOULD USE 15 SQ
 FT /OCCUPANT WHICH WILL PRODUCE A OCCUPANT LOAD OF 389.
  
 1B) THE BUILDING DATA FOUND ON THIS PAGE DECLARES THIS
 BUILDING TO BE A BUILDING TYPE 2A WHERE AS ON THE LIFE
 SAFETY SHEET THE BUILDING IS DECLARED AS A TYPE IIB
 (UNPROTECTED). DISCREPANCY, ADDITIONAL INFORMATION IS
 REQUIRED, 107.2.1.3.
  
  
 1C) SHEET A1. PLEASE PROVIDE THE ACCESSIBLE PATH FROM
 ACCESSIBLE PARKING SPACE # 17 TO THE ENTRANCE. 2010
 ACCESSIBILITY CODE 202.4 ALTERATIONS AFFECTING THE
 PRIMARY FUNCTION AREAS. PLEASE ALSO REVIEW 202.4.1
 DISPROPORTIONATE COST & 202.4.2 ACCESSIBLE FEATURES IN
 THE EVENT OF DISPROPORTIONALITY.
  
 2) SHEET A2 IS NOT SHOWING THE TOTAL TENANT SPACE,
 THERE IS APPROXIMATELY ANOTHER 80 LINIER FEET OF
 BUILDING NOT SHOWN. IT IS NOT CLEAR WHERE THE TENANT
 SEPERATION WALL WILL OCCUR OR IF THE PERSONNAL TRAINING
 ROOM IS PART OF THIS PROJECT, AGAIN WHAT OR HOW WILL
 THE OCCUPANT LOAD FOR THIS ARE ROOM BE CALCULATED. 2010
 FBC TABLE 1004.1.1.
  
 3) ON SHEET A2 THERE APPEARS TO BE A DISCREPANCY
 BETWEEN WHAT IS THERE NOW AND WHAT WAS SHOWN ON THE
 LAST KNOWN PERMIT WITH ELEVATIONS OF THE EAST WALL.
 PERMIT # 12050428 FOR NEW FRONT DOUBLE DOORS INDICATED
 ON THE LONG NARROW PORTION OF THE BUILDING FACING EAST
 3 LARGE OVER HEAD DOORS AND JALOUSE WINDOWS, ON SHEET
 A2 SLIDDING DOOR ARE SHOWN AND NO WINDOWS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 NOTE: 2010 EXST BLDG CODE 901.3 CHANGE OF OCCUPANCY
 CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
  
 4) 2010 EXST BLDG CODE 912.2 FIRE PROTECTION SYSTEMS.
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 912.2.1 AND 912.2.2.
 912.2.1 FIRE SPRINKLER SYSTEM.
  
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 2010 FBC-B F] 903.2.1.3 GROUP A-3. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE PROVIDED FOR GROUP A-3
 OCCUPANCIES WHERE ONE OF THE FOLLOWING CONDITIONS
 EXISTS:
 (2). THE FIRE AREA HAS AN OCCUPANT LOAD OF 300 OR MORE.
  
 5) 2010 EXST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION
 SYSTEM. WHERE A CHANGE IN OCCUPANCY CLASSIFICATION
 OCCURS THAT REQUIRES A FIRE ALARM AND DETECTION SYSTEM
 TO BE PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE
 WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING,
 SUCH SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE
 THE CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM
 NOTIFICATION APPLIANCES SHALL BE AUTOMATICALLY
 ACTIVATED THROUGHOUT THE BUILDING. WHERE THE BUILDING
 IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM, ALARM
 NOTIFICATION APPLIANCES SHALL BE PROVIDED THROUGHOUT
 THE AREA WHERE THE CHANGE OF OCCUPANCY OCCURS AND SHALL
 BE AUTOMATICALLY ACTIVATED.
  
 2010 FBC-B [F] 907.2.1 GROUP A.
 A MANUAL FIRE ALARM SYSTEM THAT ACTIVATES THE OCCUPANT
 NOTIFICATION SYSTEM IN ACCORDANCE WITH SECTION 907.5
 SHALL BE INSTALLED IN GROUP A OCCUPANCIES HAVING AN
 OCCUPANT LOAD OF 300 OR MORE. EXCEPTION: MANUAL FIRE
 ALARM BOXES ARE NOT REQUIRED WHERE THE BUILDING IS
 EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM
 INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.1 AND THE
 OCCUPANT NOTIFICATION APPLIANCES WILL ACTIVATE
 THROUGHOUT THE NOTIFICATION ZONES UPON SPRINKLER
 WATERFLOW.
  
 6) 2010 EXST BLDG CODE 912.3 INTERIOR FINISH. IN AREAS
 OF THE BUILDING UNDERGOING THE CHANGE OF OCCUPANCY
 CLASSIFICATION, THE INTERIOR FINISH OF WALLS AND
 CEILINGS SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING FOR THE NEW OCCUPANCY
 CLASSIFICATION.
  
 7) 2010 EXST BLDG CODE 912.4.1 MEANS OF EGRESS FOR
 CHANGE TO HIGHER HAZARD CATEGORY.
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 THE MAIN WORK OUT AREA SHOWN ON SHEET A2 & LS1 HAS TWO
 EXIT DOORS LEADING TO THE EXTERIOR THERE IS A 3RD DOOR
 THAT LEADS INTO A STORAGE AREA. THE TWO DOUBLE DOORS
 THAT LEAD TO THE EXTERIOR ARE NOT 1/2 OF THE DIAGONAL
 DISTANCE FOR THAT ROOM, PLEASE SEE 2010 FBC-B 1015.2.1
 TWO EXITS OR EXIT ACCESS DOORWAYS.
 WHERE TWO EXITS OR EXIT ACCESS DOORWAYS ARE REQUIRED
 FROM ANY PORTION OF THE EXIT ACCESS, THE EXIT DOORS OR
 EXIT ACCESS DOORWAYS SHALL BE PLACED A DISTANCE APART
 EQUAL TO NOT LESS THAN ONE-HALF OF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN
 EXIT DOORS...
  
 PLEASE NOTE THE DOOR THAT LEADS TO THE STORAGE ROOM AND
 TO THE EXTERIOR CAN NOT BE USED AS AN EXIT. 2010 FBC-B
 1014.2 EGRESS THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION. (4.) EGRESS SHALL NOT PASS THROUGH
 KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED FOR
 SIMILAR PURPOSES.
  
 8) PLANS DO NOT INDICATE THE TYPE OF HARDWARE FOR THE
 EXIT DOORS, NEITHER DOES THE CLOSED PERMIT 12050428 FOR
 THE FRONT DOORS. 2010 FBC-B 1008.1.10 PANIC AND FIRE
 EXIT HARDWARE. DOORS SERVING A GROUP H OCCUPANCY AND
 DOORS SERVING ROOMS OR SPACES WITH AN OCCUPANT LOAD OF
 50 OR MORE IN A GROUP A OR E OCCUPANCY SHALL NOT BE
 PROVIDED WITH A LATCH OR LOCK UNLESS IT IS PANIC
 HARDWARE OR FIRE EXIT HARDWARE.
  
 9) THE PLANS DO NOT PROVIDE THE TYPE OF FINISHES AND
 BASE MATERIALS TO BE INSTALLED IN THE RESTROOMS.
 2010 FBC-B 1210.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF URINALS
 AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM)
 ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 1210.3 SHOWERS.
 SHOWER COMPARTMENTS AND WALLS ABOVE BATHTUBS WITH
 INSTALLED SHOWER HEADS SHALL BE FINISHED WITH A SMOOTH,
 NONABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 70
 INCHES (1778 MM) ABOVE THE DRAIN INLET.
  
 10) SHEET A3 DOES NOT INDICATE WHAT TYPE OF SHEATHING
 OR BASE WILL BE USED FOR THE SHOWER WALLS, PLEASE
 REVIEW SECTIONS BELOW, ALSO THE PLANS INDICATE THE USE
 OF PAINTED MR BOARD FOR THE CEILINGS BUT THE THICKNESS
 OF THE GYPSUM BOARD IS NOT PROVIDED NOR IS THE SPAN FOR
 THE CEILING FRAMING PROVIDED IN THE SHOWERS, PLEASE
 PROVIDE DOCUMENTATION FOR CODE COMPLIANCE.
 2509.2 BASE FOR TILE.
 GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS,
 DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE
 SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT
 SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288
 OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
  
 2509.3 LIMITATIONS.
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED
 IN THE FOLLOWING LOCATIONS:
  
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
  
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
  
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16
 INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD.
  
 11) PLEASE REVIEW THE ADA-1 SHEET FOR THE ACCESSIBLE
 SHOWER COMPARTMENTS, IT IS NOT CLEAR IF THE DESIGNER IS
 TRYING TO COMPLY WITH THE 2010 ACCESSIBILITY CODE
 608.2.2 FOR A STANDARD ROLL IN TYPE SHOWER OR 608.2.3
 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENT. IF YOU ARE
 DESIGNING TO STANDARD ROLL-IN TYPE SHOWER COMPARTMENT
 THEN THE PLANS ARE NOT IN COMPLIANCE WITH 608.2.2.1.
  
 IF DESIGNED TO THE ALTERNATE ROLL-IN TYPE SHOWER, THE
 DESIGNER WILL NEED TO REVIEW SECTIONS THAT DEAL WITH:
 2010 ACCESSIBILITY CODE:
 608.3.3 POSITIONING AND LENGTH OF BACKING ,AND REQUIRED
 GRAB BARS AND THE REQUIRED LENGHT OF GRAB BARS
 608.4 SEAT LOCATION (OPTIONAL)
 608.5 CONTROLS STANDARD ROLL IN VS TRANSFER TYPE
 SHOWER?
 608.5.3 CONTROL LOCATIONS
 608.6 SHOWER SPRAY UNIT AND WATER
 608.7 THRESHOLDS
  
 12) 12) PLEASE REVIEW ADA-1 SHEET THE ACCESSIBLE
 SHOWERS AND THE BENCHES AT THE ENTRANCE TO THE SHOWERS.
 THESE ACCESSIBLE BENCHES WILL BE REQUIRED TO MEET THE
 REQUIREMENTS FOUND UNDER TTHE 2010 FL ACCESSIBILTY CODE
 903 1-7.
  
 13) PLEASE PROVIDE THE DIMENSION FROM TTHE BUILDING TO
 THE WEST PROPERTY LINE WALL TO SHOW COMPLIANCE WITH
 2010 EXST BLDG CODE 912.6 EXTERIOR WALL FIRE RATING,
 AND 912.6.1.
  
 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-02-07 Cont ID  
Sent By rlecky Date 2013-02-07 Time 16:36 Rev Time 0.00
Received By rlecky Date 2013-02-07 Time 16:29 Sent To  
Notes
2013-02-07 16:36:53STAMPED ONE SET. SECOND SET SIGNED OUT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-02-02 Cont ID  
Sent By wjolin Date 2013-02-02 Time 18:50 Rev Time 0.00
Received By wjolin Date 2013-02-02 Time 18:10 Sent To  
Notes
2013-02-02 18:28:124115 GEORGIA AVENUE
 PERMIT #13010708
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 THE NORTH HALF OF THE BUILDING SHOWING THE STORAGE AREA
 AND PERSONAL TRAINING ROOM WAS NOT SUBMITTED IN THE
 ARCHITECTURAL DRAWINGS.
  
 IN BUILDINGS NOT PROTECTED BY A SPRINKLER SYSTEM, THE
 MINIMUM SEPARATION DISTANCE BETWEEN TWO EXITS OR EXIT
 ACCESS DOORS SHALL BE NOT LESS THAN ONE-HALF THE LENGTH
 OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA BEING SERVED.
  
 PLANS DO NOT INDICATE ANY FIRE-RATED WALLS SEPARATING
 THE ASSEMBLY OCCUPANCIES FROM THE STORAGE OCCUPANCY.
 EACH NEW FIRE-RATED BARRIER SHALL BE PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER. PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY
 SHALL BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 PROVIDE A FURNITURE AND EQUIPMENT LAYOUT PLAN.
  
 NO FLAME SPREAD OR SMOKE DEVELOPMENT INFORMATION
 PROVIDED FOR INTERIOR WALL AND CEILING FINISH
 MATERIALS.
  
 PROVIDE A BREAKDOWN SHOWING THE ROOM SQUARE FOOTAGE
 AREAS AND THE OCCUPANT LOAD FACTORS USED FOR DETERMING
 OCCUPANT LOAD.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PERSONAL TRAINING ROOM SHALL NOT EXIT THROUGH A MORE
 HAZARDOUS ROOM (STORAGE).
  
 NO DOOR SCHEDULE OR HARDWARE INFORMATION PROVIDED. FOR
 ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR
 MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS
 TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES
 ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC
 HARDWARE.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 ELECTRICAL DRAWINGS DO NOT SHOW ANY CIRCUITRY SUPPLYING
 THE EXIT SIGNS.
  
 EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM
 OF 1? HOURS IN THE EVENT OF FAILURE OF NORMAL LIGHTING.
 EMERGENCY LIGHTING FACILITIES SHALL BE ARRANGED TO
 PROVIDE INITIAL ILLUMINATION THAT IS NOT LESS THAN AN
 AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, NOT LESS THAN
 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT
 FLOOR LEVEL.
  
 AT THIS TIME A THOROUGH AND COMPLETE PLAN REVIEW CANNOT
 BE PERFORMED DUE TO LACK OF PLAN INFORMATION.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-07 Cont ID  
Sent By rlecky Date 2013-02-07 Time 16:36 Rev Time 0.00
Received By rlecky Date 2013-01-25 Time 16:16 Sent To  
Notes
2013-01-28 16:22:50B13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-01-31 Cont ID  
Sent By jwitmer Date 2013-01-31 Time 09:54 Rev Time 0.00
Received By jwitmer Date 2013-01-31 Time 09:54 Sent To  
Notes
2013-01-31 09:55:06BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-01-31 Cont ID  
Sent By lwagner Date 2013-01-31 Time 10:11 Rev Time 0.00
Received By lwagner Date 2013-01-29 Time 15:51 Sent To  
Notes
2013-01-31 10:18:38FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 THE RESTROOMS AND OTHER PLUMBING FIXTURES APPEAR TO BE
 NEW. NO PLUMBING DRAWINGS WERE FOUND WITH THIS SET OF
 PLANS. IF THE FIXTURES ARE EXISTING, PLEASE INDICATE
 THIS ON THE PLANS.
  
 ***NOTE***
 SEPARATE PLUMBING APPLICATION, DRAWINGS, FEES AND
 PERMIT WOULD BE ACCEPTABLE ALSO.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692