Plan Review Details - Permit 13010668
Plan Review Stops For Permit 13010668
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-12-26 Cont ID  
Sent By skennedy Date 2013-12-26 Time 11:37 Rev Time 0.00
Received By skennedy Date 2013-12-26 Time 11:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-01-31 Cont ID  
Sent By rlecky Date 2013-01-31 Time 09:52 Rev Time 0.00
Received By rlecky Date 2013-01-31 Time 09:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-12-23 Cont ID  
Sent By rferguso Date 2013-12-23 Time 13:24 Rev Time 0.00
Received By rferguso Date 2013-12-23 Time 13:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-09-19 Cont ID  
Sent By wjolin Date 2013-09-19 Time 11:36 Rev Time 0.00
Received By wjolin Date 2013-09-19 Time 11:33 Sent To  
Notes
2013-09-19 11:36:015701 VILLAGE BOULEVARD
 PERMIT #13010668
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DELAYED-EGRESS LOCKING SYSTEMS SHALL COMPLY WITH THE
 REQUIREMENTS OF 7.2.1.6.1 (FLORIDA FIRE PREVENTION CODE
 - NFPA 101 WITH FLORIDA AMENDMENTS) WHEREBY THE
 BUILDING NEEDS TO BE PROTECTED THROUGHOUT BY EITHER AN
 APPROVED, SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM OR
 AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM.
  
 MAN-TRAPS/LOCKUPS SHALL COMPLY WITH THE REQUIREMENTS OF
 22.4.5 (FLORIDA FIRE PREVENTION CODE - NFPA 101 WITH
 FLORIDA AMENDMENTS).
  
 ***MET WITH TYCO SECURITY REPS SHERI WILLER AND RON
 BICKEL ON 09/19/13 TO DISCUSS MAN-TRAP/LOCK-UP
 REQUIRMENTS AND DELAYED EGRESS REQUIREMENTS. PLANS TO
 BE RESUBMITTED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-01-30 Cont ID  
Sent By wjolin Date 2013-01-30 Time 13:12 Rev Time 0.00
Received By wjolin Date 2013-01-30 Time 12:31 Sent To E
Notes
2013-01-30 13:12:345701 VILLAGE BOULEVARD
 PERMIT #13010668
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 INDICATE THE LOCATIONS OF THE MOTION SENSORS AND PUSH
 TO EXIT BUTTONS.
  
 INDICATE THE LOCATIONS OF THE EXISTING EXIT SIGNS.
  
 DELAYED-EGRESS LOCKING SYSTEMS SHALL COMPLY WITH THE
 REQUIREMENTS OF 7.2.1.6.1 (FLORIDA FIRE PREVENTION CODE
 - NFPA 101 WITH FLORIDA AMENDMENTS) WHEREBY THE
 BUILDING NEEDS TO BE PROTECTED THROUGHOUT BY EITHER AN
 APPROVED, SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM OR
 AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM.
  
 MAN-TRAPS/LOCKUPS SHALL COMPLY WITH THE REQUIREMENTS OF
 22.4.5 (FLORIDA FIRE PREVENTION CODE - NFPA 101 WITH
 FLORIDA AMENDMENTS).
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-12-26 Cont ID  
Sent By skennedy Date 2013-12-26 Time 11:37 Rev Time 0.00
Received By skennedy Date 2013-12-18 Time 17:54 Sent To  
Notes
2013-12-18 17:55:37SENT TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-09-19 Cont ID  
Sent By wjolin Date 2013-09-19 Time 11:36 Rev Time 0.00
Received By wjolin Date 2013-08-13 Time 13:58 Sent To  
Notes
2013-08-13 13:59:13INCOMING SENT TO FIRE BOX . JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-01-31 Cont ID  
Sent By rlecky Date 2013-01-31 Time 09:52 Rev Time 0.00
Received By rlecky Date 2013-01-28 Time 09:23 Sent To  
Notes
2013-01-28 09:23:43TO FIRE
  