Plan Review Details - Permit 13010628
Plan Review Stops For Permit 13010628
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-05-31 Cont ID  
Sent By jwitmer Date 2013-05-31 Time 09:18 Rev Time 0.00
Received By jwitmer Date 2013-05-31 Time 07:30 Sent To  
Notes
2013-05-31 09:19:48 
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 13010628
 ADD: 2471 OKEECHOBEE BLVD
 CONT: PARKWAY CONSTRUCTION
 TEL: (469)322-3758
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 PROVISOS ARE TO BE APPROVED BY THE BUILDING DEPARTMENT
 BEFORE THE FRAMING INSPECTION.
  
 1) SHEET A-0.1 & A1.0 BOTH INDICATE THE NEW GUARD RAIL
 BUT THE PLANS FAIL TO PROVIDE DETAILS FOR THE HANDRAIL
 REQUIREMENT PER 2010 ACCESSIBILITY CODE 405.8. BOTH
 SIDES OF THE RAMP!
  
 2) EITHER OR MOVE THE BILCO HATCH TO ROOF ZONE TWO OR
 PROVIDE ANOTHER ROOF HATCH THAT WILL MEET THE NEGATIVE
 PRESSURES OF -96.96. THE PLANS INDICATE A NEW ROOF
 HATCH, FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:(31)(A) ACCESS HATCHES. A INFORMATION SHEET
 ON BILCO HATCH WAS SUBMITTED AND A PRODUCT APPROVAL
 NUMBER NOA 11-0722.10 IS REFERENCED NO PRODUCT APPROVAL
 WAS SUBMITTED. I PRINTED OUT THE MIAMI-DADE NOA THE
 PRESSURES FOR THIS PRODUCT ARE =/- 70 PSF. SHEET A-4.0
 THE REAR ELEVATION INDICATES THERE IS NO REAR PARAPET
 WHICH CREATES A ROOF ZONE 3, THE LOCATION OF THE ROOF
 HATCH IS LOCATED IN THE ROOF ZONE 3 WITH THE -96.96
 PRESSURES WHICH EXCEEDS THE PRESSURES FOR THE PRODUCT
 APPROVAL.
  
 3) ROOF TOP GUARD RAIL SYSTEM LOCATED AT THE ROOF HATCH
 WILL REQUIRE SHOP DRAWINGS TO BE REVIEWED BY THE
 DESIGNER OF RECORD BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT. 2010 FBC-B 1013.5 & 1013.6.
  
 4) PLEASE PROVIDE PRODUCT APPROVAL FOR ROOFTOP
 PREFABRICATED A/C CONDENSER STANDS FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS: (31)((G) PRE-ENGINEERED
 A/C STANDS.
  
 5) AWNINGS ARE TO BE SUBMITTED UNDER SEPARATE PERMIT,
 WITH ASSOCIATE FEES & REVIEW. NOTE
 ENGINEERED AWNINGS SYSTEMS MUST BE SIGNED & SEALED
 ORIGINAL SIGNATURES. PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 6) A ROOFING PERMIT WILL BE REQUIRED FOR ALL ROOF WORK
 ASSOCIATED FOR THE NEW OPENINGS WITHIN THE ROOF AND
 CURBS THAT ARE BEING INSTALLED. FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)(D) NOTE:
 FLAT DECKS PLEASE IDENTIFY WHICH SUB-SYSTEM WILL BE
 APPLIED, CIRCLE THE SYSTEM TYPE AND MAXIMUM PRESSURES
 FOR ROOF ZONE 1. IF THE PRESSURES ARE HIGHER IN ZONES 2
 & 3 VERIFY LIMITATIONS TO SEE IF ENHANCED FASTENING CAN
 BE TAKEN AND IF RAS 117 CALCULATIONS ARE REQUIRED BY A
 DESIGN PROFESSIONAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-05-30 Cont ID  
Sent By jwitmer Date 2013-05-30 Time 15:02 Rev Time 0.00
Received By jwitmer Date 2013-05-23 Time 09:30 Sent To  
Notes
2013-05-23 09:33:42BUILDING PLAN REVIEW
 PERMIT: 13010628
 ADD: 2471 OKEECHOBEE BLVD
 CONT: TBD/ PARKWAY CONSTRUCTION
 TEL: (469)322-3758
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 MAY 30/2013
 ACTION:
  
  
  
 1) COMPLIED. ADDRESS 2471 OKEECHOBEE BLVD SUITE "A".
  
 2) COMPLIED.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6) 3RD REQUEST SHEET A-0.1 & A1.0 BOTH INDICATE THE NEW
 GUARD RAIL BUT THE PLANS FAIL TO PROVIDE DETAILS FOR
 THE HANDRAIL REQUIREMENT PER 2010 ACCESSIBILITY CODE
 405.8. BOTH SIDES OF THE RAMP!
  
 7) SHEET A-3.1 & A-7.1:
 7A1) 3RD REQUEST. THE PLANS INDICATE A NEW ROOF HATCH,
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:(31)(A)
 ACCESS HATCHES. A INFORMATION SHEET ON BILCO HATCH WAS
 SUBMITTED AND A PRODUCT APPROVAL NUMBER NOA 11-0722.10
 IS REFERENCED NO PRODUCT APPROVAL WAS SUBMITTED. I
 PRINTED OUT THE MIAMI-DADE NOA THE PRESSURES FOR THIS
 PRODUCT ARE =/- 70 PSF. SHEET A-4.0 THE REAR ELEVATION
 INDICATES THERE IS NO REAR PARAPET WHICH CREATES A ROOF
 ZONE 3, THE LOCATION OF THE ROOF HATCH IS LOCATED IN
 THE ROOF ZONE 3 WITH THE -96.96 PRESSURES WHICH EXCEEDS
 THE PRESSURES FOR THE PRODUCT APPROVAL.
  
 7A)(2) 2RD REQUEST, PLEASE ALSO REVIEW GUARDS 1013.6
 AND 1013.5. THE LITERATURE SUBMITTED WAS NOT LEGIBLE,
 DID NOT PROVIDE WHAT THE HEIGHT OF THIS GAURDRAIL.
 GAURDS MUST ALSO MEET THE STRENGTH REQUIREMENTS OF
 1607.1.1. THIS CAN BE A ITEM LISTED WITH A PROVISO:
 SHOP DRAWINGS TO FOLLOW MEETING THESE CONDITIONS.
  
 7B) SEMI-COMPLIED. THE RESPONCE DOES PROVIDE DETAILS ON
 RAISED CURB DETAILS THAT WERE TESTED TO THE MIAMI-DADE
 PROTOCAL, BUT THE ACTUAL MIAMI-DADE PRODUCT APPROVALS
 HAVE NOT BEEN PROVIDED, THERE ARE (6) LISTED FOR THYBAR
 ROOF CURBS. A-7.1 & M1.3 BOTH INDICATE A DETAIL FOR
 RAISED CURBS, PLEASE PROVIDE THE PRODUCT APPROVAL FOR
 THE NEW CURB THAT IS BEING INSTALLED FOR A/C UNIT #4.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
  
 7C) COMPLIED.
  
 7D)COMPLIED.
  
 7E) 3RD REQUEST. WE PRINTED OUT THE FL 14209 REPORT IT
 IS FOR THE 2007 FBC NOT THE CURRENT 2010 FBC, WE ALSO
 CHECKED THE MIAMI-DADE SITE FOR PRODUCT LISTED UNDER
 PRECISION ALIMINUM PRODUCTS AND THERE WERE NO CURRENT
 REPORTS LISTED ON EITHER WEB-SITE. A/C STANDS FOR ROOF
 TOP CONDENSORS. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)((G) PRE-ENGINEERED A/C STANDS.
  
 7F) COMPLIED. PRINTED THE PRODUCT APPROVAL FOR JMB PIPE
 PROP ADJUSTABLE PVC PIPE STAND NOA 11-1019.05.
  
 8A) 3RD REQUEST , A ROOFING PERMIT WILL BE REQUIRED FOR
 ALL ROOF REPAIRS FOR THE NEW OPENINGS WITHIN THE ROOF
 AND CURBS THAT ARE BEING INSTALLED. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS: FLAT DECK RESPONCE
 INDICATES A PRODUCT APPROVAL FL # 10124.1 WHICH IS FOR
 GAF ASPHALT ROOF SHINLES, THIS ROOF IS A FLAT DECK,
 SHINGLES CAN'T BE USED WHEN SLOPES ARE LESS THAN 2:12.
  
 8B) AWNING DETAILS METAL ROOFS, RESPONCE INDICATES AN
 ENGINEERED AWNING SYSTEM. IF THESE ARE TO BE CONSIDERED
 AWNINGS, THEY ARE UNDER SEPERATE PERMIT, THE
 ENGINEERING WILL NEED TO BE ORIGINAL SIGNED AND SEALED
 DRAWINGS. PLEASE ALSO SUBTRACT THE AMOUNT OF THE
 AWNINGS OUT OF THIS PERMIT SO IT WILL BE APPLIED TO THE
 SEPERATE AWNING PERMIT. PROVISO.
  
 9-14) COMPLIED.
  
 15) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-03-18 Cont ID  
Sent By jwitmer Date 2013-03-18 Time 15:46 Rev Time 0.00
Received By jwitmer Date 2013-03-18 Time 15:46 Sent To  
Notes
2013-03-18 16:55:40BUILDING PLAN REVIEW
 PERMIT: 13010628
 ADD: 2471 OKEECHOBEE BLVD
 CONT: TBD/ PARKWAY CONSTRUCTION
 TEL: (469)322-3758
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 MARCH 18/2013
 ACTION: DENIED
  
 1)2ND REQUEST, THE ADDRESS PROVIDED ON THE PLANS AS
 WELL AS THE PERMIT APPLICATION IS THE SITE ADDRESS FOR
 THE WHOLE PARCEL. THIS TENANT EITHER HAS AN INDIVIDUAL
 STREET ADDRESS OR A SUITE NUMBER TO IDENTIFY THE
 INDIVIDUAL TENANT SPACE FOR INSPECTION PURPOSES,
 RECORDS, RECORD RETENSION AS WELL AS EMERGENCIES. 105.3
 ACTION ON APPLICATION WPB AMENDMENTS TO ADMINISTRATIVE
 CODE, CHAPTER 1/ 2010 FBC. PLEASE SEE P B COUNTY
 PROPERTY APPRAISERS WEB SITE, PUT IN THE PCN
 74-4343-19-08-000-0010 AND THE WHOLE SITE COMES UP WITH
 2471 FOR A SITE ADDRESS. 18.2417 ACRES AND 235501 TOTAL
 SQUARE FEET.
  
 2) SEMI-COMPLIED, WILL NEED TO CHANGE EITHER THE
 ADDRESS OR THE SQUARE FEET OF THE PROJECT, AREA ENTERED
 FROM PLANS IS 13,314 SF. CHANGE OF OCCUPANCY FROM
 MERCANTILE TO A2 ASSEMBLY, ENERGY CALCULATIONS
 REQUIRED, 2010 FBC-ENERGY CODE 913.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) 2ND REQUEST, SEMI COMPLIED. SHEET A-0.1 & S-2.0 BOTH
 INDICATE A NEW DOORWAY AND ACCESSIBLE RAMP. PLEASE
 REVIEW TTHE 2010 ACCESSIBILITY CODE 405.7.4.RAMPS,
 CHANGE IN DIRECTION. THE PLAN DOES NOT INDICATE A
 BOTTOM LANDING, IS THERE ENOUGH ROOM? 2010
 ACCESSIBILITY 405.7.
 SHEET S-2.0 THE RAMP SHOWS A WIDTH DIMENSION OF 5'-0"
 AN OVER ALL DIMENSION CROSS SECTION WAY, THE
 ACCESSBILITY CODE REQUIRES A 5'-0" X 5'-0" CLEAR
 LANDING 2010 ACCESSIBILITY CODE 405.7.4.
  
  
  
  
  
 6) 2ND REQUEST SHEET A-0.1 & A1.0 BOTH INDICATE THE NEW
 GAURD RAIL BUT THE PLANS FAIL TO PROVIDE DETAILS FOR
 THE HANDRAIL PER 2010 ACCESSIBILITY CODE 405.8.
  
 7) SHEET A-3.1 & A-7.1:
 7A1) 2ND REQUEST, THE PLANS INDICATE A NEW ROOF HATCH,
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:(31)(A)
 ACCESS HATCHES. A INFORMATION SHEET ON BILCO HATCH WAS
 SUBMITTED AND A PRODUCT APPROVAL NUMBER NOA 11-0722.10
 IS REFERENCED NO PRODUCT APPROVAL WAS SUBMITTED.
  
 7A)(2) 2ND REQUEST, PLEASE ALSO REVIEW GUARDS 1013.6.
  
 7B) COMPLIED. A-7.1 & M1.3 BOTH INDICATE A DETAIL FOR
 RAISED CURBS, PLEASE PROVIDE THE PRODUCT APPROVAL FOR
 THE NEW CURB THAT IS BEING INSTALLED FOR A/C UNIT #4.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
  
 7C) COMPLIED. THE PLANS INDICATE THE EXISTING CURBS ARE
 TO HAVE AN ADAPTOR OVER THE EXISTING CURB, PLEASE
 PROVIDE THE MANUFACTURERS SPECIFICATIONS .HOW THEY WILL
 BE SECURED TO THE EXISTING CURB? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 7D)COMPLIED. A-7.1 DETAIL # 3 INDICATES THE USE OF WOOD
 SLEEPERS AND PITCH PANS, THIS HAS NOT BEEN ALLOWED IN
 FLORIDA SINCE THE 2001 FBC. 2010 FBC-B TABLE 1509.7
 PROVIDES THE REQUIRED HEIGHT OF THE UNIT ABOVE THE ROOF
 COVERING DEPENDING ON THE WIDTH OF THE UNIT.
  
 7E) COMPLIED. A/C STANDS FOR ROOF TOP CONDENSORS.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)((G)
 PRE-ENGINEERED A/C STANDS.
  
 7F) 2ND REQUEST ROOF TOP BLOX, AN ENGINEERING LAB TEST
 REULTS WERE SUBMITTED IT APPEARS TO BE A SITE SPECIFIC
 CASE IN ELLINGTON, MAINE FOR A 150 MPH WIND ZONE. WE DO
 ACCESPT NATIONALLY RECONIZED REPORTS FROM THE ICC ER
 REPORTS, ERS REPORTS ETC, PLEASE PROVIDE A CURRENT
 REPORT FROM A NATIONALLY RECONIZED TESTING AGENCY. THE
 REPORT SUBMITTED FOR ROOF TOP BLOX INDICATES THE WIND
 TEST WAS FOR 150 MPH, WE ARE LOCATED IN A 170 MPH WIND
 ZONE.
  
 8) 2ND REQUEST , A ROOFING PERMIT WILL BE REQUIRED FOR
 ALL ROOF REPAIRS FOR THE NEW OPENINGS WITHIN THE ROOF
 AND CURBS THAT ARE BEING INSTALLED. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES FLAT ROOF
 REPAIR AS WELL AS THE METAL FOR THE AWNING DETAIL.
  
 9) DISCREPANCY SHEET A4.0 LIST THE EXTERIOR OF THE
 BUILDING TO RECEIVE A 3 COAT STUCCO APPLICATION, SHEET
 A7.2 DETAIL # 12 INDICATES THE USE OF PAREX AND A
 ERS-2564 REPORT WAS SUBMITTED FOR A ONE COAT STUCCO
 SYSTEM, WHICH SYSTEM IS CORRECT?
  
 10-14) COMPLIED.
  
 15) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-02-08 Cont ID  
Sent By jwitmer Date 2013-02-08 Time 15:15 Rev Time 0.00
Received By jwitmer Date 2013-02-08 Time 10:11 Sent To  
Notes
2013-02-08 10:15:07BUILDING PLAN REVIEW
 PERMIT: 13010628
 ADD: 2471 OKEECHOBEE BLVD
 CONT: TBD/ PARKWAY CONSTRUCTION
 TEL: (469)322-3758
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 FEB. 08/2013
 ACTION: DENIED
  
 1) THE ADDRESS PROVIDED ON THE PLANS AS WELL AS THE
 PERMIT APPLICATION IS THE SITE ADDRESS FOR THE WHOLE
 PARCEL. THIS TENANT EITHER HAS AN INDIVIDUAL STREET
 ADDRESS OR A SUITE NUMBER TO IDENTIFY THE INDIVIDUAL
 TENANT SPACE FOR INSPECTION PURPOSES, RECORDS, RECORD
 RETENSION AS WELL AS EMERGENCIES. 105.3 ACTION ON
 APPLICATION WPB AMENDMENTS TO ADMINISTRATIVE CODE,
 CHAPTER 1/ 2010 FBC.
  
 2) CHANGE OF OCCUPANCY FROM MERCANTILE TO A2 ASSEMBLY,
 ENERGY CALCULATIONS REQUIRED, 2010 FBC-ENERGY CODE 913.
  
 3) THESE PLANS APPEAR TO HAVE VARIOUS DETAILS THAT MAY
 NOT BE APPLICABLE TO THIS PERMIT. IF THE DETAILS DO NOT
 SERVE THIS PROJECT PLEASE EITHER DELETE THE DETAIL OF
 CROSS THEM OUT. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. WPB ADMINMENTS TO THE ADMINISTRTIVE CODE
 2010.
  
 4) SHEET A1.0 & A1.1 DETAIL # 3 INDICATES A STAGE.
 NOTES INDICATE THE STAGE TO BE BUILT BY OTHERS, WILL
 THE DESIGN OF THE STAGE BE PART OF THE DESIGNER OF
 RECORDS PERMIT SET OF DRAWINGS? IF IT IS NOT THEN IT
 SHOULD NOT BE IN THIS PACKAGE. THERE ARE TWO ISSUES AT
 HAND WITH THE STAGE;
 4A) NO PLANS INDICATING THE TYPE OF MATERIALS THE STAGE
 IS TO BE CREATED FROM, NOR IS THE HEIGTH OF THE STAGE
 PROVIDED? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
 4B) HOW VERTICAL ACCESSIBILITY WILL BE ADDRESSED. 2010
 FBC ACCESSIBILITY 201.1.1.
  
 5) SHEET A-0.1 & S-2.0 BOTH INDICATE A NEW DOORWAY AND
 ACCESSIBLE RAMP. PLEASE REVIEW TTHE 2010 ACCESSIBILITY
 CODE 405.7.4.RAMPS, CHANGE IN DIRECTION. THE PLAN DOES
 NOT INDICATE A BOTTOM LANDING, IS THERE ENOUGH ROOM?
 2010 ACCESSIBILITY 405.7.
  
 6) SHEET A-0.1 & A1.0 BOTH INDICATE THE NEW HANDRAIL
 BUT THE PLANS FAIL TO PROVIDE DETAILS FOR THE HANDRAIL
 PER 2010 ACCESSIBILITY CODE 405.8.
  
 7) SHEET A-3.1 & A-7.1:
 7A) THE PLANS INDICATE A NEW ROOF HATCH, FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:(31)(A) ACCESS
 HATCHES. PLEASE ALSO REVIEW GUARDS 1013.6.
  
 7B) A-7.1 & M1.3 BOTH INDICATE A DETAIL FOR RAISED
 CURBS, PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE NEW
 CURB THAT IS BEING INSTALLED FOR A/C UNIT #4. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
  
 7C) THE PLANS INDICATE THE EXISTING CURBS ARE TO HAVE
 AN ADAPTOR OVER THE EXISTING CURB, PLEASE PROVIDE THE
 MANUFACTURERS SPECIFICATIONS .HOW THEY WILL BE SECURED
 TO THE EXISTING CURB? 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 7D) A-7.1 DETAIL # 3 INDICATES THE USE OF WOOD SLEEPERS
 AND PITCH PANS, THIS HAS NOT BEEN ALLOWED IN FLORIDA
 SINCE THE 2001 FBC. 2010 FBC-B TABLE 1509.7 PROVIDES
 THE REQUIRED HEIGHT OF THE UNIT ABOVE THE ROOF COVERING
 DEPENDING ON THE WIDTH OF THE UNIT.
  
 7E) A/C STANDS FOR ROOF TOP CONDENSORS. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS: (31)((G)
 PRE-ENGINEERED A/C STANDS.
  
 7F) ROOF TOP BLOX, AN ENGINEERING LAB TEST REULTS WERE
 SUBMITTED IT APPEARS TO BE A SITE SPECIFIC CASE IN
 ELLINGTON, MAINE FOR A 150 MPH WIND ZONE. WE DO ACCESPT
 NATIONALLY RECONIZED REPORTS FROM THE ICC ER REPORTS,
 ERS REPORTS ETC, PLEASE PROVIDE A CURRENT REPORT FROM A
 NATIONALLY RECONIZED TESTING AGENCY.
  
 8) A ROOFING PERMIT WILL BE REQUIRED FOR ALL ROOF
 REPAIRS FOR THE NEW OPENINGS WITHIN THE ROOF AND CURBS
 THAT ARE BEING INSTALLED. FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES FLAT ROOF
 REPAIR AS WELL AS THE METAL FOR THE AWNING DETAIL.
  
 9) THE SHEET A-7.2 INDICATES THE USE OF EFIS WALL
 INSULATION AND WALL FINISHES, PLEASE PROVIDE THE
 PRODUCT APPROVAL FOR EFIS WALL SYSTEMS. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(C) , EFIS SYSTEMS,
  
 10) SHEET A-7.4 DETAIL # 13 BOOTHS BY OTHERS. PLEASE
 PROVIDE WHAT TYPE OF MATERIALS WILL BE USED IN COVERING
 THE BOOTHS. 2010 FBC-B 806.4.
  
 11) SHEET A-8.0 THE DOOR SCHEDULE ALL EXIT DOORS WILL
 REQUIRE PANIC HARDWARE IT APPEARS DOOR # 1 & 7 DO NOT
 INDICATE PANIC HARDWARE IN THE HARDWARE SCHEDULE. DOOR
 # 3 INDICATES EXISTING AND DOES NOT LIST ANY HARDWARE.
 2010 FBC-B 1008.1.10.
  
 12) SHEET A-9.2 PLEASE REVIEW THE MENS & WOMENS
 HANDICAPPED STALL REQUIREMENTS, 2010 FLORIDA
 ACCESSIBILITY CODE REQUIRES THE LAV TO BE IN THE SAME
 TOILET COMPARTMENT,
 SEE 604.8.1.6, 604.8.1.7
  
 13) SHEET A-9.2 INDICATE THE RESTROOMS TO HAVE A TILE
 FINISH ON THE WALLS BUT THE PLANS DO NOT PROVIDE WHAT
 TYPE OF BACKER BOARD IS TO BE INSTALLED. SEE:
 13A) 210.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF URINALS
 AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM)
 ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
 13B) 2509.2 BASE FOR TILE.
 GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS,
 DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE
 SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT
 SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288
 OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
  
 14) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 14.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 14.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 14.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 14.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 14.5) COMPONENTS & CLADDING PRESSURES POSITVE &
 NEGATIVE TABLE 1609.2(2) . PROVIDE PRESSURES FOR ZONES
 1-5 ROOF & WALL ZONES.
  
 15) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-03-22 Cont ID  
Sent By rlecky Date 2013-03-22 Time 12:56 Rev Time 0.00
Received By rlecky Date 2013-03-22 Time 12:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-02-14 Cont ID  
Sent By rlecky Date 2013-02-14 Time 08:53 Rev Time 0.00
Received By rlecky Date 2013-02-13 Time 15:51 Sent To  
Notes
2013-02-14 08:53:1613010628
 2471 OKEECHOBEE BLVD
 CHUCK E CHEESE
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS.
 NEC 110.22, 110.16, 110.22
  
 PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE
 WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC
 ENERGY CONSERVATION 505.3
  
 PROVIDE AND ILLUSTRATE THE SAFE WORKING CLEARANCES AND
 DEDICATED WORKING SPACE AT ALL ELECTRICAL PANEL BOARDS
 AND TRANSFORMERS. NEC 110.26, 240.24
  
 REVISE ELECTRICAL SERVICE RISER PLAN TO SHOW FEEDERS
 WITH 400 AMP CAPACITY. NEC 215.5, T310.16
  
 REVISE MDP SCHEDULE TO REFLECT THE APPROPRIATE OVER
 CURRENT PROTECTION FOR THE FEEDER TO THE ELECTRICAL
 PANELS. NEC 240.4, T. 310.16
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR VOICE/DATA,
 CABLE, POS, AND FIRE ALARM SYSTEMS.
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-05-18 Cont ID  
Sent By wjolin Date 2013-05-18 Time 18:57 Rev Time 0.00
Received By wjolin Date 2013-05-18 Time 18:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-03-16 Cont ID  
Sent By wjolin Date 2013-03-16 Time 18:50 Rev Time 0.00
Received By wjolin Date 2013-03-16 Time 18:35 Sent To  
Notes
2013-03-16 18:50:162471 OKEECHOBEE BOULEVARD - #777
 PERMIT #13010628
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: SHEET LS.1: UPDATE THE CODE LIST TO
 REFERENCE THE 2010 EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF BOTH
 NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 REPEAT COMMENT: SHEET D1.0: ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. SMOKING SHALL BE PROHIBITED EXCEPT IN
 DESIGNATED EXTERIOR AREAS. ALL OTHER DEMOLITION OR
 CONSTRUCTION AREAS SHALL HAVE "NO SMOKING" SIGNS
 POSTED. WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES
 FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 REPEAT COMMENT: SHEET D1.0: FIRE PROTECTION SYSTEMS
 SHALL REMAIN ACTIVE DURING DEMOLITION AND RENOVATION
 ACTIVITIES. IN THE EVENT A FIRE PROTECTION SYSTEM IS
 OUT OF SERVICE FOR MORE THAN 4-HOURS IN A 24-HOUR
 PERIOD, THE BUILDING SHALL BE PLACED UNDER A FIRE
 WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED IN
 WRITING (FAX: 561-804-4774) AND APPROVED BY THE OFFICE
 OF THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 REPEAT COMMENT: EVERY ASSEMBLY OCCUPANCY ROOM NOT
 HAVING FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE
 ROOM POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT
 FROM THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE
 NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM.
  
 REPEAT COMMENT: INDICATE THE FLAME SPREAD AND SMOKE
 DEVELOPEMENT CLASSIFICATION OF WALL AND CEILING
 FINISHES.
  
 REPEAT COMMENT: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED
 EXIT DOORS WITH EXIT SIGNS.
  
 REPEAT COMMENT: ENGINEERED FIRE ALARM AND FIRE
 SPRINKLER CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A
 GENERAL BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS
 BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
  
 REPEAT COMMENT: PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
 REPEAT COMMENT: PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES AS NEW ASSEMBLY OCCUPANCIES WITH AN OCCUPANT
 LOAD EXCEEDING 300 OCCUPANTS SHALL RECEIVE FIRE ALARM
 NOTIFICATION BY VISIBLE SIGNALS AND VOICE
 ANNOUNCEMENTS. REFERENCE SECTION 12.3.4.3.3 OF FLORIDA
 FIRE PREVENTION CODE - NFPA 101
  
 REPEAT COMMENT: PROVIDE A PRE-RECORDED FIRE ALARM
 EVACUATION MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS
 BEEN REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT,
 AND EXIT THE BUILDING IMMEDIATELY.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM, FIRE ALARM SYSTEM, KITCHEN EXHAUST HOOD, AND
 KITCHEN HOOD FIRE SUPPRESSION SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-02-04 Cont ID  
Sent By wjolin Date 2013-02-04 Time 14:10 Rev Time 0.00
Received By wjolin Date 2013-02-04 Time 13:29 Sent To  
Notes
2013-02-04 14:10:502471 OKEECHOBEE BOULEVARD - #777
 PERMIT #13010628
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET LS.1: UPDATE THE CODE LIST TO REFERENCE THE 2010
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 SHEET D1.0: ALL CONSTRUCTION AND DEMOLITION WORK SHALL
 CONFORM TO THE REQUIREMENTS OF NFPA 241. SMOKING SHALL
 BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 SHEET D1.0: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE
 DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE
 EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR
 MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE SUBMITTED IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 INDICATE THE FLAME SPREAD AND SMOKE DEVELOPEMENT
 CLASSIFICATION OF WALL AND CEILING FINISHES.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 SHEET E1.1: PLANS APPEAR TO SHOW ONLY 6 EMERGENCY
 LIGHTING FIXTURES.
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PROVIDE SPEAKER/STROBE NOTIFICATION APPLIANCES AS NEW
 ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING
 300 OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY
 VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS. REFERENCE
 SECTION 12.3.4.3.3 OF FLORIDA FIRE PREVENTION CODE ?
 NFPA 101
  
 PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE
 NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN
 THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM, FIRE ALARM SYSTEM, KITCHEN EXHAUST HOOD, AND
 KITCHEN HOOD FIRE SUPPRESSION SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2013-03-08 Cont ID  
Sent By lwagner Date 2013-03-08 Time 10:01 Rev Time 0.00
Received By lwagner Date 2013-03-07 Time 14:20 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2013-02-07 Cont ID  
Sent By lwagner Date 2013-02-07 Time 15:53 Rev Time 0.00
Received By lwagner Date 2013-02-07 Time   Sent To  
Notes
2013-02-07 15:53:05FBC 2010 FUEL GAS REVIEW #1
 DENIED:
  
 SHEET MEP 1.1 , P5.1 SHOWS REGULATORS WITH A SHUTOFF
 VALVE DOWNSTREAM.
 409.4 MP REGULATOR VALVES.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-05-31 Cont ID  
Sent By jwitmer Date 2013-05-31 Time 10:19 Rev Time 0.00
Received By jwitmer Date 2013-05-02 Time 09:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-03-22 Cont ID  
Sent By rlecky Date 2013-03-22 Time 12:57 Rev Time 0.00
Received By rlecky Date 2013-03-04 Time 10:29 Sent To  
Notes
2013-03-05 10:29:22C26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-02-14 Cont ID  
Sent By rlecky Date 2013-02-14 Time 08:54 Rev Time 0.00
Received By rlecky Date 2013-01-23 Time 09:18 Sent To  
Notes
2013-01-29 09:19:25SENT TO C13 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status N Date 2013-06-04 Cont ID  
Sent By jwitmer Date 2013-06-04 Time 13:22 Rev Time 0.00
Received By jwitmer Date 2013-06-04 Time 13:22 Sent To  
Notes
2013-06-04 13:23:46P B COUNTY IMPACT FEE ASSESSMENT
 BY: WILLIAM M SWOOPE
 NO FEES SEE STAMP ON PLANS. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2013-05-30 Cont ID  
Sent By jwitmer Date 2013-05-30 Time 15:00 Rev Time 0.00
Received By jwitmer Date 2013-05-30 Time 15:00 Sent To  
Notes
2013-05-30 15:00:29BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-03-19 Cont ID  
Sent By jwitmer Date 2013-03-19 Time 14:27 Rev Time 0.00
Received By jwitmer Date 2013-03-19 Time 14:27 Sent To  
Notes
2013-03-19 14:28:10BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-02-08 Cont ID  
Sent By jwitmer Date 2013-02-08 Time 15:14 Rev Time 0.00
Received By jwitmer Date 2013-02-08 Time 15:14 Sent To  
Notes
2013-02-08 15:15:05BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-03-22 Cont ID  
Sent By hmoser Date 2013-03-22 Time 08:49 Rev Time 0.00
Received By hmoser Date 2013-03-22 Time 08:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-02-08 Cont ID  
Sent By hmoser Date 2013-02-08 Time 13:18 Rev Time 0.00
Received By hmoser Date 2013-02-08 Time 10:39 Sent To  
Notes
2013-02-08 13:17:53MECHANICAL PLANS DENIED
 1) PROVIDE HEAT & COOLING LOADS WITH THE PLANS
 PER SECTION 503.2.1 FLORIDA ENERGY CODE 2010
 2) REFER TO SECTION503.2.4.4 SHUT OFF DAMPER CONTROLS.
 2010 FLORIDA ENERGY CODE.
 3) PROVIDE DUCT SIZE ON ALL EXHAUST DUCT.
 PER SECTION 107 FBC.
 4) PROVIDE A DETAIL ON THE RTU TO CURB TIE DOWN FROM
 THE
 ENGINEER. PER SECTION 301.12 WIND RESISTANCE 2010 FBC
 (M)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-03-08 Cont ID  
Sent By lwagner Date 2013-03-08 Time 10:56 Rev Time 0.00
Received By lwagner Date 2013-03-07 Time 14:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-02-08 Cont ID  
Sent By lwagner Date 2013-02-08 Time 10:36 Rev Time 0.00
Received By lwagner Date 2013-02-06 Time 15:32 Sent To  
Notes
2013-02-07 12:43:05FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. A LAVATORY IS REQUIRED IN THE ACCESSIBLE RESTROOM
 STALLS.
 FBC ACCESSIBILITY 2010 604.8.1.6 LAVATORY. IN NEW
 CONSTRUCTION, THE WHEELCHAIR ACCESSIBLE TOILET
 COMPARTMENT SHALL CONTAIN AN ACCESSIBLE LAVATORY WITHIN
 IT, WHICH MUST BE AT LEAST 19 INCHES WIDE BY 17 INCHES
 DEEP, NOMINAL SIZE, AND WALL-MOUNTED. THE LAVATORY
 SHALL BE MOUNTED SO AS NOT TO OVERLAP THE CLEAR FLOOR
 SPACE AREAS REQUIRED BY SECTION 604 FOR THE WHEELCHAIR
 ACCESSIBLE TOILET COMPARTMENT AND SHALL COMPLY WITH
 SECTION 606. SUCH LAVATORIES SHALL BE COUNTED AS PART
 OF THE REQUIRED FIXTURE COUNT FOR THE BUILDING. SEE
 ALSO SECTION 213.3.4.
  
 2. SHEET P1.1 IF FPWH IS A WALL HYDRANT, THEY REQUIRE
 SEPARATE SHUT OFF VALVES.
 606.2 LOCATION OF SHUTOFF VALVES. (2) ON THE WATER
 SUPPLY PIPE TO EACH SILLCOCK IN OTHER THAN ONE- AND
 TWO-FAMILY RESIDENTIAL OCCUPANCIES.
  
 3. SHEET P2.1, P5.1 PLEASE SHOW THE KITCHEN MOP SINK
 CONNECTED TO THE GREASE SYSTEM.
 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES REQUIRED.
 A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE
 SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES
 AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS...
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2013-05-31 Cont ID  
Sent By jwitmer Date 2013-05-31 Time 09:20 Rev Time 0.00
Received By jwitmer Date 2013-05-31 Time 09:20 Sent To  
Notes
2013-05-31 09:20:26BUILDING PLAN REVIEW
 PERMIT: 13010628
 ADD: 2471 OKEECHOBEE BLVD
 CONT: PARKWAY CONSTRUCTION
 TEL: (469)322-3758
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 A ROOFING PERMIT WILL BE REQUIRED FOR ALL ROOF WORK
 ASSOCIATED FOR THE NEW OPENINGS WITHIN THE ROOF AND
 CURBS THAT ARE BEING INSTALLED. FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)(D) NOTE:
 FLAT DECKS PLEASE IDENTIFY WHICH SUB-SYSTEM WILL BE
 APPLIED, CIRCLE THE SYSTEM TYPE AND MAXIMUM PRESSURES
 FOR ROOF ZONE 1. IF THE PRESSURES ARE HIGHER IN ZONES 2
 & 3 VERIFY LIMITATIONS TO SEE IF ENHANCED FASTENING CAN
 BE TAKEN AND IF RAS 117 CALCULATIONS ARE REQUIRED BY A
 DESIGN PROFESSIONAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-02-01 Cont ID  
Sent By ajones Date 2013-02-01 Time 15:54 Rev Time 0.00
Received By ajones Date 2013-02-01 Time 15:54 Sent To  
Notes
2013-02-01 15:55:332/1/13- PASSED WITH PROVISO THAT ANY EXTERIOR CHANGES
 TO THE PARKING LOT OR LANDSCAPED AREAS REQUIRES A
 SEPERATE PERMIT.
  
 ANGELLA VANN, PLANNING AND ZONING ADMINISTRATOR
 561-822-1441
  