| 2013-02-08 10:15:07 | BUILDING PLAN REVIEW |
| | PERMIT: 13010628 |
| | ADD: 2471 OKEECHOBEE BLVD |
| | CONT: TBD/ PARKWAY CONSTRUCTION |
| | TEL: (469)322-3758 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | FEB. 08/2013 |
| | ACTION: DENIED |
| | |
| | 1) THE ADDRESS PROVIDED ON THE PLANS AS WELL AS THE |
| | PERMIT APPLICATION IS THE SITE ADDRESS FOR THE WHOLE |
| | PARCEL. THIS TENANT EITHER HAS AN INDIVIDUAL STREET |
| | ADDRESS OR A SUITE NUMBER TO IDENTIFY THE INDIVIDUAL |
| | TENANT SPACE FOR INSPECTION PURPOSES, RECORDS, RECORD |
| | RETENSION AS WELL AS EMERGENCIES. 105.3 ACTION ON |
| | APPLICATION WPB AMENDMENTS TO ADMINISTRATIVE CODE, |
| | CHAPTER 1/ 2010 FBC. |
| | |
| | 2) CHANGE OF OCCUPANCY FROM MERCANTILE TO A2 ASSEMBLY, |
| | ENERGY CALCULATIONS REQUIRED, 2010 FBC-ENERGY CODE 913. |
| | |
| | 3) THESE PLANS APPEAR TO HAVE VARIOUS DETAILS THAT MAY |
| | NOT BE APPLICABLE TO THIS PERMIT. IF THE DETAILS DO NOT |
| | SERVE THIS PROJECT PLEASE EITHER DELETE THE DETAIL OF |
| | CROSS THEM OUT. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. WPB ADMINMENTS TO THE ADMINISTRTIVE CODE |
| | 2010. |
| | |
| | 4) SHEET A1.0 & A1.1 DETAIL # 3 INDICATES A STAGE. |
| | NOTES INDICATE THE STAGE TO BE BUILT BY OTHERS, WILL |
| | THE DESIGN OF THE STAGE BE PART OF THE DESIGNER OF |
| | RECORDS PERMIT SET OF DRAWINGS? IF IT IS NOT THEN IT |
| | SHOULD NOT BE IN THIS PACKAGE. THERE ARE TWO ISSUES AT |
| | HAND WITH THE STAGE; |
| | 4A) NO PLANS INDICATING THE TYPE OF MATERIALS THE STAGE |
| | IS TO BE CREATED FROM, NOR IS THE HEIGTH OF THE STAGE |
| | PROVIDED? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | 4B) HOW VERTICAL ACCESSIBILITY WILL BE ADDRESSED. 2010 |
| | FBC ACCESSIBILITY 201.1.1. |
| | |
| | 5) SHEET A-0.1 & S-2.0 BOTH INDICATE A NEW DOORWAY AND |
| | ACCESSIBLE RAMP. PLEASE REVIEW TTHE 2010 ACCESSIBILITY |
| | CODE 405.7.4.RAMPS, CHANGE IN DIRECTION. THE PLAN DOES |
| | NOT INDICATE A BOTTOM LANDING, IS THERE ENOUGH ROOM? |
| | 2010 ACCESSIBILITY 405.7. |
| | |
| | 6) SHEET A-0.1 & A1.0 BOTH INDICATE THE NEW HANDRAIL |
| | BUT THE PLANS FAIL TO PROVIDE DETAILS FOR THE HANDRAIL |
| | PER 2010 ACCESSIBILITY CODE 405.8. |
| | |
| | 7) SHEET A-3.1 & A-7.1: |
| | 7A) THE PLANS INDICATE A NEW ROOF HATCH, FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS:(31)(A) ACCESS |
| | HATCHES. PLEASE ALSO REVIEW GUARDS 1013.6. |
| | |
| | 7B) A-7.1 & M1.3 BOTH INDICATE A DETAIL FOR RAISED |
| | CURBS, PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE NEW |
| | CURB THAT IS BEING INSTALLED FOR A/C UNIT #4. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 7C) THE PLANS INDICATE THE EXISTING CURBS ARE TO HAVE |
| | AN ADAPTOR OVER THE EXISTING CURB, PLEASE PROVIDE THE |
| | MANUFACTURERS SPECIFICATIONS .HOW THEY WILL BE SECURED |
| | TO THE EXISTING CURB? 107.2.1.3 ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 7D) A-7.1 DETAIL # 3 INDICATES THE USE OF WOOD SLEEPERS |
| | AND PITCH PANS, THIS HAS NOT BEEN ALLOWED IN FLORIDA |
| | SINCE THE 2001 FBC. 2010 FBC-B TABLE 1509.7 PROVIDES |
| | THE REQUIRED HEIGHT OF THE UNIT ABOVE THE ROOF COVERING |
| | DEPENDING ON THE WIDTH OF THE UNIT. |
| | |
| | 7E) A/C STANDS FOR ROOF TOP CONDENSORS. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS: (31)((G) |
| | PRE-ENGINEERED A/C STANDS. |
| | |
| | 7F) ROOF TOP BLOX, AN ENGINEERING LAB TEST REULTS WERE |
| | SUBMITTED IT APPEARS TO BE A SITE SPECIFIC CASE IN |
| | ELLINGTON, MAINE FOR A 150 MPH WIND ZONE. WE DO ACCESPT |
| | NATIONALLY RECONIZED REPORTS FROM THE ICC ER REPORTS, |
| | ERS REPORTS ETC, PLEASE PROVIDE A CURRENT REPORT FROM A |
| | NATIONALLY RECONIZED TESTING AGENCY. |
| | |
| | 8) A ROOFING PERMIT WILL BE REQUIRED FOR ALL ROOF |
| | REPAIRS FOR THE NEW OPENINGS WITHIN THE ROOF AND CURBS |
| | THAT ARE BEING INSTALLED. FLORIDA DEPARTMENT OF |
| | COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES FLAT ROOF |
| | REPAIR AS WELL AS THE METAL FOR THE AWNING DETAIL. |
| | |
| | 9) THE SHEET A-7.2 INDICATES THE USE OF EFIS WALL |
| | INSULATION AND WALL FINISHES, PLEASE PROVIDE THE |
| | PRODUCT APPROVAL FOR EFIS WALL SYSTEMS. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(C) , EFIS SYSTEMS, |
| | |
| | 10) SHEET A-7.4 DETAIL # 13 BOOTHS BY OTHERS. PLEASE |
| | PROVIDE WHAT TYPE OF MATERIALS WILL BE USED IN COVERING |
| | THE BOOTHS. 2010 FBC-B 806.4. |
| | |
| | 11) SHEET A-8.0 THE DOOR SCHEDULE ALL EXIT DOORS WILL |
| | REQUIRE PANIC HARDWARE IT APPEARS DOOR # 1 & 7 DO NOT |
| | INDICATE PANIC HARDWARE IN THE HARDWARE SCHEDULE. DOOR |
| | # 3 INDICATES EXISTING AND DOES NOT LIST ANY HARDWARE. |
| | 2010 FBC-B 1008.1.10. |
| | |
| | 12) SHEET A-9.2 PLEASE REVIEW THE MENS & WOMENS |
| | HANDICAPPED STALL REQUIREMENTS, 2010 FLORIDA |
| | ACCESSIBILITY CODE REQUIRES THE LAV TO BE IN THE SAME |
| | TOILET COMPARTMENT, |
| | SEE 604.8.1.6, 604.8.1.7 |
| | |
| | 13) SHEET A-9.2 INDICATE THE RESTROOMS TO HAVE A TILE |
| | FINISH ON THE WALLS BUT THE PLANS DO NOT PROVIDE WHAT |
| | TYPE OF BACKER BOARD IS TO BE INSTALLED. SEE: |
| | 13A) 210.2 WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF URINALS |
| | AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) |
| | ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, |
| | THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE |
| | THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | 13B) 2509.2 BASE FOR TILE. |
| | GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS, |
| | DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE |
| | SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT |
| | SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288 |
| | OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER |
| | RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE |
| | IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN |
| | SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD |
| | SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| | COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| | GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS. |
| | REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR |
| | WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN |
| | INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840. |
| | |
| | 14) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 14.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 14.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 14.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 14.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 14.5) COMPONENTS & CLADDING PRESSURES POSITVE & |
| | NEGATIVE TABLE 1609.2(2) . PROVIDE PRESSURES FOR ZONES |
| | 1-5 ROOF & WALL ZONES. |
| | |
| | 15) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |